soft starter-ATS22-control 220V-power 230V(37kW)/400...440V(75kW)

Manufactured by:
Schneider Electric
Schneider electric

A9bf98aad57a8e35412535960da248bb5c1fb683 medium
Price (VAT excluded)
€ 2748.26
Nuova Elva code
ATS22C14Q
Manufacturer code
ATS22C14Q
Availability
Send request for quotation

This Altistart 22 soft starter can feed 3-phase asynchronous motors in supply line or delta connection. It has a rating of 140A and 230V to 440V, a rated power up to 75kW (400V to 440V in supply line) and up to 110kW (400V to 440V in motor delta connection). It is designed for simple and complex machines such as centrifugal and piston pumps, fans, screw compressors and material handling equipment. Slim form factor improves versatility; allows mounting in frames of any kind of machines. It features an Integrated bypass, this reduces noise and decreases heat dissipation. Compatibility with SoMove software allows configurations and settings to be easily transferred, meaning spares can be quickly installed. It provides smooth starting for your machinery, avoiding mechanical stresses and extending their service life.

Specifications

CertificationsC-tick
Depth229.5 mm
Height356 mm
Net Weight18 kg
Number of Phases3
StandardEN/IEC 60947-4-2
Storage Temperature-25-70 °C
Warranty Length18 months
Width150 mm

Specifications

Product Destinationasynchronous motors
Utilisation CategoryAC-53A
Product Specific Applicationpumps and fans
Ip Degree Of ProtectionIP00
Factory Setting Current131 A
Motor Power Kw37 kW 230 V || 75 kW 400 V || 75 kW 440 V
[Us] Rated Supply Voltage230...440 V - 15...10 %
Range Of ProductAltistart 22
Product Or Component Typesoft starter
Component NameATS22
Phase3 phase
Power Dissipation In W82 W for standard applications
Icl Starter Rating140 A connection in the motor supply line for standard applications
Type Of Startstart with torque control (current limited to 3.5 In)

Contractual warranty

Warranty18 months

Complementary

Device Connectionin the motor supply line || to the motor delta terminals
Power Range30-50 kW 200-240 V 3 phase || 55-100 kW 380-440 V 3 phase
Net Weight18 kg
Output Current0.4...1 Icl adjustable
Installed Device31
Connector Type1 RJ45
Motor Starter Typesoft starter
Communication Data Linkserial
Function Availableinternal bypass
Discrete Output Number2
Control Circuit Consumption20 W
Network Frequency45...66 Hz
Communication Port ProtocolModbus
Supply Voltage Limits195-484 V
Discrete Input TypeLI1, LI2, LI3) logic, 5 mA 4.3 kOhm
Physical InterfaceRS485 multidrop
Type Of Coolingforced convection
Discrete Input Number3
Assembly Stylewith heat sink
Operating Positionvertical +/- 10 degree
Ptc Probe Input750 Ohm
Width150 mm
Minimum Switching Current100 mA 12 V DC relay outputs)
Transmission Rate4800, 9600 or 19200 bps
Depth229.5 mm
Discrete Input Logicpositive logic LI1, LI2, LI3 < 5 V <= 2 mA > 11 V, >= 5 mA
Protection Typephase failure line || thermal protection motor || thermal protection starter
Supply Frequency50...60 Hz - 10...10 %
[Uc] Control Circuit Voltage230 V - 15...10 % 50/60 Hz
Height356 mm
Discrete Output Typerelay outputs R1 230 V running, alarm, trip, stopped, not stopped, starting, ready C/O || relay outputs R2 230 V running, alarm, trip, stopped, not stopped, starting, ready C/O
Maximum Switching Current5 A 250 V AC resistive 1 relay outputs || 5 A 30 V DC resistive 1 relay outputs || 2 A 250 V AC inductive 0.4 20 ms relay outputs || 2 A 30 V DC inductive 7 ms relay outputs
Discrete Input Voltage24 V <= 30 V
MarkingCE

Offer Sustainability

Rohs Exemption InformationYes
Eu Rohs DirectivePro-active compliance (Product out of EU RoHS legal scope)
Mercury FreeYes
Environmental DisclosureENVPEP100401EN
Sustainable Offer StatusGreen Premium product
Reach RegulationReference contains Substances of Very High Concern above the threshold
California Proposition 65WARNING: This product can expose you to chemicals including: Lead and lead compounds, which is known to the State of California to cause cancer and birth defects or other reproductive harm. For more information go to www.P65Warnings.ca.gov
WeeeThe product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins.
China Rohs RegulationX
Circularity ProfileENVEOLI110804EN

Environment

Product CertificationsUL || CSA || C-tick || GOST || CCC
Relative Humidity0-95 % without condensation or dripping water EN/IEC 60068-2-3
Operating Altitude<= 3280.84 ft (1000 m) without derating || > 3280.84...< 6561.68 ft (> 1000...< 2000 m) with current derating of 2.2 % per additional 100 m
StandardsEN/IEC 60947-4-2
Electromagnetic Compatibilityconducted and radiated emissions level A IEC 60947-4-2 || damped oscillating waves level 3 IEC 61000-4-12 || electrostatic discharge level 3 IEC 61000-4-2 || immunity to electrical transients level 4 IEC 61000-4-4 || immunity to radiated radio-electrical interference level 3 IEC 61000-4-3 || voltage/current impulse level 3 IEC 61000-4-5
Ambient Air Temperature For Operation-10-40 °C without derating) || 40-60 °C with current derating 2.2 % per °C)
Shock Resistance15 gn 11 ms EN/IEC 60068-2-27
Vibration Resistance1 gn 13-200 Hz)EN/IEC 60068-2-6 || 1.5 mm 2-13 Hz)EN/IEC 60068-2-6
Pollution Degreelevel 2 IEC 60664-1
Noise Level56 dB
Ambient Air Temperature For Storage-25-70 °C

Docs


Frequently bought together


Other Schneider Electric items

Request a quote