Altivar Soft Starter ATS480, 62 A, 208...690V AC, control supply 110...230V AC

Manufactured by:
Schneider Electric
Schneider%20electric

758d324dec06f3e0900ce3e2e041ec4f358204c4 medium
Price (VAT excluded)
€ 1590.14
Nuova Elva code
ATS480D62Y
Manufacturer code
ATS480D62Y
Availability
Send request for quotation

Altivar Soft Starter ATS480 is intended to start and stop asynchronous motors supplied from 208V to 690V. It meets the requirements of the most demanding applications in normal and heavy duty. With an operational rated current of 62A in normal duty, it supplies motor from 15kW to 45kW according to mains voltage. Designed for digitization, connected, optimized to meet cybersecurity standard, it simplifies project execution and maximizes the availability of applications. Its torque control (TCS) masters acceleration and deceleration. It efficiently stops high inertia application thanks to the dynamic braking and DC injection. It could be connected in-line or inside the delta to reduce its operational current. The embedded test routine simplifies the commissioning inside the delta. Its dimensions are 190mm (width) x 247mm (depth) x 290mm (height) and it weighs 8,3kg. Altivar Soft Starter ATS480 is designed to address process, infrastructures and industrial machines. It conforms to IEC/EN60947-4-1. It is certified CE, cULus, UKCA, CCC, RCM, EAC, and Marine certified DNV, ABS, BV and CCS. Display terminals, remote mounting kit, communication modules are common with Altivar Drives. Line chokes, DNV kits are common with ATS48. ATS480 is compatible with ATS48, it has same footprint, fixing, torque control algorithm, I/O, menus… The integration of Altivar Soft Starter ATS480 in EcoStruxure drastically simplifies architecture selection, detailed design and execution in automation and electrical systems. It is a Green Premium product designed to take the environmental considerations beyond current directives and regulations, compliant with RoHS and REACH.

Specifications

CertificationsABS
Depth247.0 mm
Height290.0 mm
Net Weight8.3 kg
Number of Phases3
StandardEN/IEC 60947-4-2
Storage Temperature-25-70 °C
Width190.0 mm

Specifications

Product Destinationasynchronous motors
Product Specific Applicationprocess and infrastructures
Torque Controltrue
Maximum Horse Power Rating15.0 hp 208 V normal duty || 20.0 hp 230 V normal duty || 15.0 hp 230 V heavy duty || 40.0 hp 460 V normal duty || 30.0 hp 460 V heavy duty || 50.0 hp 575 V normal duty || 40.0 hp 575 V heavy duty
Device Short NameATS480
Ip Degree Of ProtectionIP20
Supply Frequency50...60 Hz - 20...20 %
Option Cardcommunication module Profibus DP V1 || communication module PROFINET || communication module Modbus TCP/EtherNet/IP || communication module CANopen daisy chain || communication module CANopen Sub-D || communication module CANopen open style
Range Of ProductAltivar Soft Starter ATS480
Product Or Component Typesoft starter
Maximum Permanent Current47.0 A at 40 °C heavy duty
Motor Power Kw15.0 kW 230 V in the motor supply line normal duty || 11.0 kW 230 V in the motor supply line heavy duty || 30.0 kW 400 V in the motor supply line normal duty || 22.0 kW 400 V in the motor supply line heavy duty || 30.0 kW 440 V in the motor supply line normal duty || 22.0 kW 440 V in the motor supply line heavy duty || 37.0 kW 500 V in the motor supply line normal duty || 30.0 kW 500 V in the motor supply line heavy duty || 37.0 kW 525 V in the motor supply line normal duty || 30.0 kW 525 V in the motor supply line heavy duty || 45.0 kW 660 V in the motor supply line normal duty || 37.0 kW 660 V in the motor supply line heavy duty || 45.0 kW 690 V in the motor supply line normal duty || 37.0 kW 690 V in the motor supply line heavy duty || 30.0 kW 230 V to the motor delta terminals normal duty || 22.0 kW 230 V to the motor delta terminals heavy duty || 55.0 kW 400 V to the motor delta terminals normal duty || 45.0 kW 400 V to the motor delta terminals heavy duty
Phase3 phase
Utilisation CategoryAC-3A || AC-53A
[Ie] Rated Operational Currentnormal duty 62.0 A 40 °C)
[Us] Rated Supply Voltage208...690 V - 15...10 %

Complementary

Product CertificationsCE || cULus || CCC || UKCA || RCM || EAC || DNV || ABS || BV || CCS
Data Format8 bits, configurable odd, even or no parity
MarkingCE || CCC || UKCA || EAC || RCM || cULus
Output Current Drift150-700 %
Display Screen Availabletrue
Net Weight8.3 kg
Relay Output Typerelay outputs R1A 1 NO || relay outputs R1B 1 NO || relay outputs RIC NO/NC programmable
Connector Type1 RJ45
Analogue Input Number1
Communication Data Linkserial
Function Availableexternal bypass control || pre-heating || smoke extraction || multi-motor cascade || second motor set || user management || ports and services hardening || security event logging || cybersecure firmware update || single direction
Device Connectionin the motor supply line || to the motor delta terminals
Discrete Output Number2
Communication Port ProtocolModbus serial
Discrete Input TypeSTOP) logic inputs, 3500 Ohm || RUN) logic inputs, 3500 Ohm || DI3) programmable as logic input, 3500 Ohm || DI4) programmable as logic input, 3500 Ohm
Minimum Switching Current10 mA 24 V DC relay outputs
Analogue Output Number1
Physical Interface2-wire RS 485
Method Of Accessslave Modbus serial
Integrated Motor Overload Protectiontrue
[In] Rated Current Pwr Loss Specifctn62.0 A
Discrete Input Number4
Height290.0 mm
Accuracy Classclass 10E
Power Loss Per Device Current Dependent181.0 W
Number Of Addresses0-227 Modbus serial
Apparent Power0.09 kVA
Operating Positionvertical +/- 10 degree
Power Loss Static Current Independent25.0 W
Type Of Polarizationno impedance Modbus serial
Width190.0 mm
Transmission Rate1200...256000 bit/s
Depth247.0 mm
StandardsEN/IEC 60947-4-2 || UL 60947-4-2 || IEC 60664-1
Discrete Input Logicprogrammable digital input < 5 V
Protection Typephase failure line || integrated thermal protection motor || thermal protection starter || current overload motor || underload motor || excessive starting time, locked rotor motor || motor phase loss motor || line supply phase loss line || line supply phase loss motor || thermal protection motor
Discrete Output TypeDQ1) programmable digital output <= 30 V || DQ2) programmable digital output <= 30 V
Transmission FrameRTU
Analogue Output Typecurrent output AQ1 0...20 mA or 0...10 V 500 Ohm
[Uc] Control Circuit Voltage110...230 V AC 50/60 Hz - 15...10 %
Maximum Switching Currentrelay outputs 2 A 250 V AC || relay outputs 2 A 30 V DC
Relay Output Number3

Offer Sustainability

Rohs Exemption InformationYes
UpgradeabilityUpgraded components available
Eu Rohs DirectivePro-active compliance (Product out of EU RoHS legal scope)
Mercury FreeYes
Environmental DisclosureENVPEP2009021EN
Sustainable Offer StatusGreen Premium product
Reach RegulationReference contains Substances of Very High Concern above the threshold
California Proposition 65WARNING: This product can expose you to chemicals including: Lead and lead compounds, which is known to the State of California to cause cancer and birth defects or other reproductive harm. For more information go to www.P65Warnings.ca.gov
WeeeThe product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins.
China Rohs RegulationX
Circularity ProfileENVEOLI2009021EN

Environment

Maximum Acceleration Under Vibratory Load (During Transport)15 m/s² at 200...500 Hz || 10 m/s² at 9...200 Hz
[Ui] Rated Insulation Voltage690 V
Maximum Acceleration Under Vibrational Stress (During Operation)10 m/s² at 13...200 Hz
Maximum Acceleration Under Vibratory Load (During Storage)15 m/s² at 200...500 Hz || 10 m/s² at 9...200 Hz
Ambient Air Temperature For Storage-25-70 °C
Relative Humidity0-95 % without condensation or dripping water EN/IEC 60068-2-3
Operating Altitude<= 3280.84 ft (1000 m) without derating || > 3280.84...13123.36 ft (> 1000...4000 m) with current derating 1 % per 100 m
Maximum Acceleration Under Shock Load (During Storage)100 m/s² at 11 ms
Environmental Class (During Operation)class 3C3 according to IEC 60721-3-3 || class 3S2 according to IEC 60721-3-3
Maximum Deflection Under Vibratory Load (During Storage)1.75 mm at 2...9 Hz
Maximum Acceleration Under Shock Load (During Transport)100 m/s² at 11 ms
Maximum Deflection Under Vibratory Load (During Operation)1.5 mm at 2...13 Hz
Maximum Acceleration Under Shock Impact (During Operation)150 m/s² at 11 ms
[Uimp] Rated Impulse Withstand Voltage6 kV
Pollution Degreelevel 3
Electromagnetic Compatibilityconducted and radiated emissions level A IEC 60947-4-2 || conducted and radiated emissions with bypass level B IEC 60947-4-2 || damped oscillating waves level 3 IEC 61000-4-12 || electrostatic discharge level 3 IEC 61000-4-11 || immunity to electrical transients level 4 IEC 61000-4-4 || immunity to radiated radio-electrical interference level 3 IEC 61000-4-3 || voltage/current impulse level 3 IEC 61000-4-5
Ambient Air Temperature For Operation40-60 °C with current derating of 2 % per °C) || -15-40 °C without derating)
Maximum Deflection Under Vibratory Load (During Transport)1.75 mm at 2...9 Hz

Docs


Other Schneider Electric items

Request a quote