MULTIVERT 1000A, single pole switching main incomer, multiple termination
- Manufactured by:
- Mersen/Ferraz Shawmut
- Price (VAT excluded)
- € 872.28
- Nuova Elva code
- N1023121
- Manufacturer code
- N1023121
- Availability
- Send request for quotation
MULTIVERT® NH vertical fuse switch disconnectors meet all functions of NH fuse switch disconnectors. They are designed for installation on to bus bars in triple pole arrangements. MULTIVERT® main incomers 1000A are for installation on to 185mm bus bar systems. They are ready fitted with solild links 1000A. The system is a modular system, that allows the installation of individual components. MULTIVERT® offer the user the possibility of fast and easy installation as well as a high degree of protection during installation and maintenance.
Features
Installation on to 185 mm bus bar system
Suitable for top/bottom cable terminal connections
With installed cover shroud
Terminal lugs for cable terminations of large cross sections - multiple termination
With ready fitted 1000 A solid links
Safe on load connection/disconnection in accordance with IEC 60947-3
IEC/EN 60 947-3
Specifications
Country of Origin | Czech Republic |
---|---|
Frequency | 50 Hz |
Number of Poles | 3 |
Specifications | |
Frequency Hz | 50 ... 60 Hz Hz |
Product Line | MULTIVERT® 1000A , Main Incomer, 690VAC |
Product Brand | MULTIVERT® |
Installation Mounting | Bus Bar Installation |
Number Of Poles | 3-Pole |
Utilization Category | AC 21 B @ Ue = AC 400 V; Ie = 1000 A |
Utilization Category 2 | AC 20 B @ Ue = AC 690 V; Ie = 1000 A |
Switchability | 1 x triple pole, 3 x single pole |
Conventional Free Air Thermal Current - Solid Links | 1000 |
Max Power Dissipation Of Solid Links Pn | 12 W |
Rated Impulse Withstand Voltage | 8 kV |
Rated Insulation Voltage | 1000 V |
Rated Voltage Ac Iec | 690 V |
Rated Short Circuit Making Capacity With Solid Links Icm | 15 kA |
Country Of Origin | CZ |