Signal isolator - MACX MCR-EX-SL-RPSS-2I-2I - 2865382

Manufactured by:
PHOENIX CONTACT
Phoenix contact

543485a34144190d0b2dfd8be1e9c2ed012a605b medium
Price (VAT excluded)
€ 472.96
Nuova Elva code
2865382
Manufacturer code
2865382
Availability
Send request for quotation

Ex i measuring transducer repeater power supply, 2-channel; HART-transparent. Supplies Ex i 2-conductor measuring transducers and transmits the 4…20 mA signal from the Ex area to the safe area. 5-way electrical isolation, screw connection, up to SIL 3, PL.

Features

  • 2-channel

  • 4 mA ... 20 mA input, intrinsically safe, [Ex ia], powered

  • Output 4 mA ... 20 mA, active

  • HART-compatible

  • Error indication according to NAMUR NE 43

  • Up to SIL 3 according to IEC/EN 61508

  • 5-way electrical isolation

  • Power supply possible via DIN rail connector

  • Installation in Ex zone 2 permitted

  • Plug-in connection terminal blocks, screw connection technology, with integrated sockets for HART communicators

  • Housing width: 12.5 mm

  • Minimal power dissipation

  • High transmission accuracy

  • cULus Listed

  • EAC Ex

  • Functional Safety

  • IECEx

  • ATEX

  • KC-s

  • UL Listed

  • cUL Listed

Specifications

Depth113.7 mm
Height112.5 mm
Strip Length7 mm
Width12.5 mm

Ambient conditions

Noise immunityEN 61000-6-2 When being exposed to interference, there may be minimal deviations.
Ambient temperature (operation)-20 °C - 60 °C (Any mounting position)
Ambient temperature (storage/transport)-40 °C - 80 °C
Maximum altitude≤ 2000 m
Permissible humidity (operation)10 % - 95 % (non-condensing)
Degree of protectionIP20 (not assessed by UL)

Output data

Signal outputCurrent output
Current output signal4 mA - 20 mA (active)
Transmission Behavior1:1 to input signal
Load/output load current output≤ 450 Ω (20 mA)
Load/output load current output≤ 375 Ω (24 mA)
Output behavior in the event of an error< 3.6 mA (In the event of cable break at the input (as per NE 43))
Output behavior in the event of an error> 22.5 mA (In the event of cable short circuit at the input (as per NE 43))

Standards and Regulations

Electromagnetic compatibilityConformance with EMC directive
Noise emissionEN 61000-6-4
ConformanceCE-compliant, additionally EN 61326
ATEXII (1) G [Ex ia Ga] IIC
ATEXII (1) D [Ex ia Da] IIIC
ATEXII 3(1) G Ex nA [ia Ga] IIC T4 Gc
IECEx[Ex ia Ga] IIC
IECEx[Ex ia Da] IIIC
IECExEx nA [ia Ga] IIC T4 Gc
UL, USA/CanadaClass I Div 2; IS for Class I, II, III Div 1
DNV GL-TemperatureB
DNV GL-HumidityB
DNV GL-VibrationA
DNV GL-EMCA
DNV GL-EnclosureRequired protection according to the Rules shall be provided upon installation on board
GroupIIC
GroupIIB

Environmental Product Compliance

REACh SVHCLead 7439-92-1
China RoHSEnvironmentally Friendly Use Period = 50 years
China RoHSFor details about hazardous substances go to tab 'Downloads', Category 'Manufacturer's declaration'

Dimensions

Width12.5 mm
Height112.5 mm
Depth113.7 mm

Safety data

Max. external capacitance Co510 nF
Max. external capacitance Co660 nF
Max. external inductivity Lo100 µH
Safety-related maximum voltage Um253 V AC (125 V DC)
Max. output voltage Uo25.2 V
Max. output current Io93 mA
Max. output power Po587 mW
GroupIIC
Max. external inductivity Lo2 mH
Max. external capacitance Co107 nF
Max. external capacitance Co49 nF
Additional textmixed circuit
Max. external inductivity Lo1 mH
Max. external capacitance Co63 nF
Max. external inductivity Lo500 µH
Max. external capacitance Co80 nF
Max. external inductivity Lo200 µH
GroupIIB
Max. external inductivity Lo4 mH
Max. external capacitance Co820 nF
Additional textsimple circuit
Max. external capacitance Co370 nF
Max. external capacitance Co430 nF

Connection data

Connection methodScrew connection
Stripping length7 mm
Screw threadM3
Conductor cross section solid0.2 mm² - 2.5 mm²
Conductor cross section flexible0.2 mm² - 2.5 mm²
Conductor cross section AWG24 - 14
Torque0.5 Nm - 0.6 Nm

Connection data 2

Connection nameTest socket
Max. diameter2.3 mm

Input data

Signal inputIntrinsically safe
Current input signal4 mA - 20 mA
Transmitter supply voltage> 16 V (20 mA)
Underload/overload signal range0 mA - 24 mA

Power supply

Nominal supply voltage24 V DC
Supply voltage range19.2 V DC - 30 V DC (24 V DC -20%...+25%)
Max. current consumption< 100 mA (24 V / 20 mA)
Power dissipation< 1.4 W (at 24 V DC / 20 mA)

Data communication (bypass)

HART functionYes
Protocols supportedHART

Note

Utilization restrictionEMC: class A product, see manufacturer's declaration in the download area

Frequently bought together


Other PHOENIX CONTACT items

Request a quote