F202 AC-25/0,3Residual Current Circuit Breaker

Manufactured by:
ABB
Abb

799aed5e901d90c6b3f66de84b7c3fb8b288de0c medium
Nuova Elva code
F427806
Manufacturer code
2CSF202001R3250
Availability
Standard lead time: 7 days

The RCCBs F200 series assures protection to people and installations against fault current to earth. A large offer for standard instantaneous and selective AC and A types is completed with some configurations for special applications.

Specifications

Technical

StandardsIEC/EN 61008UL 1053
Product NameResidual Current Circuit Breaker
Rated Service Short-Circuit Breaking Capacity (Ics)1 kA
Maximum Surge Current0.25 kA
Leakage Current TypeAC
Rated Frequency (f)50 / 60 Hz
Power Lossat Rated Operating Conditions per Pole 1 W
Power Supply ConnectionArbitrary
Electrical Endurance10000 cycle
Number of Poles2
Operating CharacteristicInstantaneous
Mounting TypeDIN rail
Type of Residual CurrentAC type
Options ProvidedNone
Accessories AvailableYes
Connecting CapacityBusbar 10 mm²Rigid 25 ... 25 mm²Flexible 25 ... 25 mm²
Rated Cross-Section4 - Multi-Wired 0...25 mm²1 - Solid-Core 25...25 mm²
Rated Voltage (Ur)230 V
Rated Operational Voltage230 V
Rated Insulation Voltage (Ui)500 V
Rated Impulse Withstand Voltage (Uimp)4 kV
Rated Current (In)25 A
Rated Residual Current300 mA
Rated Conditional Short-Circuit Current (Inc)10 kA

Environmental

Ambient Temperature-25...55 °C
Ambient Air TemperatureOperation -25...55 °C
Degree of ProtectionIP2X
Pollution Degree2
RoHS StatusFollowing EU Directive 2011/65/EU
Environmental InformationRefer to RoHS

Technical UL/CSA

Maximum Operating Voltage UL/CSA277 V AC

Dimensions

Width in Number of Modular Spacings2
Product Net Width0.035 m
Product Net Height0.085 m
Product Net Depth / Length0.069 m
Product Net Weight0.200 kg
Built-In Depth (t2)69 mm

Container Information

Package Level 1 Unitsbox 1 piece
Package Level 1 Width80 mm
Package Level 1 Height41 mm
Package Level 1 Depth / Length94 mm
Package Level 1 Gross Weight0.235 kg
Package Level 1 EAN8012542780601
Package Level 2 Unitscrate 6 piece
Package Level 2 Width246 mm
Package Level 2 Height94 mm
Package Level 2 Depth / Length80 mm

Ordering

Minimum Order Quantity1 piece
Customs Tariff Number85363030
Country of OriginItaly (IT)
Selling Unit of Measurepiece

Classifications

ETIM 8EC000003 - Residual current circuit breaker (RCCB)
EPLAN Catalog TreeElectrical engineering / Protection devices / Ground fault current circuit breaker
EPLAN Function DefinitionGround fault current circuit-breaker / Ground fault current circuit breakers, 4 connection points / Ground fault current circuit breaker, two-pole 1/2 2/1 3/4 4/3
WEEE Category5. Small Equipment (No External Dimension More Than 50 cm)
WEEE B2C / B2BBusiness To Consumer
CN885363030
Object Classification CodeF

Other ABB items