Inline terminal - IB IL 24 DI 4-PAC - 2861234

Manufactured by:
PHOENIX CONTACT
Phoenix contact

4991df8f48dcf00d740d089a078ee1850b5d50bc medium
Price (VAT excluded)
€ 57.57
Nuova Elva code
2861234
Manufacturer code
2861234
Availability
Send request for quotation

Inline, Digital input terminal, Digital inputs: 4, 24 V DC, connection method: 3-wire, transmission speed in the local bus: 500 kbps, degree of protection: IP20, including Inline connector and labeling field

Features

  • 4 digital inputs

  • Connection of sensors in 2 and 3-wire technology

  • Maximum permissible load current per sensor: 250 mA

  • Maximum permissible load current from the terminal: 1 A

  • BV

  • BSH

  • cULus Listed

  • EAC

  • ATEX

  • LR

  • RINA

  • DNV GL

  • ABS

  • UL Listed

  • cUL Listed

  • UL Recognized

Specifications

Depth71.5 mm
Height140.5 mm
Width12.2 mm

Environmental Product Compliance

China RoHSEnvironmentally Friendly Use Period = 50 years
China RoHSFor details about hazardous substances go to tab 'Downloads', Category 'Manufacturer's declaration'

Dimensions

Width12.2 mm
Height140.5 mm
Depth71.5 mm
Note on dimensionsHousing dimensions

Interfaces

DesignationInline local bus
No. of channels2
Connection methodInline data jumper
Transmission speed500 kbps

Digital inputs

Input nameDigital inputs
Description of the inputEN 61131-2 type 1
Connection methodSpring-cage connection
Connection technology3-wire
Number of inputs4
Typical response time< 1 ms
Protective circuitShort-circuit and overload protection
Nominal input voltage UIN24 V DC
Nominal input current at UINmin. 3 mA (at nominal voltage)
Input voltage24 V DC
Input voltage range "0" signal-3 V DC - 5 V DC
Input voltage range "1" signal15 V DC - 30 V DC

Inline potentials

DesignationCommunications power (UL)
Supply voltage7.5 V DC (via voltage jumper)
Current consumptionmax. 40 mA
Power consumptionmax. 0.3 W
DesignationSegment circuit supply (US)
Supply voltage24 V DC (via voltage jumper)
Supply voltage range19.2 V DC - 30 V DC (including all tolerances, including ripple)
Current consumptionmax. 1 A
Current consumption0 A

Ambient conditions

Permissible humidity (storage/transport)10 % - 95 % (non-condensing)
Air pressure (operation)70 kPa - 106 kPa (up to 3000 m above sea level)
Air pressure (operation)80 kPa - 106 kPa (up to 3000 m above sea level, in ATEX Zone 2)
Air pressure (storage/transport)70 kPa - 106 kPa (up to 3000 m above sea level)
Degree of protectionIP20
Ambient temperature (operation)-25 °C - 55 °C
Ambient temperature (storage/transport)-25 °C - 85 °C
Permissible humidity (operation)10 % - 95 % (non-condensing)

Standards and Regulations

Connection in acc. with standardCUL
Protection classIII (IEC 61140, EN 61140, VDE 0140-1)

Electrical isolation

Test section7.5 V supply (bus logics)/24 V supply (I/O) 500 V AC 50 Hz 1 min.
Test section24 V supply (I/O) / functional earth ground 500 V AC 50 Hz 1 min.
Test section7.5 V supply (bus logics) / functional earth ground 500 V AC 50 Hz 500 min.

Note

Utilization restrictionEMC: class A product, see manufacturer's declaration in the download area