The MO165 manual motor starter magnetic only is a compact and powerful range for motor protection up to 45 kW (400 V) in width of 55 mm. The devices are used to manually switch on and off loads/motors and to protect them reliably and without the need for a fuse from short-circuits. The manual motor starter offers a rated service short-circuit breaking capacity up to 100 kA at 400 V AC. A combination together with overload relays or motor controllers allows the protection of motors. Further features are the built-in disconnect function, trip-free mechanism and a rotary handle with a clear switch position indication. The manual motor starters magnetic only are suitable for three- and single-phase applications. The handle is lockable to protect against unauthorized changes. Auxiliary contacts, signaling contacts, undervoltage releases, shunt trips, 3-phase bus bars and power in-feed blocks are available as accessory.

Specifications

Ordering

Minimum Order Quantity1 piece
Customs Tariff Number85362010

Dimensions

Product Net Width55 mm
Product Net Height142.65 mm
Product Net Depth / Length122.1 mm
Product Net Weight0.95 kg

Technical

Rated Operational Power AC-3 (Pe)(400 V) Three Phase 7.5 kW
Rated Operational Power AC-3e (Pe)(400 V) Three Phase 7.5 kW
Rated Operational VoltageMain Circuit 690 V ACMain Circuit 250 V DC
Rated Operational Current (Ie)20 A
Rated Operational Current AC-3 (Ie)20 A
Rated Operational Current AC-3e (Ie)20 A
Rated Operational Current DC-5 (Ie)20 A
Rated Frequency (f)Main Circuit 50 HzMain Circuit 60 Hz
Rated Impulse Withstand Voltage (Uimp)Main Circuit 8 kV
Rated Insulation Voltage (Ui)1000 V
Power Loss3.72 W
Number of Poles3
Conventional Free-air Thermal Current (Ith)Main Circuit 20 A
Degree of ProtectionHousing IP20Main Circuit Terminals IP10
Pollution Degree3
Electrical Durability25000 cycle
Mechanical Durability50000 cycle
Terminal TypeScrew Terminals
Connecting Capacity Main CircuitFlexible with Ferrule 1/2x 1 ... 35 mm²Flexible with Insulated Ferrule 1/2x 1 ... 35 mm²Flexible 1/2x 1 ... 35 mm²Rigid 1/2x 1 ... 4 mm²Solid 1/2x 1 ... 4 mm²Stranded 1/2x 1 ... 50 mm²
Tightening TorqueMain Circuit 4 N·m
Wire Stripping LengthMain Circuit 16 mm
Recommended Screw DriverPozidriv 2
Mounting PositionPosition 1 to 6
Mounting on DIN RailTH35-15 (35 x 15 mm Mounting Rail) acc. to IEC 60715TH35-7.5 (35 x 7.5 mm Mounting Rail) acc. to IEC 60715
Minimum Mounting DistanceElectrical Conductive Board, Horizontal - Up to 1000 V 1.5 mmElectrical Conductive Board, Horizontal - Up to 400 V 0 mmElectrical Conductive Board, Horizontal - Up to 690 V 1.5 mmElectrical Conductive Board, Vertical 75 mmOther Device Same Type, Horizontal 0 mmOther Device Same Type, Vertical 150 mm
Actuator TypeRotary Handle
Contact Position IndicationON / OFF / TRIP
StandardsCSA 22.2 No. 14IEC/EN 60947-1IEC/EN 60947-2IEC/EN 60947-4-1UL 60947-4-1
RemarksFor overload protection of the motors, an appropriate thermal or electronic overload relays must be used
Rated Service Short-Circuit Breaking Capacity (Ics)(230 V AC) 100 kA(250 V DC) 3 Poles in Series 100 kA(400 V AC) 100 kA(440 V AC) 75 kA(500 V AC) 40 kA(690 V AC) 10 kA
Rated Ultimate Short-Circuit Breaking Capacity (Icu)(230 V AC) 100 kA(250 V DC) 100 kA(400 V AC) 100 kA(440 V AC) 75 kA(500 V AC) 40 kA(690 V AC) 10 kA
Rated Instantaneous Short-Circuit Current Setting (Ii)300 A
Setting RangeNone

Technical UL/CSA

Short-Circuit Current Rating (SCCR)Manual Self-Protected Combination Controllers (Type E), (480Y / 277 V AC) 65 kAManual Self-Protected Combination Controllers (Type E), (600Y / 347 V AC) 30 kAAny UL Listed Fuses or Circuit-Breakers, Group Installations (480 V AC) 65 kAAny UL Listed Fuses or Circuit-Breakers, Group Installations (600 V AC) 30 kAAny UL Listed Fuses or Circuit-Breakers, Motor Disconnect (480 V AC) 65 kAAny UL Listed Fuses or Circuit-Breakers, Motor Disconnect (600 V AC) 30 kAAny UL Listed Fuses or Circuit-Breakers, Tap Conductor Protection in Group Installations (480Y / 277 V AC) 65 kAAny UL Listed Fuses or Circuit-Breakers, Tap Conductor Protection in Group Installations (600Y / 347 V AC) 30 kA
Maximum Operating Voltage UL/CSAMain Circuit 600 V AC
Ampere Rating UL/CSA20 A
Horsepower Rating UL/CSA(200 V AC) Three Phase 5 Hp(208 V AC) Three Phase 5 Hp(220 ... 240 V AC) Three Phase 5 Hp(440 ... 480 V AC) Three Phase 10 Hp(550 ... 600 V AC) Three Phase 15 Hp
Full Load Amps Motor Use(200 V AC) Three Phase 17.5 A(208 V AC) Three Phase 16.7 A(220 ... 240 V AC) Three Phase 15.2 A(440 ... 480 V AC) Three Phase 14 A(550 ... 600 V AC) Three Phase 17 A
Locked Rotor Amps(200 V AC) Three Phase 105.8 A(208 V AC) Three Phase 102 A(220 ... 240 V AC) Three Phase 92 A(440 ... 480 V AC) Three Phase 81 A(550 ... 600 V AC) Three Phase 93 A
General Use Rating UL/CSA(600 V AC) 20 A
Connecting Capacity Main Circuit UL/CSAFlexible 1/2x 16-0 AWGStranded 1/2x 16-0 AWG
Tightening Torque UL/CSAMain Circuit 35 in·lb

Environmental

Ambient Air TemperatureOperation -25 ... +60 °COperation Compensated -25 ... +60 °CStorage -50 ... +80 °C
Ambient Air Temperature CompensationNo
Maximum Operating Altitude Permissible2000 m
Resistance to Shock acc. to IEC 60068-2-2711 ms Pulse 25g
Resistance to Vibrations acc. to IEC 60068-2-65g / 3 ... 150 Hz
RoHS StatusFollowing EU Directive 2011/65/EU

Container Information

Package Level 1 Unitsbox 1 piece
Package Level 1 Width78 mm
Package Level 1 Depth / Length155 mm
Package Level 1 Height155 mm
Package Level 1 Gross Weight1.1 kg
Package Level 1 EAN4013614486135
Package Level 2 Unitscarton 12 piece
Package Level 2 Width330 mm
Package Level 2 Depth / Length400 mm
Package Level 2 Height320 mm
Package Level 2 Gross Weight13 kg
Package Level 2 EAN4013614503993

Classifications

Object Classification CodeF
ETIM 5EC000074 - Motor protective circuit-breaker
eClassV11.0 : 27370401
IDEA Granular Category Code (IGCC)4845 >> 3 Pole Motor Circuit Protector Circuit Breakers
E-Number (Finland)3707292