Bus coupler - IL PB BK DI8 DO4/EF-PAC - 2692322

Manufactured by:
PHOENIX CONTACT
Phoenix%20contact

Fbf2f0852c07d2934adbda5bdbeaaedf1739b0ff medium
Price (VAT excluded)
€ 283.68
Nuova Elva code
2692322
Manufacturer code
2692322
Availability
Send request for quotation

Inline, Bus coupler, PROFIBUS DP, D-SUB-9 female connector, Digital inputs: 8, 24 V DC, connection method: 3-wire, Digital outputs: 4, 24 V DC, 500 mA, connection method: 3-wire, transmission speed in the local bus: 500 kbps / 2 Mbps, degree of protection: IP20, including Inline connectors and marking fields

Features

  • PROFIBUS connection via 9-pos. D-SUB socket

  • Electrical isolation between PROFIBUS interface and logic

  • Eight digital inputs, four digital outputs (on-board)

  • Connection of a maximum of 16 PCP devices

  • DP/V1 for class 1 and class 2 masters

  • PROFIBUS data transmission speed of 9.6 kbps to 12 Mbps

  • Rotary coding switches for setting the PROFIBUS address

  • Supported PROFIBUS addresses from 0 to 126

  • I&M functions

  • IO-Link call (firmware 2.0 or later)

  • Operation of PROFIsafe devices

  • BV

  • PROFIBUS

  • GL-SW

  • EAC

  • cULus Recognized

  • ATEX

  • LR

  • RINA

  • GL

  • DNV GL

  • UL Recognized

  • cUL Recognized

Specifications

Depth71.5 mm
Height119.8 mm
Output Voltage24 V
Width80 mm

Digital outputs

Output nameDigital outputs
Connection methodInline connector
Connection technology3-wire
Number of outputs4
Protective circuitShort-circuit and overload protection Freewheeling circuit in the output driver
Output voltage24 V DC -1 V (At nominal current)
Nominal output voltage24 V DC
Maximum output current per channel500 mA
Maximum output current per module / terminal block2 A
Maximum output current per module2 A
Nominal load, inductive12 VA (1.2 H, 48 Ω)
Nominal load, lamp12 W
Nominal load, ohmic12 W
Limitation of the voltage induced on circuit interruptionapprox. -30 V
Output current when switched offmax. 10 µA (When not loaded, a voltage can be measured even at an output that is not set.)
Behavior with overloadAuto restart
Behavior with inductive overloadOutput can be destroyed
Reverse voltage resistance to short pulsesReverse voltage proof

System limits of the bus coupler

DesignationSystem limits of the bus coupler
Amount of process datamax. 488 Byte (per station)
Amount of process datamax. 244 Byte (Input)
Amount of process datamax. 244 Byte (Output)
Number of parameter datamax. 244 Byte (including 14 bytes for the bus coupler, DP/V1, and the local inputs and outputs)
Number of configuration datamax. 244 Byte (including 5 bytes for the local inputs and outputs)
Number of supported devicesmax. 63 (per station)
Number of local bus devices that can be connectedmax. 61 (The on-board I/Os are two devices)
Number of devices with parameter channelmax. 16
Number of supported branch terminals with remote bus branch0
Response time of I/Ostyp. 4 ms (aligned I/Os; transmission speed: PROFIBUS 1.5 Mbps, local bus 500 kbps)

Standards and Regulations

Protection classIII (IEC 61140, EN 61140, VDE 0140-1)
Mechanical testsVibration resistance in acc. with EN 60068-2-6/IEC 60068-2-6 5g
Mechanical testsShock in acc. with EN 60068-2-27/IEC 60068-2-27 Operation: 25g, 11 ms duration, semi-sinusoidal shock impulse
Connection in acc. with standardCUL

Inline potentials

DesignationBus coupler supply UBC; Communications power UL (7.5 V) and the analog supply UANA (24 V) are generated from the bus coupler supply.
Supply voltage24 V DC (via Inline connector)
Supply voltage range19.2 V DC - 30 V DC (including all tolerances, including ripple)
Current consumption80 mA (without connected I/O terminal blocks)
Current consumptionmax. 0.98 A
DesignationCommunications power (UL)
Supply voltage7.5 V DC
Power supply unitmax. 0.8 A DC
DesignationSupply of analog modules (UANA)
Supply voltage24 V DC
Power supply unitmax. 0.5 A DC
DesignationMain circuit supply (UM)
Power supply unitmax. 8 A DC (sum of UM + US)
Current consumptionmax. 8 A DC
DesignationSegment circuit supply (US)
Power consumptiontyp. 1.7 W (entire device)
Current consumption6 mA (without connected peripherals)

Dimensions

Width80 mm
Height119.8 mm
Depth71.5 mm
Note on dimensionsSpecfications with connectors

Interfaces

DesignationPROFIBUS DP
No. of channels1
Connection methodD-SUB-9 female connector
Transmission speed9.6 kbps - 12 Mbps
Number of positions9
DesignationInline local bus
Connection methodInline data jumper
Transmission speed500 kbps / 2 Mbps (automatic detection, no combined system)

Digital inputs

Input nameDigital inputs
Description of the inputEN 61131-2 type 1
Connection methodInline connector
Connection technology3-wire
Number of inputs8
Typical response timeapprox. 500 µs
Protective circuitReverse polarity protection Suppressor diode
Nominal input voltage UIN24 V DC
Nominal input current at UINtyp. 3 mA
Input voltage24 V DC
Input voltage range "0" signal-30 V DC - 5 V DC
Input voltage range "1" signal15 V DC - 30 V DC
Typical input current per channeltyp. 3 mA
Delay at signal change from 0 to 12.9 ms
Delay at signal change from 1 to 02.9 ms

Ambient conditions

Permissible humidity (storage/transport)10 % - 95 % (non-condensing)
Air pressure (operation)70 kPa - 106 kPa (up to 3000 m above sea level)
Air pressure (storage/transport)70 kPa - 106 kPa (up to 3000 m above sea level)
Degree of protectionIP20
Ambient temperature (operation)-25 °C - 60 °C
Ambient temperature (storage/transport)-25 °C - 85 °C
Permissible humidity (operation)10 % - 95 % (non-condensing)

Environmental Product Compliance

REACh SVHCLead 7439-92-1
China RoHSEnvironmentally friendly use period: unlimited = EFUP-e
China RoHSNo hazardous substances above threshold values

Note

Utilization restrictionEMC: class A product, see manufacturer's declaration in the download area

Frequently bought together


Other PHOENIX CONTACT items

Request a quote