Bus coupler - IL PN BK DI8 DO4 2TX-PAC - 2703994
- Manufactured by:
- PHOENIX CONTACT
- Price (VAT excluded)
- € 308.55
- Nuova Elva code
- 2703994
- Manufacturer code
- 2703994
- Availability
- Send request for quotation
PROFINET bus coupler, 8 inputs, 24 V DC, 4 outputs, 24 V DC, 500 mA, complete with I/O connectors
Features
Up to 61 terminals (16 PCP devices) can be connected
80 mm design width
Approved for PROFIsafe applications
Eight digital inputs, four digital outputs (on-board)
Automatic speed detection of the system bus
BV
cULus Listed
PROFINET
ATEX
LR
RINA
DNV GL
ABS
UL Listed
cUL Listed
Specifications
Depth | 71.5 mm |
---|---|
Height | 119.8 mm |
Output Voltage | 24 V |
Width | 80 mm |
Digital outputs | |
Nominal load, ohmic | 12 W |
Limitation of the voltage induced on circuit interruption | approx. -30 V |
Output current when switched off | max. 10 µA (When not loaded, a voltage can be measured even at an output that is not set.) |
Behavior with overload | Auto restart |
Behavior with inductive overload | Output can be destroyed |
Reverse voltage resistance to short pulses | Reverse voltage proof |
Output name | Digital outputs |
Connection method | Inline connector |
Connection technology | 2, 3-wire |
Number of outputs | 4 |
Protective circuit | Short-circuit and overload protection Freewheeling circuit in the output driver |
Output voltage | 24 V DC -1 V (At nominal current) |
Nominal output voltage | 24 V DC |
Maximum output current per channel | 500 mA |
Maximum output current per module / terminal block | 2 A |
Maximum output current per module | 2 A |
Nominal load, inductive | 12 VA (1.2 H, 48 Ω) |
Nominal load, lamp | 12 W |
Power supply for module electronics | |
Connection method | Spring-cage connection |
Designation | Bus coupler supply UBC; Communications power UL (7.5 V) and the analog supply UANA (24 V) are generated from the bus coupler supply. |
Supply voltage | 24 V DC (via Inline connector) |
Supply voltage range | 19.2 V DC - 30 V DC (including all tolerances, including ripple) |
Supply current | 138 mA |
Current consumption | typ. 138 mA (from UBK) |
Current consumption | max. 0.91 A DC (from UBK) |
Power dissipation | typ. 3 W (entire device) |
System limits of the bus coupler | |
Amount of process data | max. 488 Byte (max. 244 bytes IN - max. 244 bytes OUT) |
Amount of process data | max. 244 Byte (Input) |
Amount of process data | max. 244 Byte (Output) |
Number of supported devices | max. 63 (per station) |
Number of local bus devices that can be connected | max. 61 (The on-board I/Os are two devices) |
Number of devices with parameter channel | max. 16 |
Number of supported branch terminals with remote bus branch | 0 |
Inline potentials | |
Designation | Bus coupler supply UBC; Communications power UL (7.5 V) and the analog supply UANA (24 V) are generated from the bus coupler supply. |
Supply voltage | 24 V DC |
Supply voltage range | 19.2 V DC - 30 V DC (via Inline connector) |
Current consumption | 138 mA (without connected I/O terminal blocks) |
Current consumption | typ. 138 mA |
Current consumption | max. 0.91 A DC |
Designation | Communications power (UL) |
Supply voltage | 7.5 V DC ±5 % |
Power supply unit | max. 0.8 A DC (observe derating) |
Power consumption | typ. 3 W (entire device) |
Designation | Supply of analog modules (UANA) |
Power supply unit | max. 0.5 A DC (observe derating) |
Designation | Main circuit supply (UM) |
Power supply unit | max. 8 A DC (Sum of UM + US; 4 A, maximum, when used in potentially explosive areas.) |
Current consumption | 3 mA (without sensors) |
Designation | Segment circuit supply (US) |
Supply voltage range | 19.2 V DC - 30 V DC (including all tolerances, including ripple) |
Current consumption | max. 8 A DC |
Current consumption | 3 mA (without actuators) |
Standards and Regulations | |
Mechanical tests | Vibration resistance in acc. with EN 60068-2-6/IEC 60068-2-6 5g |
Mechanical tests | Shock in acc. with EN 60068-2-27/IEC 60068-2-27 Operation: 25g, 11 ms duration, semi-sinusoidal shock impulse |
Protection class | III (IEC 61140, EN 61140, VDE 0140-1) |
Dimensions | |
Width | 80 mm |
Height | 119.8 mm |
Depth | 71.5 mm |
Note on dimensions | Specfications with connectors |
Interfaces | |
Designation | PROFINET |
No. of channels | 2 |
Connection method | RJ45 socket, auto negotiation |
Transmission speed | 100 Mbps (acc. to PROFINET standard) |
Transmission physics | Ethernet in RJ45 twisted pair |
Designation | Inline local bus |
Connection method | Inline data jumper |
Transmission speed | 500 kbps / 2 Mbps (automatic detection, no combined system) |
Digital inputs | |
Input name | Digital inputs |
Description of the input | EN 61131-2 type 1 |
Connection method | Inline connector |
Connection technology | 2, 3-wire |
Number of inputs | 8 |
Typical response time | approx. 500 µs |
Protective circuit | Reverse polarity protection Polarity protection diode |
Nominal input voltage UIN | 24 V DC |
Nominal input current at UIN | typ. 3 mA |
Filter time | 3 ms |
Input voltage | 24 V DC |
Input voltage range "0" signal | -30 V DC - 5 V DC |
Input voltage range "1" signal | 15 V DC - 30 V DC |
Typical input current per channel | typ. 3 mA |
Delay at signal change from 0 to 1 | 5 ms |
Delay at signal change from 1 to 0 | 5 ms |
Ambient conditions | |
Permissible humidity (storage/transport) | 10 % - 95 % (according to DIN EN 61131-2) |
Air pressure (operation) | 70 kPa - 106 kPa (up to 3000 m above sea level) |
Air pressure (storage/transport) | 70 kPa - 106 kPa (up to 3000 m above sea level) |
Degree of protection | IP20 |
Ambient temperature (operation) | -25 °C - 55 °C (observe derating) |
Ambient temperature (storage/transport) | -40 °C - 85 °C |
Permissible humidity (operation) | 10 % - 95 % (according to DIN EN 61131-2) |
Environmental Product Compliance | |
REACh SVHC | Lead 7439-92-1 |
China RoHS | Environmentally friendly use period: unlimited = EFUP-e |
China RoHS | No hazardous substances above threshold values |
Note | |
Utilization restriction | EMC: class A product, see manufacturer's declaration in the download area |