MO165-20 Manual Motor Starter Magnetic Only
- Manufactured by:
- ABB
The MO165 manual motor starter magnetic only is a compact and powerful range for motor protection up to 45 kW (400 V) in width of 55 mm. The devices are used to manually switch on and off loads/motors and to protect them reliably and without the need for a fuse from short-circuits. The manual motor starter offers a rated service short-circuit breaking capacity up to 100 kA at 400 V AC. A combination together with overload relays or motor controllers allows the protection of motors. Further features are the built-in disconnect function, trip-free mechanism and a rotary handle with a clear switch position indication. The manual motor starters magnetic only are suitable for three- and single-phase applications. The handle is lockable to protect against unauthorized changes. Auxiliary contacts, signaling contacts, undervoltage releases, shunt trips, 3-phase bus bars and power in-feed blocks are available as accessory.
Specifications
Ordering | |
---|---|
Minimum Order Quantity | 1 piece |
Customs Tariff Number | 85362010 |
Dimensions | |
Product Net Width | 55 mm |
Product Net Height | 142.65 mm |
Product Net Depth / Length | 122.1 mm |
Product Net Weight | 0.95 kg |
Technical | |
Rated Operational Power AC-3 (Pe) | (400 V) Three Phase 7.5 kW |
Rated Operational Power AC-3e (Pe) | (400 V) Three Phase 7.5 kW |
Rated Operational Voltage | Main Circuit 690 V ACMain Circuit 250 V DC |
Rated Operational Current (Ie) | 20 A |
Rated Operational Current AC-3 (Ie) | 20 A |
Rated Operational Current AC-3e (Ie) | 20 A |
Rated Operational Current DC-5 (Ie) | 20 A |
Rated Frequency (f) | Main Circuit 50 HzMain Circuit 60 Hz |
Rated Impulse Withstand Voltage (Uimp) | Main Circuit 8 kV |
Rated Insulation Voltage (Ui) | 1000 V |
Power Loss | 3.72 W |
Number of Poles | 3 |
Conventional Free-air Thermal Current (Ith) | Main Circuit 20 A |
Degree of Protection | Housing IP20Main Circuit Terminals IP10 |
Pollution Degree | 3 |
Electrical Durability | 25000 cycle |
Mechanical Durability | 50000 cycle |
Terminal Type | Screw Terminals |
Connecting Capacity Main Circuit | Flexible with Ferrule 1/2x 1 ... 35 mm²Flexible with Insulated Ferrule 1/2x 1 ... 35 mm²Flexible 1/2x 1 ... 35 mm²Rigid 1/2x 1 ... 4 mm²Solid 1/2x 1 ... 4 mm²Stranded 1/2x 1 ... 50 mm² |
Tightening Torque | Main Circuit 4 N·m |
Wire Stripping Length | Main Circuit 16 mm |
Recommended Screw Driver | Pozidriv 2 |
Mounting Position | Position 1 to 6 |
Mounting on DIN Rail | TH35-15 (35 x 15 mm Mounting Rail) acc. to IEC 60715TH35-7.5 (35 x 7.5 mm Mounting Rail) acc. to IEC 60715 |
Minimum Mounting Distance | Electrical Conductive Board, Horizontal - Up to 1000 V 1.5 mmElectrical Conductive Board, Horizontal - Up to 400 V 0 mmElectrical Conductive Board, Horizontal - Up to 690 V 1.5 mmElectrical Conductive Board, Vertical 75 mmOther Device Same Type, Horizontal 0 mmOther Device Same Type, Vertical 150 mm |
Actuator Type | Rotary Handle |
Contact Position Indication | ON / OFF / TRIP |
Standards | CSA 22.2 No. 14IEC/EN 60947-1IEC/EN 60947-2IEC/EN 60947-4-1UL 60947-4-1 |
Remarks | For overload protection of the motors, an appropriate thermal or electronic overload relays must be used |
Rated Service Short-Circuit Breaking Capacity (Ics) | (230 V AC) 100 kA(250 V DC) 3 Poles in Series 100 kA(400 V AC) 100 kA(440 V AC) 75 kA(500 V AC) 40 kA(690 V AC) 10 kA |
Rated Ultimate Short-Circuit Breaking Capacity (Icu) | (230 V AC) 100 kA(250 V DC) 100 kA(400 V AC) 100 kA(440 V AC) 75 kA(500 V AC) 40 kA(690 V AC) 10 kA |
Rated Instantaneous Short-Circuit Current Setting (Ii) | 300 A |
Setting Range | None |
Technical UL/CSA | |
Short-Circuit Current Rating (SCCR) | Manual Self-Protected Combination Controllers (Type E), (480Y / 277 V AC) 65 kAManual Self-Protected Combination Controllers (Type E), (600Y / 347 V AC) 30 kAAny UL Listed Fuses or Circuit-Breakers, Group Installations (480 V AC) 65 kAAny UL Listed Fuses or Circuit-Breakers, Group Installations (600 V AC) 30 kAAny UL Listed Fuses or Circuit-Breakers, Motor Disconnect (480 V AC) 65 kAAny UL Listed Fuses or Circuit-Breakers, Motor Disconnect (600 V AC) 30 kAAny UL Listed Fuses or Circuit-Breakers, Tap Conductor Protection in Group Installations (480Y / 277 V AC) 65 kAAny UL Listed Fuses or Circuit-Breakers, Tap Conductor Protection in Group Installations (600Y / 347 V AC) 30 kA |
Maximum Operating Voltage UL/CSA | Main Circuit 600 V AC |
Ampere Rating UL/CSA | 20 A |
Horsepower Rating UL/CSA | (200 V AC) Three Phase 5 Hp(208 V AC) Three Phase 5 Hp(220 ... 240 V AC) Three Phase 5 Hp(440 ... 480 V AC) Three Phase 10 Hp(550 ... 600 V AC) Three Phase 15 Hp |
Full Load Amps Motor Use | (200 V AC) Three Phase 17.5 A(208 V AC) Three Phase 16.7 A(220 ... 240 V AC) Three Phase 15.2 A(440 ... 480 V AC) Three Phase 14 A(550 ... 600 V AC) Three Phase 17 A |
Locked Rotor Amps | (200 V AC) Three Phase 105.8 A(208 V AC) Three Phase 102 A(220 ... 240 V AC) Three Phase 92 A(440 ... 480 V AC) Three Phase 81 A(550 ... 600 V AC) Three Phase 93 A |
General Use Rating UL/CSA | (600 V AC) 20 A |
Connecting Capacity Main Circuit UL/CSA | Flexible 1/2x 16-0 AWGStranded 1/2x 16-0 AWG |
Tightening Torque UL/CSA | Main Circuit 35 in·lb |
Environmental | |
Ambient Air Temperature | Operation -25 ... +60 °COperation Compensated -25 ... +60 °CStorage -50 ... +80 °C |
Ambient Air Temperature Compensation | No |
Maximum Operating Altitude Permissible | 2000 m |
Resistance to Shock acc. to IEC 60068-2-27 | 11 ms Pulse 25g |
Resistance to Vibrations acc. to IEC 60068-2-6 | 5g / 3 ... 150 Hz |
RoHS Status | Following EU Directive 2011/65/EU |
Container Information | |
Package Level 1 Units | box 1 piece |
Package Level 1 Width | 78 mm |
Package Level 1 Depth / Length | 155 mm |
Package Level 1 Height | 155 mm |
Package Level 1 Gross Weight | 1.1 kg |
Package Level 1 EAN | 4013614486135 |
Package Level 2 Units | carton 12 piece |
Package Level 2 Width | 330 mm |
Package Level 2 Depth / Length | 400 mm |
Package Level 2 Height | 320 mm |
Package Level 2 Gross Weight | 13 kg |
Package Level 2 EAN | 4013614503993 |
Classifications | |
Object Classification Code | F |
ETIM 5 | EC000074 - Motor protective circuit-breaker |
eClass | V11.0 : 27370401 |
IDEA Granular Category Code (IGCC) | 4845 >> 3 Pole Motor Circuit Protector Circuit Breakers |
E-Number (Finland) | 3707292 |
E-Number (Sweden) | 3110059 |