Low power loss MV fuse 24kV 10A for transformer UTE 55mm 520mm with striker
- Manufactured by:
- Mersen/Ferraz Shawmut
- Price (VAT excluded)
- € 257.84
- Nuova Elva code
- T1045206
- Manufacturer code
- T1045206
- Availability
- Send request for quotation
FR-type fuses are designed to protect HV/LV power distribution transformers. Designed to be coordinated with other equipment, these current limiting fuse-links interrupt fault currents before they reach their peak. The fault current is interrupted inside the fuse-link body and although this is very fast, there is no sign of it outside. The 24kV fuses were specially designed with very low power losses, for use in SF6-insulated or compact air-insulated fused switchgear combinations The main elements in these fuses are a barrel of class F insulating synthetic material, nickel plated aluminium end contacts, pure silver fuse elements and a composite material fuse element holder to withstand high temperatures. Thanks to their structure, based on a synthetic material, FR fuse-links are the perfect answer to the stress involved in use inside HV bays and fuse-link chambers.
Features
Outstanding withstand to operating stresses
100% synthetic structure
Reduce power losses by 30 to 40% (24kV)
High breaking capacity
High current limitation
EDF Approval which guarantees high performances and quality of fuses manifactured (24kV)
IEC 62271-105
IEC 62271-107
IEC 60787
IEC/TR 62655
IEC 60282-1
UTE C64-210
Specifications
Amperage | 10 A |
---|---|
Country of Origin | France |
Diameter | 2.17 in |
Mounting Type | Clip |
Terminal Material | Nickel-Plated Aluminum |
Terminal Type | Cylindrical |
Specifications | |
Average type striker | force 1 ±0.5 Joules |
Country Of Origin | FR,HU |
Product Line | Limitor® - NF/UTE Back-up Fuses, 7,2kV to 24kV - Type FR |
Product Brand | Limitor® |
Body Insulating Material | Class F insulating synthetic material |
Connection Terminal Material | Nickel-Plated Aluminum |
Connection Terminal Type | Cylindrical |
Fuse Size | d=55mm, L=520mm |
Mounting | Clip |
Ampere Rating | 10 A |
Rated Voltage Ac Iec | 24 kV |
Ac Max I R Breaking Capacity I1 | 12.5 kA |
Product Diameter | 2.17 in |
Ac Min Interrupting Rating Mbc | 50 A |
Clearing I2T At Rated Voltage | 1.3 kA²s |
Power Dissipation At Rated Current Value | 25 W |