E1.2N 1600 Ekip Dip LSI 3p WMP
- Manufactured by:
- ABB
- Price (VAT excluded)
- € 10029.60
- Nuova Elva code
- 1SDA072232R1
- Manufacturer code
- 1SDA072232R1
- Availability
- Send request for quotation
MOVING PART FOR C.BREAKER SACE EMAX2 E1.2N 1600 THREE-POLE WITH SOLID-STATE RELEASE IN AC EKIP/DIP-LSI R 1600 FITTED WITH: 4 AUXILIARY CONTACT AND C.BREAKER IN POSITION OPEN-CLOSED
Specifications
Ordering | |
---|---|
EAN | 8015644760823 |
Minimum Order Quantity | 1 piece |
Customs Tariff Number | 85362090 |
Dimensions | |
Product Net Width | 278 mm |
Product Net Height | 363.5 mm |
Product Net Depth / Length | 271 mm |
Product Net Weight | 18 kg |
Container Information | |
Package Level 1 Depth / Length | 330 mm |
Package Level 1 Gross Weight | 20 kg |
Package Level 1 EAN | 8015644760823 |
Package Level 1 Units | 1 piece |
Package Level 1 Width | 270 mm |
Package Level 1 Height | 350 mm |
Additional Information | |
Current Type | AC |
Electrical Durability | Ue =< 440 V 3000 cycleUe = 500 ... 690 V 6500 cycle30 cycles per hour |
Mechanical Durability | 20000 cycle60 cycles per hour |
Number of Poles | 3 |
Power Loss | 400 W |
Product Main Type | SACE Emax 2 |
Product Name | Air Circuit Breaker |
Product Type | Air Circuit Breaker |
Rated Service Short-Circuit Breaking Capacity, in % of Icu (Ics) | 100 % |
Rated Current (In) | 1600 A |
Rated Voltage (Ur) | 690 V |
Rated Impulse Withstand Voltage (Uimp) | acc. to IEC 60947-2 12 kV |
Rated Insulation Voltage (Ui) | AC 1000 V |
Rated Operational Voltage | 690 V AC |
Rated Service Short-Circuit Breaking Capacity (Ics) | (220 V AC) 66 kA(230 V AC) 66 kA(380 V AC) 66 kA(400 V AC) 50 kA(415 V AC) 50 kA(440 V AC) 50 kA(500 V AC) 50 kA(660 V AC) 50 kA(690 V AC) 50 kA |
Rated Short-time Withstand Current (Icw) | for 1 s 50 kAfor 3 s 30 kA |
Rated Ultimate Short-Circuit Breaking Capacity (Icu) | (400 V AC) 66 kA(415 V AC) 66 kA(440 V AC) 66 kA(500 V AC) 50 kA(525 V AC) 50 kA(690 V AC) 50 kA |
Rated Uninterrupted Current (Iu) | 1600 A |
Release Type | EL |
Standards | IEC |
Sub-type | E1.2 |
Version | W |
Classifications | |
ETIM 4 | EC000228 - Power circuit-breaker for trafo/generator/installation prot. |
ETIM 5 | EC000228 - Power circuit-breaker for trafo/generator/installation prot. |
ETIM 6 | EC000228 - Power circuit-breaker for trafo/generator/installation prot. |
ETIM 7 | EC000228 - Power circuit-breaker for trafo/generator/installation protection |
Object Classification Code | Q |
WEEE Category | 5. Small Equipment (No External Dimension More Than 50 cm) |