E1.2N 630 Ekip Dip LI 3p F F

Manufactured by:
ABB
Abb

9bca8c0a7336c242ae909b5fd374f2ed87065351 medium
Price (VAT excluded)
€ 6419.70
Nuova Elva code
1SDA070721R1
Manufacturer code
1SDA070721R1
Availability
Send request for quotation

C.BREAKER SACE EMAX2 E1.2N 630 FIXED THREE-POLE WITH FRONT TERMINALS AND SOLID-STATE RELEASE IN AC EKIP/DIP-LI R 630 FITTED WITH: 4 AUXILIARY CONTACT AND C.BREAKER IN POSITION OPEN-CLOSED

Specifications

Ordering

Minimum Order Quantity1 piece
Customs Tariff Number85362090

Dimensions

Product Net Width210 mm
Product Net Height296 mm
Product Net Depth / Length183 mm
Product Net Weight14 kg

Container Information

Package Level 1 Gross Weight16 kg
Package Level 1 EAN8015644745714
Package Level 1 Units1 piece
Package Level 1 Width270 mm
Package Level 1 Height350 mm
Package Level 1 Depth / Length330 mm

Environmental

RoHS StatusFollowing EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019

Additional Information

Current TypeAC
Electrical DurabilityUe =< 440 V 8000 cycleUe = 500 ... 690 V 8000 cycle30 cycles per hour
Mechanical Durability20000 cycle60 cycles per hour
Number of Poles3
Power Loss31 W
Product Main TypeSACE Emax 2
Product NameAir Circuit Breaker
Product TypeAir Circuit Breaker
Rated Service Short-Circuit Breaking Capacity, in % of Icu (Ics)100 %
Rated Current (In)630 A
Rated Voltage (Ur)690 V
Rated Impulse Withstand Voltage (Uimp)acc. to IEC 60947-2 12 kV
Rated Insulation Voltage (Ui)AC 1000 V
Rated Operational Voltage690 V AC
Rated Service Short-Circuit Breaking Capacity (Ics)(220 V AC) 66 kA(230 V AC) 66 kA(380 V AC) 66 kA(400 V AC) 50 kA(415 V AC) 50 kA(440 V AC) 50 kA(500 V AC) 50 kA(660 V AC) 50 kA(690 V AC) 50 kA
Rated Short-time Withstand Current (Icw)for 1 s 50 kAfor 3 s 30 kA
Rated Ultimate Short-Circuit Breaking Capacity (Icu)(400 V AC) 66 kA(415 V AC) 66 kA(440 V AC) 66 kA(500 V AC) 50 kA(525 V AC) 50 kA(690 V AC) 50 kA
Rated Uninterrupted Current (Iu)630 A
ReleaseEkip Dip LI
Release TypeEL
Short-Circuit Performance LevelN
StandardsIEC
Sub-typeE1.2
Terminal Connection TypeFront
VersionF

Classifications

ETIM 4EC000228 - Power circuit-breaker for trafo/generator/installation prot.
ETIM 5EC000228 - Power circuit-breaker for trafo/generator/installation prot.
Object Classification CodeQ
WEEE Category5. Small Equipment (No External Dimension More Than 50 cm)

Other ABB items

Request a quote