HV fuse, DIN 43625 , VDE0670 T402, 7,2kV 63A, 192mm, 45mm, medium striker 80N
- Manufactured by:
- Mersen/Ferraz Shawmut
- Price (VAT excluded)
- € 151.51
- Nuova Elva code
- M1000235
- Manufacturer code
- M1000235
- Availability
- Send request for quotation
Mersen HV fuse-links have been used for reliable protection in high-voltage switchgear and controlgear and high-voltage systems for decades. Limitor®-PD HV fuses are back-up fuses as defined in the standards IEC 60282-1 and VDE 0670 T402 and dedicated to protect transformers against effects of short-circuit currents. The VDE 0670 T402 defines fuses between 6.3A and 160A, for other ratings, thanks to consult Limitor®-P HV fuses range. To guarantee high quality, Mersen uses the best materials fuse-elements are in pure silver, caps are in copper coated with silver and bodies are in ceramic.
Features
High current limitation
Low switching voltage
Quick breaking
medium striker 80N/30mm
Energy efficency
New cap design for a better compatibility with all types of clips
and easier assembly
Coordination with IEC 60787, IEC 62271-105, IEC/TR 62655
Indoor and outdoor applications
IEC 60282-1
VDE 0670 part 4
VDE 0670 part 402
DIN 43625
Specifications
Amperage | 63 A |
---|---|
Country of Origin | Hungary |
Diameter | 2.56 in |
Mounting Type | Clip |
Terminal Material | Silver-Plated Copper |
Terminal Type | Cylindrical |
Specifications | |
Ampere Rating | 63 A |
Product Brand | Limitor® |
Body Insulating Material | Ceramic |
Connection Terminal Material | Silver-Plated Copper |
Connection Terminal Type | Cylindrical |
Fuse Size | d=65mm, L=192mm |
Mounting | Clip |
Rated Voltage Ac Iec | 7.2 kV |
Ac Max I R Breaking Capacity I1 | 63 kA |
Product Diameter | 2.56 in |
Ac Min Interrupting Rating Mbc | 220 A |
Clearing I2T At Rated Voltage | 61.7 kA²s |
Power Dissipation At Rated Current Value | 60 W |
Country Of Origin | HU |
Product Line | Limitor®- PD Back-up Fuses, without Controlled Power Dissipation |