Power supply unit 2866404
- Manufactured by:
- PHOENIX CONTACT
- Price (VAT excluded)
- € 538.86
- Nuova Elva code
- 2866404
- Manufacturer code
- 2866404
- Availability
- Send request for quotation
Primary-switched TRIO POWER power supply for DIN rail mounting, input: 3-phase, output: 24 V DC/40 A
Features
Use the third negative terminal block as a grounding terminal block and minimize installation costs
Rugged design with metal housing and wide temperature range from -25 to +70°C
Maximum operational reliability thanks to high MTBF (mean time between failures) of more than 500,000 hours and high dielectric strength of up to 300 V AC
Compensation of voltage drops by means of output voltage that can be adjusted on the front
cULus Listed
EAC
cULus Recognized
EAC
UL Listed
cUL Listed
UL Recognized
cUL Recognized
Specifications
Height | 130 mm |
---|---|
Operating Temperature | -25 °C |
Protection Rating | IP20 |
Width | 139 mm |
Output data | |
Nominal output voltage | 24 V DC ±1 % |
Setting range of the output voltage (U<sub>Set</sub>) | 22.5 V DC - 29.5 V DC (> 24 V DC, constant capacity restricted) |
Nominal output current (I<sub>N</sub>) | 40 A (-25 °C - 55 °C) |
Derating | 55 °C - 70 °C (2.5%/K) |
Connection in parallel | Yes, for redundancy and increased capacity |
Connection in series | yes |
Feedback resistance | 35 V DC |
Protection against surge voltage on the output | < 35 V DC |
Max. capacitive load | unlimited |
Active current limitation | Approx. 48 A |
Control deviation | < 1 % (change in load, static 10 % - 90 %) |
Control deviation | < 2 % (change in load, dynamic 10 % - 90 %) |
Control deviation | < 0.1 % (change in input voltage ±10 %) |
Residual ripple | < 20 mVPP |
Output power | 960 W |
Typical response time | < 1 s |
Peak switching voltages nominal load | < 40 mVPP |
Maximum power dissipation in no-load condition | 16 W |
Power loss nominal load max. | 91 W |
Standards and Regulations | |
Standard – Protection against shock currents, basic requirements for protective separation in electrical equipment | EN 50178 |
Standard – Limitation of mains harmonic currents | EN 61000-3-2 |
UL approvals | UL/C-UL listed UL 508 |
UL approvals | UL/C-UL Recognized UL 60950-1 |
Shock | 15g in all directions in acc. with IEC 60068-2-27 |
Vibration (operation) | < 15 Hz, amplitude ±2.5 mm (according to IEC 60068-2-6) |
Vibration (operation) | 15 Hz - 150 Hz, 2.3g, 90 min. |
Rail applications | EN 50121-4 |
Electromagnetic compatibility | Conformance with EMC Directive 2014/30/EU |
Noise immunity | EN 61000-6-2:2005 |
Connection in acc. with standard | CUL |
Standards/regulations | EN 61000-4-2 |
Contact discharge | 4 kV (Test Level 2) |
Standards/regulations | EN 61000-4-3 |
Frequency range | 80 MHz - 1 GHz |
Test field strength | 10 V/m |
Frequency range | 1.4 GHz - 2 GHz |
Test field strength | 3 V/m |
Standards/regulations | EN 61000-4-4 |
Comments | Criterion B |
Standards/regulations | EN 61000-6-3 |
Standards/regulations | EN 61000-4-6 |
Frequency range | 0.15 MHz - 80 MHz |
Voltage | 10 V (Test Level 3) |
Standards/regulations | EN 61000-4-11 |
Low Voltage Directive | Conformance with LV directive 2006/95/EC |
Standard - Electrical safety | EN 60950-1/VDE 0805 (SELV) |
Standard – Electronic equipment for use in electrical power installations and their assembly into electrical power installations | EN 50178/VDE 0160 (PELV) |
Standard – Safety extra-low voltage | EN 60950-1 (SELV) |
Standard – Safety extra-low voltage | EN 60204 (PELV) |
Standard - Safe isolation | DIN VDE 0100-410 |
Environmental Product Compliance | |
REACh SVHC | Lead 7439-92-1 |
China RoHS | Environmentally Friendly Use Period = 25; |
China RoHS | For details about hazardous substances go to tab “Downloads”, Category “Manufacturer's declaration” |
Dimensions | |
Width | 139 mm |
Height | 130 mm |
Depth | 190 mm |
Input data | |
Nominal input voltage range | 3x 400 V AC - 500 V AC |
Input voltage range | 3x 320 V AC - 575 V AC |
Input voltage range | 2x 360 V AC - 575 V AC (for 2-phase operation) |
AC frequency range | 45 Hz - 65 Hz |
Discharge current to PE | < 3.5 mA |
Current consumption | 3x 2 A (400 V AC) |
Current consumption | 3x 1.6 A (480 V AC) |
Nominal power consumption | 1387 VA |
Inrush surge current | < 20 A |
Mains buffering | > 16 ms (400 V AC) |
Mains buffering | > 20 ms (480 V AC) |
Choice of suitable circuit breakers | 6 A - 16 A (Characteristics B, C, D, K) |
Power factor (cos phi) | 0.76 |
Type of protection | Transient surge protection |
Protective circuit/component | Varistor |
Connection data, input | |
Connection method | Screw connection |
Conductor cross section solid min. | 0.2 mm² |
Conductor cross section solid max. | 6 mm² |
Conductor cross section flexible min. | 0.2 mm² |
Conductor cross section flexible max. | 4 mm² |
Conductor cross section AWG min. | 22 |
Conductor cross section AWG max. | 10 |
Stripping length | 8 mm |
Screw thread | M3 |
Connection data, output | |
Connection method | Screw connection |
Conductor cross section solid min. | 0.5 mm² |
Conductor cross section solid max. | 16 mm² |
Conductor cross section flexible min. | 0.5 mm² |
Conductor cross section flexible max. | 10 mm² |
Conductor cross section AWG min. | 8 |
Conductor cross section AWG max. | 6 |
Stripping length | 10 mm |
Screw thread | M4 |
Ambient conditions | |
Degree of protection | IP20 |
Ambient temperature (operation) | -25 °C - 70 °C (> 55° C derating : 2.5%/K) |
Ambient temperature (storage/transport) | -40 °C - 85 °C |
Max. permissible relative humidity (operation) | 95 % (at 25 °C, non-condensing) |
Climatic class | 3K3 (in acc. with EN 60721) |
Degree of pollution | 2 |