Inline, Analog input terminal, Analog inputs: 2, 0 V ... 10 V, -10 V ... 10 V, 0 mA ... 20 mA, 4 mA ... 20 mA, -20 mA ... 20 mA, connection method: 2-wire, transmission speed in the local bus: 500 kbps, degree of protection: IP20, including Inline connector and labeling field

Features

  • 2 analog single-ended signal inputs for the connection of either voltage or current signals

  • Connection of sensors in 2-wire technology

  • Current ranges: 0 mA ... 20 mA, 4 mA ... 20 mA, ±20 mA

  • Voltage ranges: 0 V ... 10 V, ±10 V

  • Channels are parameterized independently of one another via the bus system

  • Measured values can be represented in four different formats

  • Resolution depends on the representation format and the measuring range

  • Process data update of both channels within a max. of 1.5 ms

  • BV

  • BSH

  • cULus Listed

  • EAC

  • ATEX

  • LR

  • RINA

  • DNV GL

  • ABS

  • UL Listed

  • cUL Listed

  • UL Recognized

Specifications

Depth71.5 mm
Height136.8 mm
Width12.2 mm

Electrical isolation

Test section7.5 V supply (bus logic), 24 V supply UANA / I/O 500 V AC 50 Hz 1 min.
Test section7.5 V supply (bus logic), 24 V supply UANA/functional earth ground 500 V AC 50 Hz 1 min.
Test sectionI/O / functional earth ground 500 V AC 50 Hz 1 min.

Dimensions

Width12.2 mm
Height136.8 mm
Depth71.5 mm
Note on dimensionsHousing dimensions

Interfaces

DesignationInline local bus
No. of channels2
Connection methodInline data jumper
Transmission speed500 kbps

Analog inputs

Description of the inputSingle-ended inputs, voltage or current
Input nameAnalog inputs
Number of inputs2
Connection methodInline shield connector
Connection technology2-wire
Note regarding the connection technologyshielded
A/D conversion timetyp. 120 µs (per channel)
Limit frequency (3 dB)40 Hz
Type of protectionSurge protection
Data formatsIB IL, IB ST, IB RT, standardized representation
Measuring principleSuccessive approximation
Measured value resolution16 bits (15 bits + sign bit)
Measured value representation16 bit two's complement
Current input signal0 mA - 20 mA
Current input signal4 mA - 20 mA
Current input signal-20 mA - 20 mA
Input resistance current input50 Ω (Shunt)
Voltage input signal0 V - 10 V
Voltage input signal-10 V - 10 V
Input resistance of voltage input> 220 kΩ
Common mode voltage range signal - ground40 V (between current input and functional earth ground)

Ambient conditions

Permissible humidity (storage/transport)10 % - 95 % (non-condensing)
Air pressure (operation)70 kPa - 106 kPa (up to 3000 m above sea level)
Air pressure (operation)80 kPa - 106 kPa (up to 3000 m above sea level, in ATEX Zone 2)
Air pressure (storage/transport)70 kPa - 106 kPa (up to 3000 m above sea level)
Degree of protectionIP20
Ambient temperature (operation)-25 °C - 55 °C
Ambient temperature (storage/transport)-25 °C - 85 °C
Permissible humidity (operation)10 % - 95 % (non-condensing)

Inline potentials

DesignationCommunications power (UL)
Supply voltage7.5 V DC (via voltage jumper)
Current consumptiontyp. 45 mA
Current consumptionmax. 60 mA
DesignationSupply of analog modules (UANA)
Supply voltage24 V DC (via voltage jumper)
Supply voltage range19.2 V DC - 30 V DC (including all tolerances, including ripple)
Current consumptiontyp. 13 mA
Current consumptionmax. 18 mA
Power consumptiontyp. 662 mW

Environmental Product Compliance

REACh SVHCLead 7439-92-1
China RoHSEnvironmentally friendly use period: unlimited = EFUP-e
China RoHSNo hazardous substances above threshold values

Standards and Regulations

Connection in acc. with standardCUL
Protection classIII (IEC 61140, EN 61140, VDE 0140-1)

Note

Utilization restrictionEMC: class A product, see manufacturer's declaration in the download area