Altivar Soft Starter ATS480, 140 A, 208...690V AC, control supply 110...230V AC
- Manufactured by:
- Schneider Electric
- Price (VAT excluded)
- € 3032.26
- Nuova Elva code
- ATS480C14Y
- Manufacturer code
- ATS480C14Y
- Availability
- Send request for quotation
Altivar Soft Starter ATS480 is intended to start and stop asynchronous motors supplied from 208V to 690V. It meets the requirements of the most demanding applications in normal and heavy duty. With an operational rated current of 140A in normal duty, it supplies motor from 37kW to 110kW according to mains voltage. Designed for digitization, connected, optimized to meet cybersecurity standard, it simplifies project execution and maximizes the availability of applications. Its torque control (TCS) masters acceleration and deceleration. It efficiently stops high inertia application thanks to the dynamic braking and DC injection. It could be connected in-line or inside the delta to reduce its operational current. The embedded test routine simplifies the commissioning inside the delta. Its dimensions are 200mm (width) x 272mm (depth) x 340mm (height) and it weighs 12,4kg. Altivar Soft Starter ATS480 is designed to address process, infrastructures and industrial machines. It conforms to IEC/EN60947-4-1. It is certified CE, cULus, UKCA, CCC, RCM, EAC, and Marine certified DNV, ABS, BV and CCS. Display terminals, remote mounting kit, communication modules are common with Altivar Drives. Line chokes, DNV kits are common with ATS48. ATS480 is compatible with ATS48, it has same footprint, fixing, torque control algorithm, I/O, menus… The integration of Altivar Soft Starter ATS480 in EcoStruxure drastically simplifies architecture selection, detailed design and execution in automation and electrical systems. It is a Green Premium product designed to take the environmental considerations beyond current directives and regulations, compliant with RoHS and REACH.
Specifications
Certifications | ABS |
---|---|
Depth | 272.0 mm |
Height | 340.0 mm |
Net Weight | 12.4 kg |
Number of Phases | 3 |
Standard | EN/IEC 60947-4-2 |
Storage Temperature | -25-70 °C |
Width | 200.0 mm |
Specifications | |
Product Destination | asynchronous motors |
Product Specific Application | process and infrastructures |
Torque Control | true |
Maximum Horse Power Rating | 40.0 hp 208 V normal duty || 30.0 hp 208 V heavy duty || 50.0 hp 230 V normal duty || 40.0 hp 230 V heavy duty || 100.0 hp 460 V normal duty || 75.0 hp 460 V heavy duty || 125.0 hp 575 V normal duty || 100.0 hp 575 V heavy duty |
Device Short Name | ATS480 |
Ip Degree Of Protection | IP00 |
Supply Frequency | 50...60 Hz - 20...20 % |
Option Card | communication module Profibus DP V1 || communication module PROFINET || communication module Modbus TCP/EtherNet/IP || communication module CANopen daisy chain || communication module CANopen Sub-D || communication module CANopen open style |
Range Of Product | Altivar Soft Starter ATS480 |
Product Or Component Type | soft starter |
Maximum Permanent Current | 110.0 A at 40 °C heavy duty |
Motor Power Kw | 37.0 kW 230 V in the motor supply line normal duty || 30.0 kW 230 V in the motor supply line heavy duty || 75.0 kW 400 V in the motor supply line normal duty || 55.0 kW 400 V in the motor supply line heavy duty || 75.0 kW 440 V in the motor supply line normal duty || 55.0 kW 440 V in the motor supply line heavy duty || 90.0 kW 500 V in the motor supply line normal duty || 75.0 kW 500 V in the motor supply line heavy duty || 90.0 kW 525 V in the motor supply line normal duty || 75.0 kW 525 V in the motor supply line heavy duty || 110.0 kW 660 V in the motor supply line normal duty || 90.0 kW 660 V in the motor supply line heavy duty || 110.0 kW 690 V in the motor supply line normal duty || 90.0 kW 690 V in the motor supply line heavy duty || 75.0 kW 230 V to the motor delta terminals normal duty || 55.0 kW 230 V to the motor delta terminals heavy duty || 110.0 kW 400 V to the motor delta terminals normal duty || 90.0 kW 400 V to the motor delta terminals heavy duty |
Phase | 3 phase |
Utilisation Category | AC-3A || AC-53A |
[Ie] Rated Operational Current | normal duty 140.0 A 40 °C) |
[Us] Rated Supply Voltage | 208...690 V - 15...10 % |
Complementary | |
Product Certifications | CE || cULus || CCC || UKCA || RCM || EAC || DNV || ABS || BV || CCS |
Data Format | 8 bits, configurable odd, even or no parity |
Marking | CE || CCC || UKCA || EAC || RCM || cULus |
Output Current Drift | 150-700 % |
Display Screen Available | true |
Net Weight | 12.4 kg |
Relay Output Type | relay outputs R1A 1 NO || relay outputs R1B 1 NO || relay outputs RIC NO/NC programmable |
Connector Type | 1 RJ45 |
Analogue Input Number | 1 |
Communication Data Link | serial |
Function Available | external bypass control || pre-heating || smoke extraction || multi-motor cascade || second motor set || user management || ports and services hardening || security event logging || cybersecure firmware update || single direction |
Device Connection | in the motor supply line || to the motor delta terminals |
Discrete Output Number | 2 |
Communication Port Protocol | Modbus serial |
Discrete Input Type | STOP) logic inputs, 3500 Ohm || RUN) logic inputs, 3500 Ohm || DI3) programmable as logic input, 3500 Ohm || DI4) programmable as logic input, 3500 Ohm |
Minimum Switching Current | 10 mA 24 V DC relay outputs |
Analogue Output Number | 1 |
Physical Interface | 2-wire RS 485 |
Method Of Access | slave Modbus serial |
Integrated Motor Overload Protection | true |
[In] Rated Current Pwr Loss Specifctn | 140.0 A |
Discrete Input Number | 4 |
Height | 340.0 mm |
Accuracy Class | class 10E |
Power Loss Per Device Current Dependent | 366.0 W |
Number Of Addresses | 0-227 Modbus serial |
Apparent Power | 0.09 kVA |
Operating Position | vertical +/- 10 degree |
Power Loss Static Current Independent | 25.0 W |
Type Of Polarization | no impedance Modbus serial |
Width | 200.0 mm |
Transmission Rate | 1200...256000 bit/s |
Depth | 272.0 mm |
Standards | EN/IEC 60947-4-2 || UL 60947-4-2 || IEC 60664-1 |
Discrete Input Logic | programmable digital input < 5 V |
Protection Type | phase failure line || integrated thermal protection motor || thermal protection starter || current overload motor || underload motor || excessive starting time, locked rotor motor || motor phase loss motor || line supply phase loss line || line supply phase loss motor || thermal protection motor |
Discrete Output Type | DQ1) programmable digital output <= 30 V || DQ2) programmable digital output <= 30 V |
Transmission Frame | RTU |
Analogue Output Type | current output AQ1 0...20 mA or 0...10 V 500 Ohm |
[Uc] Control Circuit Voltage | 110...230 V AC 50/60 Hz - 15...10 % |
Maximum Switching Current | relay outputs 2 A 250 V AC || relay outputs 2 A 30 V DC || relay outputs |
Relay Output Number | 3 |
Offer Sustainability | |
Rohs Exemption Information | Yes |
Upgradeability | Upgraded components available |
Eu Rohs Directive | Pro-active compliance (Product out of EU RoHS legal scope) |
Mercury Free | Yes |
Environmental Disclosure | ENVPEP2009022EN |
Sustainable Offer Status | Green Premium product |
Reach Regulation | Reference contains Substances of Very High Concern above the threshold |
California Proposition 65 | WARNING: This product can expose you to chemicals including: Lead and lead compounds, which is known to the State of California to cause cancer and birth defects or other reproductive harm. For more information go to www.P65Warnings.ca.gov |
Weee | The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins. |
China Rohs Regulation | X |
Circularity Profile | ENVEOLI2009022EN |
Environment | |
Maximum Acceleration Under Vibratory Load (During Transport) | 15 m/s² at 200...500 Hz || 10 m/s² at 9...200 Hz |
[Ui] Rated Insulation Voltage | 690 V |
Maximum Acceleration Under Vibrational Stress (During Operation) | 10 m/s² at 13...200 Hz |
Maximum Acceleration Under Vibratory Load (During Storage) | 15 m/s² at 200...500 Hz || 10 m/s² at 9...200 Hz |
Ambient Air Temperature For Storage | -25-70 °C |
Relative Humidity | 0-95 % without condensation or dripping water EN/IEC 60068-2-3 |
Operating Altitude | <= 3280.84 ft (1000 m) without derating || > 3280.84...13123.36 ft (> 1000...4000 m) with current derating 1 % per 100 m |
Maximum Acceleration Under Shock Load (During Storage) | 100 m/s² at 11 ms |
Environmental Class (During Operation) | class 3C3 according to IEC 60721-3-3 || class 3S2 according to IEC 60721-3-3 |
Maximum Deflection Under Vibratory Load (During Storage) | 1.75 mm at 2...9 Hz |
Maximum Acceleration Under Shock Load (During Transport) | 100 m/s² at 11 ms |
Maximum Deflection Under Vibratory Load (During Operation) | 1.5 mm at 2...13 Hz |
Maximum Acceleration Under Shock Impact (During Operation) | 150 m/s² at 11 ms |
[Uimp] Rated Impulse Withstand Voltage | 6 kV |
Pollution Degree | level 3 |
Electromagnetic Compatibility | conducted and radiated emissions level A IEC 60947-4-2 || conducted and radiated emissions with bypass level B IEC 60947-4-2 || damped oscillating waves level 3 IEC 61000-4-12 || electrostatic discharge level 3 IEC 61000-4-11 || immunity to electrical transients level 4 IEC 61000-4-4 || immunity to radiated radio-electrical interference level 3 IEC 61000-4-3 || voltage/current impulse level 3 IEC 61000-4-5 |
Ambient Air Temperature For Operation | 40-60 °C with current derating of 2 % per °C) || -15-40 °C without derating) |
Maximum Deflection Under Vibratory Load (During Transport) | 1.75 mm at 2...9 Hz |