sub-base - soldered electromechanical relays ABE7 - 16 channels - relay 10 mm
- Manufactured by:
- Schneider Electric
- Price (VAT excluded)
- € 223.34
- Nuova Elva code
- ABE7R16S210
- Manufacturer code
- ABE7R16S210
- Availability
- Send request for quotation
This product is part of the Modicon ABE7 range, an offer of connection sub-bases for Telefast pre-wired system. The sub-base with soldered electromechanical relay, provides 16 channels. It has normally opened contact for pre-actuator. This product enables rapid connection of I/O modules. It is a relay sub base with a supply voltage of 24V DC and a maximum current of 10A per output. It offers electrical durability about 500000 operating cycles. It is an IP2x rated product. Its dimension is 206mm (Width). It weighs 0.405kg. It is suitable for all types of industrial applications. This product is certified by GL, CSA, DNV, BV, LROS and UL. The fixing is done by clips (35mm symmetrical DIN rail) and screws (solid plate with fixing kit). Modicon ABE7 means greater simplicity to rationalise wiring in automation system equipment. Pre-wired system enabling connection and adaptation of control signals of PLC cards equipped with HE10 connectors.
Specifications
Certifications | CSA |
---|---|
Net Weight | 0.405 kg |
Number of Channels | 16 |
Operating Temperature | -5-60 °C IEC 61131-2 |
Storage Temperature | -40-80 °C IEC 61131-2 |
Warranty Length | 18 months |
Width | 206 mm |
Specifications | |
Range Of Product | Modicon ABE7 |
Product Or Component Type | electromechanical output relay sub-base |
Number Of Terminal Per Channel | 2 |
Number Of Channels | 16 |
[Us] Rated Supply Voltage | 24 V DC PLC end |
Contractual warranty | |
Warranty | 18 months |
Complementary | |
Contacts Type And Composition | 1 NO preactuator end |
Electrical Durability | 500000 cycles 600 mA 24 V DC-13 10 ms preactuator end) || 500000 cycles 1500 mA 230 V AC-12 preactuator end) || 500000 cycles 1500 mA 24 V DC-12 preactuator end) || 500000 cycles 900 mA 230 V AC-15 preactuator end) |
Fixing Mode | by clips 35 mm symmetrical DIN rail) || by screws solid plate with fixing kit) |
[Uimp] Rated Impulse Withstand Voltage | 2.5 kV IEC 60947-1 |
Maximum Switching Voltage | 250 V AC 50/60 Hz IEC 60947-5-1 || 30 V DC IEC 60947-5-1 |
Contact Bounce Time | <= 5 ms 1 NO |
Polarity Distribution | volt-free |
Tightening Torque | 0.6 N.m flat Ø 3.5 mm |
Mechanical Durability | 20000000 cycles |
Operating Time | <= 10 ms coil energisation and NO closing || <= 5 ms coil de-energisation and NO opening |
Maximum Power Dissipation Per Channel In W | 0.36 W PLC end) |
Minimum Switching Current | 10 mA >= 5 V |
Drop-Out Voltage | 2.4 V 20 °C PLC end) |
Width | 206 mm |
Operating Rate In Hz | 10 Hz no load || 0.5 Hz at Ie |
Electrical Reliability | 1e-008 |
Threshold Tripping Voltage | 19.7 V 40 °C |
Drop-Out Current | 1 mA 20 °C |
Switching Frequency | <= 0.5 Hz || <= 10 Hz |
Terminal Block Type | removable |
Installation Category | II IEC 60664-1 |
Maximum Current Per Output Common | 10 A |
Current Per Channel | 5 A preactuator end |
[Ui] Rated Insulation Voltage | 2000 V |
Net Weight | 0.405 kg |
Offer Sustainability | |
Rohs Exemption Information | Yes |
Circularity Profile | ENVEOLI1212029EN |
Eu Rohs Directive | Pro-active compliance (Product out of EU RoHS legal scope) |
Mercury Free | Yes |
Environmental Disclosure | ENVPEP121229EN |
Sustainable Offer Status | Green Premium product |
Reach Regulation | Free of Substances of Very High Concern above the threshold |
California Proposition 65 | WARNING: This product can expose you to chemicals including: Lead and lead compounds, which is known to the State of California to cause cancer and birth defects or other reproductive harm. For more information go to www.P65Warnings.ca.gov |
Reach Free Of Svhc | Yes |
Weee | The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins. |
China Rohs Regulation | X |
Environment | |
Product Certifications | GL || CSA || DNV || UL || EAC |
Ambient Air Temperature For Storage | -40-80 °C IEC 61131-2 |
Protective Treatment | TC |
Resistance To Fast Transients | 2 kV level 3 IEC 61000-4-4 |
Resistance To Radiated Fields | 10 V/m 26000000-1000000000 Hz)IEC 61000-4-3 level 3 |
Ambient Air Temperature For Operation | -5-60 °C IEC 61131-2 |
Shock Resistance | 15 gn 11 ms IEC 60068-2-27 |
Dielectric Strength | 2000 V IEC 60947-1 |
Max Immunity To Microbreaks | 5 ms |
Ip Degree Of Protection | IP2X conforming to IEC 60529 |
Pollution Degree | 2 IEC 60664-1 |
Resistance To Incandescent Wire | 750 °C 30 s IEC 60695-2-11 |