XT1N 160 TMD 160-1600 3p F F

Manufactured by:
ABB
Abb

2b96614d4b892b52c0ee67e3e1a540779d98984f medium
Nuova Elva code
XT1N160TMD3
Manufacturer code
1SDA067418R1
Availability
Send request for quotation

C.BREAKER TMAX XT1N 160 FIXED THREE-POLE WITH FRONT TERMINALS AND THERMOMAGNETIC RELEASE TMD R 160-1600 A

Specifications

Ordering

E-Number (Finland)3640521
E-Number (Sweden)3182427
Minimum Order Quantity1 piece
Customs Tariff Number85362090

Dimensions

Product Net Width76.2 mm
Product Net Height130 mm
Product Net Depth / Length70 mm
Product Net Weight1.094 kg

Container Information

Package Level 1 Height135 mm
Package Level 1 Depth / Length143 mm
Package Level 1 Gross Weight1.143 kg
Package Level 1 EAN8015644013127
Package Level 1 Units1 piece
Package Level 1 Width128 mm

Environmental

RoHS StatusFollowing EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019

Additional Information

Circuit Breaker Type to be AssociatedPower Distribution
Current TypeAC/DC
Electrical Durability120 cycles per hour8000 cycle
Mechanical DurabilityNr. Operations 240 cycles per hourNr. Operations 25000 cycle
Number of Poles3
Opening TimeCB with SOR 15 msCB with UVR 15 ms
Order Multiple1 piece
Power Lossat Rated Operating Conditions per Pole 15 W
Product Main TypeSACE Tmax XT
Product NameLeistungsschalter
Product TypeCB
Rated Current (In)160 A
Rated Frequency (f)50 / 60 Hz
Rated Voltage (Ur)690 V
Rated Impulse Withstand Voltage (Uimp)8 kV
Rated Instantaneous Short-Circuit Current Setting (Ii)1600 A
Rated Insulation Voltage (Ui)800 V
Rated Operational Voltage690 V AC500 V DC
Rated Service Short-Circuit Breaking Capacity (Ics)(220 V AC) 50 kA(230 V AC) 50 kA(240 V AC) 50 kA(380 V AC) 36 kA(415 V AC) 36 kA(440 V AC) 18 kA(500 V AC) 15 kA(525 V AC) 11 kA(690 V AC) 5 kA(250 V DC) 2 Poles in Series 36 kA(500 V DC) 3 Poles in Series 36 kA
Rated Ultimate Short-Circuit Breaking Capacity (Icu)(220 V AC) 65 kA(230 V AC) 65 kA(240 V AC) 65 kA(380 V AC) 36 kA(415 V AC) 36 kA(440 V AC) 36 kA(500 V AC) 30 kA(525 V AC) 22 kA(690 V AC) 6 kA(250 V DC) 2 Poles in Series 36 kA(500 V DC) 3 Poles in Series 36 kA
Rated Uninterrupted Current (Iu)160 A
ReleaseTMD
Release TypeTM
Setting Range112...160 A
Short-Circuit Performance LevelN
StandardsIEC
Sub-typeXT1
Terminal Connection TypeFixed Circuit-Breakers
VersionF

Classifications

ETIM 4EC000228 - Power circuit-breaker for trafo/generator/installation prot.
ETIM 5EC000228 - Power circuit-breaker for trafo/generator/installation prot.
Object Classification CodeQ
WEEE Category5. Small Equipment (No External Dimension More Than 50 cm)

Other ABB items