Repeater - PSI-REP-PROFIBUS/12MB - 2708863
- Manufactured by:
- PHOENIX CONTACT
- Price (VAT excluded)
- € 619.79
- Nuova Elva code
- 2708863
- Manufacturer code
- 2708863
- Availability
- Send request for quotation
Modular repeater for electrical isolation and range increase for PROFIBUS up to 12 Mbps, 4-way isolation, rail-mountable, supply 24 V DC
Features
Automatic data rate detection or fixed data rate setting via DIP switches
Suitable for all data rates up to 12 Mbps
High-quality 4-way isolation between all interfaces
Bit oversampling for reliable detection of sporadic disturbances
Bit retiming for unrestricted cascading of devices
Filtering of faulty telegrams based on start delimiter detection
Can be combined with PSI-MOS FO converters in a modular way thanks to DIN rail connectors
EAC
cULus Recognized
ATEX
KC
UL Listed
cUL Listed
UL Recognized
cUL Recognized
Specifications
Depth | 105 mm |
---|---|
Height | 99 mm |
Width | 35 mm |
Conformance/approvals | |
Designation | CE |
Identification | CE-compliant |
Designation | EAC |
Identification | EAC |
Designation | ATEX |
Identification | II 3 G Ex nA nC IIC T4 Gc X |
Additional text | Please follow the special installation instructions in the documentation! |
Designation | UL, USA/Canada |
Identification | 508 Listed |
Identification | Class I, Zone 2, AEx nA nC IIC T6 |
Identification | Class I, Zone 2, Ex nA nC IIC T6 Gc X |
Identification | Class I, Div. 2, Groups A, B, C, D |
Designation | Corrosive gas test |
Identification | ISA-S71.04-1985 G3 Harsh Group A |
Ambient conditions | |
Altitude | ≤ 2000 m (Restrictions for ATEX applications) |
Degree of protection | IP20 |
Noise immunity | EN 61000-4-2 |
Ambient temperature (operation) | -20 °C - 60 °C |
Ambient temperature (storage/transport) | -40 °C - 85 °C |
Permissible humidity (operation) | 30 % - 95 % (non-condensing) |
Altitude | ≤ 5000 m (For restrictions, see the manufacturer's declaration for altitude operation) |
Environmental Product Compliance | |
REACh SVHC | Lead 7439-92-1 |
China RoHS | Environmentally Friendly Use Period = 50 years |
China RoHS | For details about hazardous substances go to tab 'Downloads', Category 'Manufacturer's declaration' |
Standards and Regulations | |
Electromagnetic compatibility | Conformance with EMC Directive 2014/30/EU |
Type of test | Free fall in acc. with IEC 60068-2-32 |
Test result | 1 m |
Type of test | Vibration resistance in acc. with EN 60068-2-6/IEC 60068-2-6 |
Test result | 5g, 10...150 Hz, 2.5 h, in XYZ direction |
Type of test | Shock in acc. with EN 60068-2-27/IEC 60068-2-27 |
Test result | 15g, 11 ms period, half-sine shock pulse |
Noise emission | EN 55011 |
Noise immunity | EN 61000-4-2 |
Free from substances that could impair the application of coating | according to P-VW 3.10.7 57 65 0 VW-AUDI-Seat central standard |
Connection in acc. with standard | CUL |
Standards/regulations | EN 61000-4-2 |
Contact discharge | ± 6 kV |
Standards/regulations | EN 61000-4-3 |
Frequency range | 80 MHz - 3 GHz |
Standards/regulations | EN 61000-4-4 |
Comments | Criterion B |
Standards/regulations | EN 61000-4-5 |
Signal | ± 1 kV |
Standards/regulations | EN 55011 |
Standards/regulations | EN 61000-4-6 |
Designation | Air clearances and creepage distances |
Standards/regulations | DIN EN 50178, DIN EN 60950 |
Dimensions | |
Width | 35 mm |
Height | 99 mm |
Depth | 105 mm |
Interfaces | |
Interface 1 | PROFIBUS acc. to IEC 61158, RS-485 2-conductor |
Operating mode | Through PROFIBUS connector |
Connection method | D-SUB-9 female connector |
File format/coding | UART (11 Bit, NRZ) |
Data direction switching | Automatic control, min. station response time 2 bits |
Transmission medium | 2-wire twisted pair, shielded |
Transmission length | ≤ 1200 m (Depends on transmission speed and cable type) |
Termination resistor | external |
Conductor cross section solid min. | 0.2 mm² |
Conductor cross section solid max. | 2.5 mm² |
Conductor cross section flexible min. | 0.2 mm² |
Conductor cross section flexible max. | 2.5 mm² |
Conductor cross section AWG min. | 24 |
Conductor cross section AWG max. | 14 |
Output nominal voltage | 5 V DC ±5 % |
Output current | 50 mA |
Digital outputs | |
Output name | Relay output |
Output description | Alarm output |
Number of outputs | 1 |
Maximum switching voltage | 30 V DC (1 A) |
Maximum switching voltage | 65 V DC (0.46 A) |
Maximum switching voltage | 150 V AC (0.46 A) |
Power supply | |
Nominal supply voltage | 24 V DC (With UL approval) |
Supply voltage range | 18 V DC - 30 V DC (via pluggable COMBICON screw terminal block) |
Typical current consumption | < 90 mA (24 V DC ) |
Note | |
Utilization restriction | EMC: class A product, see manufacturer's declaration in the download area |