Miniature Circuit Breaker - S200M - 2P - C - 16 A
- Manufactured by:
- ABB
System pro M compact S200M miniature circuit breakers are current limiting. They have two different tripping mechanisms, the delayed thermal tripping mechanism for overload protection and the electromechanic tripping mechanism for short circuit protection. They are available in different characteristics (B,C,D,K,Z), configurations (1P,1P+N,2P,3P,3P+N,4P), breaking capacities (up to 10 kA at 230/400 V AC) and rated currents (up to 63A). All MCBs of the product range S200M comply with IEC/EN 60898-1 and IEC/EN 609 47-2, allowing the use for residential, commercial and industrial applications. Bottom-fitting auxiliary contact can be mounted on S200M to save 50% space.
Specifications
Technical | |
---|---|
Standards | IEC/EN 60898-1IEC/EN 60947-2 |
Product Name | Miniature Circuit Breaker |
Rated Current (In) | 16 A |
Rated Short-Circuit Capacity (Icn) | (230 V AC) 10 kA(400 V AC) 10 kA |
Rated Ultimate Short-Circuit Breaking Capacity (Icu) | (230 V AC) 25 kA(400 V AC) 15 kA(440 V AC) 15 kA |
Rated Conditional Short-Circuit Current (Inc) | (230 V) 15 kA(400 V) 25 kA |
Rated Service Short-Circuit Breaking Capacity (Ics) | (230 V AC) 7.5 kA |
Frequency (f) | 50 Hz |
Rated Frequency (f) | 50 / 60 Hz |
Power Loss | 5 Wat Rated Operating Conditions per Pole 2.5 W |
Power Supply Connection | Arbitrary |
Contact Position Indication | Red ON / Green OFF |
Tripping Characteristic | C |
Energy Limiting Class | 3 |
Electrical Endurance | 20000 AC cycle |
Mechanical Endurance (Nendu) | 20000 cycle |
Number of Poles | 2 |
Number of Protected Poles | 2 |
Overvoltage Category | III |
Product Range | S200M |
Tightening Torque | 2.8 N·m |
Screw Terminal Type | Failsafe Bi-directional Cylinder-lift Terminal |
Actuator Marking | I / O |
Rated Voltage (Ur) | 400 V AC |
Actuator Material | Insulation Group II, Black, Sealable |
Housing Material | Insulation Group II, RAL 7035 |
Mounting on DIN Rail | TH35-7.5 (35 x 7.5 mm Mounting Rail) acc. to IEC 60715TH35-15 (35 x 15 mm Mounting Rail) acc. to IEC 60715 |
Mounting Position | Any |
Recommended Screw Driver | Pozidriv 2 |
Accessories Available | Yes |
Connecting Capacity | Busbar 10 / 10 mm²Flexible with Ferrule 0.75 ... 25 mm²Flexible 0.75 ... 25 mm²Rigid 0.75 ... 35 mm²Stranded 0.75 ... 35 mm² |
Installation Size | acc. to DIN 43880 1 |
Terminal Type | Screw Terminals |
Rated Operational Voltage | acc. to IEC 60898-1 400 V ACacc. to IEC 60947-2 440 V AC |
Operational Voltage | Maximum (Incl. Tolerance) 125 V DCMaximum (Incl. Tolerance) 440 V ACMinimum 12 V ACMinimum 12 V DC |
Rated Insulation Voltage (Ui) | acc. to IEC/EN 60664-1 440 V |
Rated Impulse Withstand Voltage (Uimp) | 4 kVat 2000 m 5 kVat Sea Level 6.2 kV |
Dielectric Test Voltage | 50/60 Hz, 1 min: 2 kV |
Input Voltage Type | AC/DC |
Environmental | |
Ambient Air Temperature | Operation -25 ... +55 °CStorage -40 ... +70 °C |
Reference Ambient Air Temperature | 30 °C |
Degree of Protection | IP20Enclosure with Cover IP40 |
Pollution Degree | 3 |
Environmental Conditions | 28 cycleswith 55 °C / 90-96 %and 25 °C / 95-100 % |
Resistance to Vibrations acc. to IEC 60068-2-6 | 5g, 20 cycles at 5 ... 150 ... 5 Hz with load 0.8 In |
Resistance to Shock acc. to IEC 60068-2-27 | 25g / 2 shocks / 13 ms |
RoHS Status | Following EU Directive 2011/65/EU |
Environmental Information | 2CDK400030D0201 |
Technical UL/CSA | |
Maximum Operating Voltage UL/CSA | 125 V DC480Y/277 V AC |
Interrupting Rating acc. to UL1077 | (125 V DC) 10 kA(277 V AC) 6 kA(480Y / 277 V AC) 6 kA |
Connecting Capacity UL/CSA | Busbar 14-8 AWGConductor 14-4 AWG |
Tightening Torque UL/CSA | 18 in·lb |
Dimensions | |
Width in Number of Modular Spacings | 2 |
Product Net Width | 35 mm |
Product Net Height | 88 mm |
Product Net Depth / Length | 69 mm |
Product Net Weight | 0.25 kg |
Pole Net Weight | 0.115 kg |
Built-In Depth (t2) | 69 mm |
Container Information | |
Package Level 1 Units | carton 5 piece |
Package Level 1 Width | 92 mm |
Package Level 1 Height | 80 mm |
Package Level 1 Depth / Length | 183 mm |
Package Level 1 Gross Weight | 1.3 kg |
Package Level 1 EAN | 4016779605694 |
Package Level 2 Units | carton 60 piece |
Package Level 2 Width | 275 mm |
Package Level 2 Height | 210 mm |
Package Level 2 Depth / Length | 400 mm |
Package Level 2 Gross Weight | 15.4 kg |
Package Level 2 EAN | 4016779977272 |
Ordering | |
Minimum Order Quantity | 1 piece |
Customs Tariff Number | 85362010 |
E-Number (Finland) | 3210798 |
E-Number (Sweden) | 2101227 |
Country of Origin | Germany (DE) |
Selling Unit of Measure | piece |
Classifications | |
ETIM 8 | EC000042 - Miniature circuit breaker (MCB) |
EPLAN Catalog Tree | Electrical engineering / Protection devices / General |
EPLAN Function Definition | Circuit breaker / Double circuit-breaker / Double circuit breaker 1_2_3_4 |
WEEE Category | 5. Small Equipment (No External Dimension More Than 50 cm) |
WEEE B2C / B2B | Business To Consumer |
CN8 | 8536 20 10 |
eClass | V11.0 : 27141901 |
Object Classification Code | F |