Dupline Repeater

Manufactured by:
CARLO GAVAZZI PANTEC
Carlo gavazzi

7f873d59c3e97e97d3cfa1e863cf3882c8c00d54 medium
Nuova Elva code
D38920000024
Manufacturer code
D38920000024
Availability
Send request for quotation

The Dupline® Repeater is used to increase the distance in a Dupline® network. Furthermore, it can be used as a “Power-booster” in sections with several Dupline®-supplied units.

Features

  • Repeaters make any transmission-distance possible (cascading of repeaters possible)

  • Power-booster for applications with several Dupline®-supplied units

  • Minimized delay (max. 1 Dupline® scan)

  • Number of channels adjusted automatically

  • H8-housing

  • LED-indication for power supply, primary Dupline® OK and secondary Dupline® (follows Dupline® carrrier)

  • Built-in channel generator function for secondary Dupline®

  • AC power supply

  • The Dupline® repeater is used to increase the distance in a Dupline® network. Furthermore, it can be used as “Power-booster” in sections with several Dupline® supplied units.

  • The repeater introduces a delay of 1 Dupline® scan when transferring pulses from se-condary Dupline® to primary Dupline®, while pulses from primary Dupline® to secondary Dupline® are transferred with a max. delay of 1 ms.

  • When using analog transmission including synchronizer it is necessary to be cautious due to the above mentioned delay. In this case the analog transmitter should not be connected on the secondary side. On the other hand the synchronizer and the analog receivers can be placed without restrictions.

  • By application of the Dupline® repeater there are no problems when transferring the functions of the master generator.

  • Concerning the numbers of channels the repeater adjusts itself based on numbers of channels on the input side of the Dupline® network.

  • The repeater has a built-in channel generator function for the secondary Dupline®. This channel generator function locks itself on to the function of the channel generator on the primary side.

Specifications

Frequency65 Hz
MaterialPC/ABS CYCOLOY C 2100
Output Voltage8.2 V
Protection RatingIP 40
Voltage24 V
Weight485 g

Overview

Supply24 VAC

Input (Primary Dupline)

Dielectric voltage Primary Dupline to Secondary Dupline®≥ 2 kVAC (rms)

Output (Secondary Dupline)

Number of outputs1
Output voltage8.2 VDC
Current≤ 45 mA
Short-circuit protection≤ 60 s
Output impedance≤ 15 Ω
Sequence timeFollows primary Dupline®
Distance to transmitters100%

Dupline Transmission Delay From

Primary to secondary1 mSec
Secondary to primarymax 1 Dupline® scan 136 mSec

Supply Specifications

Power supplyOvervoltage cat. III (IEC 60664)
Rated operational voltage through term. 21 & 2224 VAC, ±15%
Frequency45 to 65 Hz
Voltage interruption≤ 40 ms
Rated operational power6 VA
Power dissipation≤ 7 W
Rated impulse withstand voltage800 V

Dielectric Voltage

Supply - Primary Dupline®≥ 4 kVAC (rms)
Supply - Secondary Dupline®≥ 4 kVAC (rms)

General Specifications

Power ON delay≤ 5 s
Indication for Supply ONLED, green
Indication for Primary Dupline® OKLED, yellow
Indication for Secondary Dupline® carrierLED, yellow
DimensionsH8-housing
MaterialPC/ABS CYCOLOY C 2100
Weight485 g
MTBF65,000 hours

Environment

Degree of protectionIP 40
Pollution degree3 (IEC 60664)
Operating temperature0° to +50°C (+32° to +122°F)
Storage temperature-50° to +85°C (-58° to +185°F)

Mechanical Resistance

Shock15 G (11 ms)
Vibration2 G (6 to 55 Hz)

Docs