Dupline Repeater
- Manufactured by:
- CARLO GAVAZZI PANTEC
The Dupline® Repeater is used to increase the distance in a Dupline® network. Furthermore, it can be used as a “Power-booster” in sections with several Dupline®-supplied units.
Features
Repeaters make any transmission-distance possible (cascading of repeaters possible)
Power-booster for applications with several Dupline®-supplied units
Minimized delay (max. 1 Dupline® scan)
Number of channels adjusted automatically
H8-housing
LED-indication for power supply, primary Dupline® OK and secondary Dupline® (follows Dupline® carrrier)
Built-in channel generator function for secondary Dupline®
AC power supply
The Dupline® repeater is used to increase the distance in a Dupline® network. Furthermore, it can be used as “Power-booster” in sections with several Dupline® supplied units.
The repeater introduces a delay of 1 Dupline® scan when transferring pulses from se-condary Dupline® to primary Dupline®, while pulses from primary Dupline® to secondary Dupline® are transferred with a max. delay of 1 ms.
When using analog transmission including synchronizer it is necessary to be cautious due to the above mentioned delay. In this case the analog transmitter should not be connected on the secondary side. On the other hand the synchronizer and the analog receivers can be placed without restrictions.
By application of the Dupline® repeater there are no problems when transferring the functions of the master generator.
Concerning the numbers of channels the repeater adjusts itself based on numbers of channels on the input side of the Dupline® network.
The repeater has a built-in channel generator function for the secondary Dupline®. This channel generator function locks itself on to the function of the channel generator on the primary side.
Specifications
Frequency | 65 Hz |
---|---|
Material | PC/ABS CYCOLOY C 2100 |
Output Voltage | 8.2 V |
Protection Rating | IP 40 |
Voltage | 24 V |
Weight | 485 g |
Overview | |
Supply | 24 VAC |
Input (Primary Dupline) | |
Dielectric voltage Primary Dupline to Secondary Dupline® | ≥ 2 kVAC (rms) |
Output (Secondary Dupline) | |
Number of outputs | 1 |
Output voltage | 8.2 VDC |
Current | ≤ 45 mA |
Short-circuit protection | ≤ 60 s |
Output impedance | ≤ 15 Ω |
Sequence time | Follows primary Dupline® |
Distance to transmitters | 100% |
Dupline Transmission Delay From | |
Primary to secondary | 1 mSec |
Secondary to primary | max 1 Dupline® scan 136 mSec |
Supply Specifications | |
Power supply | Overvoltage cat. III (IEC 60664) |
Rated operational voltage through term. 21 & 22 | 24 VAC, ±15% |
Frequency | 45 to 65 Hz |
Voltage interruption | ≤ 40 ms |
Rated operational power | 6 VA |
Power dissipation | ≤ 7 W |
Rated impulse withstand voltage | 800 V |
Dielectric Voltage | |
Supply - Primary Dupline® | ≥ 4 kVAC (rms) |
Supply - Secondary Dupline® | ≥ 4 kVAC (rms) |
General Specifications | |
Power ON delay | ≤ 5 s |
Indication for Supply ON | LED, green |
Indication for Primary Dupline® OK | LED, yellow |
Indication for Secondary Dupline® carrier | LED, yellow |
Dimensions | H8-housing |
Material | PC/ABS CYCOLOY C 2100 |
Weight | 485 g |
MTBF | 65,000 hours |
Environment | |
Degree of protection | IP 40 |
Pollution degree | 3 (IEC 60664) |
Operating temperature | 0° to +50°C (+32° to +122°F) |
Storage temperature | -50° to +85°C (-58° to +185°F) |
Mechanical Resistance | |
Shock | 15 G (11 ms) |
Vibration | 2 G (6 to 55 Hz) |