Resistance/potiposition transducer - MINI MCR-SL-R-UI - 2864095
- Manufactured by:
- PHOENIX CONTACT
- Price (VAT excluded)
- € 303.87
- Nuova Elva code
- 2864095
- Manufacturer code
- 2864095
- Availability
- Send request for quotation
MCR potiposition transducer for conversion of potentiometer positions into a standard analog signal, 0 Ω input... 100 Ω to 0 kΩ ... 100 kΩ
Features
Power supply possible via the foot element (TBUS)
Automatic potentiometer detection without manual adjustment
Error indication via diagnostic LED and analog signal
For 100 Ω to 100 kΩ potentiometers
potentiometer signals to create standard signals
Configurable measuring range and output signals
Highly-compact potentiometer transducer for electrical isolation, conversion, amplification, and filtering of
Input and output signals can be configured via DIP switches
3-way isolation
A potentiometer sub-range can be linearized via the "teach-in" switch on the device
cULus Listed
cULus Recognized
ATEX
EAC
DNV GL
UL Listed
cUL Listed
UL Recognized
cUL Recognized
Specifications
Depth | 101.2 mm |
---|---|
Height | 93.1 mm |
Strip Length | 12 mm |
Width | 6.2 mm |
Ambient conditions | |
Noise immunity | EN 61000-6-2 When being exposed to interference, there may be minimal deviations. |
Ambient temperature (operation) | -20 °C - 65 °C |
Ambient temperature (storage/transport) | -40 °C - 85 °C |
Maximum altitude | ≤ 2000 m |
Permissible humidity (operation) | 5 % - 95 % (non-condensing) |
Degree of protection | IP20 |
Environmental Product Compliance | |
REACh SVHC | Lead 7439-92-1 |
China RoHS | Environmentally Friendly Use Period = 50 years |
China RoHS | For details about hazardous substances go to tab 'Downloads', Category 'Manufacturer's declaration' |
Power supply | |
Nominal supply voltage | 24 V DC |
Supply voltage range | 19.2 V DC - 30 V DC (The DIN rail bus connector (ME 6,2 TBUS-2 1,5/5-ST-3,81 GN, Order No. 2869728) can be used to bridge the supply voltage. It can be snapped onto a 35 mm DIN rail according to EN 60715)) |
Typical current consumption | < 25 mA (at 24 V DC) |
Power consumption | < 500 mW |
Dimensions | |
Width | 6.2 mm |
Height | 93.1 mm |
Depth | 101.2 mm |
Connection data | |
Connection method | Screw connection |
Stripping length | 12 mm |
Screw thread | M3 |
Conductor cross section solid | 0.2 mm² - 2.5 mm² |
Conductor cross section flexible | 0.2 mm² - 2.5 mm² |
Conductor cross section AWG | 26 - 12 |
Input data | |
Potentiometer | 100 Ω - 100 kΩ |
Reference voltage source | < 3.6 V |
Output data | |
Voltage output signal | 0 V - 5 V |
Voltage output signal | 0 V - 10 V |
Voltage output signal | 1 V - 5 V |
Voltage output signal | 10 V - 0 V |
Current output signal | 0 mA - 20 mA |
Current output signal | 4 mA - 20 mA |
Current output signal | 20 mA - 0 mA |
Current output signal | 20 mA - 4 mA |
Max. voltage output signal | 12.5 V |
Max. current output signal | 23 mA |
Load/output load voltage output | > 10 kΩ |
Load/output load current output | < 500 Ω (20 mA) |
EMC data | |
Designation | Electromagnetic RF field |
Standards/regulations | EN 61000-4-3 |
Typical deviation from the measuring range final value | 5 % |
Designation | Fast transients (burst) |
Standards/regulations | EN 61000-4-4 |
Designation | Conducted interferences |
Standards/regulations | EN 61000-4-6 |
Standards and Regulations | |
Electromagnetic compatibility | Conformance with EMC directive |
Noise emission | EN 61000-6-4 |
Connection in acc. with standard | CUL |
Designation | Electromagnetic RF field |
Standards/regulations | EN 61000-4-3 |
Standards/regulations | EN 61000-4-4 |
Designation | Conducted interferences |
Standards/regulations | EN 61000-4-6 |
Electrical isolation | Basic insulation according to EN 61010 |
Conformance | CE-compliant |
ATEX | II 3 G Ex nA IIC T4 Gc X |
UL, USA/Canada | UL 508 Recognized |
UL, USA/Canada | Class I, Div. 2, Groups A, B, C, D T4 |
Note | |
Utilization restriction | EMC: class A product, see manufacturer's declaration in the download area |