Inline terminal - IB IL 24 DO 16-PAC - 2861292
- Manufactured by:
- PHOENIX CONTACT
- Price (VAT excluded)
- € 223.88
- Nuova Elva code
- 2861292
- Manufacturer code
- 2861292
- Availability
- Send request for quotation
Inline, Digital output terminal, Digital outputs: 16, 24 V DC, 500 mA, connection method: 3-wire, transmission speed in the local bus: 500 kbps, degree of protection: IP20, including Inline connectors and marking fields
Features
16 digital outputs
Connection of actuators in 2 and 3-wire technology
Nominal current per output: 500 mA
Total current of the terminal: 8 A
Short-circuit-proof and overload-protected outputs
BV
BSH
cULus Listed
EAC
ATEX
LR
RINA
DNV GL
ABS
UL Listed
cUL Listed
UL Recognized
Specifications
Depth | 71.5 mm |
---|---|
Height | 140.5 mm |
Output Voltage | 24 V |
Width | 48.8 mm |
Digital outputs | |
Output name | Digital outputs |
Connection method | Spring-cage connection |
Connection technology | 3-wire |
Number of outputs | 16 |
Protective circuit | Overload protection, short-circuit protection of outputs Zener diode in output chip |
Output voltage | 24 V DC (US - 1 V) |
Maximum inrush current | max. 1.5 A (at nominal lamp load for 20 ms) |
Nominal output voltage | 24 V DC |
Maximum output current per channel | 500 mA |
Maximum output current per module | 8 A |
Nominal load, inductive | 12 W (1.2 H, 48 Ω) |
Nominal load, lamp | 12 W |
Nominal load, ohmic | 12 VA (48 Ω) |
Output voltage when switched off | max. 2 V |
Output current when switched off | max. 300 µA |
Behavior with overload | Auto restart |
Behavior with inductive overload | Output can be destroyed |
Reverse voltage resistance to short pulses | Reverse voltage proof |
Environmental Product Compliance | |
REACh SVHC | Lead 7439-92-1 |
China RoHS | Environmentally Friendly Use Period = 50 years |
China RoHS | For details about hazardous substances go to tab 'Downloads', Category 'Manufacturer's declaration' |
Dimensions | |
Width | 48.8 mm |
Height | 140.5 mm |
Depth | 71.5 mm |
Note on dimensions | Housing dimensions |
Interfaces | |
Designation | Inline local bus |
No. of channels | 2 |
Connection method | Inline data jumper |
Transmission speed | 500 kbps |
Inline potentials | |
Designation | Communications power (UL) |
Supply voltage | 7.5 V DC (via voltage jumper) |
Current consumption | max. 90 mA |
Power consumption | max. 0.675 W |
Designation | Segment circuit supply (US) |
Supply voltage | 24 V DC (via voltage jumper) |
Supply voltage range | 19.2 V DC - 30 V DC (including all tolerances, including ripple) |
Current consumption | max. 8 A |
Current consumption | 0 A |
Ambient conditions | |
Permissible humidity (storage/transport) | 10 % - 95 % (non-condensing) |
Air pressure (operation) | 70 kPa - 106 kPa (up to 3000 m above sea level) |
Air pressure (operation) | 80 kPa - 106 kPa (up to 3000 m above sea level, in ATEX Zone 2) |
Air pressure (storage/transport) | 70 kPa - 106 kPa (up to 3000 m above sea level) |
Degree of protection | IP20 |
Ambient temperature (operation) | -25 °C - 55 °C |
Ambient temperature (storage/transport) | -25 °C - 85 °C |
Permissible humidity (operation) | 10 % - 95 % (non-condensing) |
Standards and Regulations | |
Connection in acc. with standard | CUL |
Protection class | III (IEC 61140, EN 61140, VDE 0140-1) |
Electrical isolation | |
Test section | 7.5 V supply (bus logics)/24 V supply (I/O) 500 V AC 50 Hz 1 min. |
Test section | 24 V supply (I/O) / functional earth ground 500 V AC 50 Hz 1 min. |
Test section | 7.5 V supply (bus logics) / functional earth ground 500 V AC 50 Hz 1 min. |
Note | |
Utilization restriction | EMC: class A product, see manufacturer's declaration in the download area |