variable speed drive ATV212 - 18.5kW - 25hp - 480V - 3ph - EMC - IP21

Manufactured by:
Schneider Electric
Schneider%20electric

068cf37b2a6ca2dabe07603833c28d57580295d7 medium
Price (VAT excluded)
€ 2849.37
Nuova Elva code
ATV212HD18N4
Manufacturer code
ATV212HD18N4
Availability
Send request for quotation

This Altivar 212 variable speed drive can feed 3-phase asynchronous motors. Its protection index is IP21 and it has a built-in EMC filter. It works at a rated power up to 18.5kW / 25hp and a rated voltage from 380V to 480V AC. Its design is based on eco-energy with a reduction in energy consumption of up to 70% compared to a conventional control system. Thanks to its cable temperature rise reduction technology, the Altivar 212 drive offers immediate, disturbance-free operation avoiding additional options such as a line choke or DC choke to deal with current harmonics. It weighs 11.65kg and its dimensions are, 245mm wide, 330mm high, 190mm deep. It is specifically designed for the most common fluid management applications in tertiary sector buildings (HVAC) like heating, ventilation, air conditioning and pumping. It conforms to international standards IEC/EN 61800-5-1 and IEC/EN 61800-3 (immunity and conducted and radiated EMC emissions). It is also CE, UL, CSA, C-Tick and NOM certified. The Altivar 212 offers optional motor chokes which can increase the maximum cable lengths between the drive and the motor and limit disturbance at the motor terminals. It is designed to be mounted in vertical position (+/- 10 °) on a panel, thanks to 4 fixing holes. The Altivar 212 drive can easily be adapted to all building management systems thanks to its numerous functions and communication protocols integrated as standard, Modbus, METASYS N2, APOGEE FLN P1 and BACnet. It is eco-friendly and complies with directives such as RoHS, WEEE, etc.relating to environmental protection.

Specifications

CertificationsC-tick
Depth190 mm
Height330 mm
Net Weight11.65 kg
Number of Phases3
StandardEN 55011 Class A Group 1
Storage Temperature-25-70 °C
Warranty Length18 months
Width245 mm

Specifications

Product Destinationasynchronous motors
Supply Voltage Limits323-528 V
Product Specific Applicationpumps and fans in HVAC
Emc FilterClass C2 EMC filter integrated
Maximum Horse Power Rating25 hp
Device Short NameATV212
Supply Frequency50...60 Hz - 5...5 %
Range Of ProductAltivar 212
Product Or Component Typevariable speed drive
Ip Degree Of ProtectionIP21
Motor Power Kw18.5 kW
Phase3 phase
Line Current27.8 A 480 V || 34.8 A 380 V
[Us] Rated Supply Voltage380...480 V - 15...10 %
Communication Port ProtocolAPOGEE FLN || BACnet || LonWorks || Modbus || METASYS N2

Contractual warranty

Warranty18 months

Complementary

Prospective Line Isc22 kA
Discrete Output Typeconfigurable relay logic FLA, FLC) NO - 100000 cycles || configurable relay logic FLB, FLC) NC - 100000 cycles || configurable relay logic RY, RC) NO - 100000 cycles
Transmission FrameRTU
Torque Accuracy+/- 15 %
Asynchronous Motor Control Profilevoltage/frequency ratio, 5 points || voltage/frequency ratio - Energy Saving, quadratic U/f || voltage/frequency ratio, 2 points || voltage/frequency ratio, automatic IR compensation (U/f + automatic Uo) || flux vector control without sensor, standard
Maximum Switching Current5 A 250 V AC resistive cos phi = 1 L/R = 0 ms FL, R) || 5 A 30 V DC resistive cos phi = 1 L/R = 0 ms FL, R) || 2 A 250 V AC inductive cos phi = 0.4 L/R = 7 ms FL, R) || 2 A 30 V DC inductive cos phi = 0.4 L/R = 7 ms FL, R)
Communication Servicetime out setting from 0.1 to 100 s || read device identification (43) || monitoring inhibitable || read holding registers (03) 2 words maximum || write multiple registers (16) 2 words maximum || write single register (06)
Transient Overtorque120-120 % of nominal motor torque +/- 10 % 60 s
Insulation Resistance>= 1 mOhm 500 V DC for 1 minute
Response TimeFM 2 ms +/- 0.5 ms analog || FLA, FLC 7 ms +/- 0.5 ms discrete || FLB, FLC 7 ms +/- 0.5 ms discrete || RY, RC 7 ms +/- 0.5 ms discrete
Data Format8 bits, 1 stop, odd even or no configurable parity
Electrical ConnectionVIA, VIB, FM, FLA, FLB, FLC, RY, RC, F, R, RES terminal 2.5-2.5 mm² / AWG 14 || L1/R, L2/S, L3/T terminal 25-25 mm² / AWG 3
Apparent Power28.2 kVA 380 V
Dielectric Strength3535 V DC between earth and power terminals || 5092 V DC between control and power terminals
Power Range15-25 kW 380-440 V 3 phase || 15-25 kW 480-500 V 3 phase
Net Weight11.65 kg
Type Of Polarizationno impedance
Frequency Resolutiondisplay unit 0.1 Hz || analog input 0.024/50 Hz
Accuracy+/- 0.6 % VIA) for a temperature variation 60 °C || +/- 0.6 % VIB) for a temperature variation 60 °C || +/- 1 % FM) for a temperature variation 60 °C
Switching Frequency6...16 kHz adjustable || 8...16 kHz with derating factor
Maximum Transient Current40.7 A 60 s
Connector Type1 open style || 1 RJ45
Network Frequency47.5...63 Hz
Analogue Input Number2
Functionalitymid
Motor Slip Compensationnot available in voltage/frequency ratio motor control || automatic whatever the load || adjustable
Motor Starter Typevariable speed drive
Discrete Output Number2
Minimum Switching Current3 mA 24 V DC configurable relay logic
Analogue Output Number1
Physical Interface2-wire RS 485
Power Dissipation In W603 W
Continuous Output Current37 A 380 V || 37 A 460 V
Discrete Input Logicpositive logic (source) F, R, RES), <= 5 V, >= 11 V || negative logic (sink) F, R, RES), >= 16 V, <= 10 V
Number Of Addresses1-247
Tightening Torque0.6 N.m VIA, VIB, FM, FLA, FLB, FLC, RY, RC, F, R, RES) || 4.5 N.m, 40 lb.in L1/R, L2/S, L3/T)
Discrete Input TypeF programmable 24 V DC level 1 PLC 4700 Ohm || R programmable 24 V DC level 1 PLC 4700 Ohm || RES programmable 24 V DC level 1 PLC 4700 Ohm
Speed Range1-10
Isolationelectrical between power and control
Local Signallingfor DC bus energized 1 LED (red)
Linearity ErrorVIA +/- 0.15 % of maximum value input || VIB +/- 0.15 % of maximum value input || FM +/- 0.2 % output
Specific ApplicationHVAC
Output Voltage<= power supply voltage
Nominal Switching Frequency8 kHz
Type Of Cablewithout mounting kit 1 IEC cable 45 °C, copper 90 °C / XLPE/EPR || without mounting kit 1 IEC cable 45 °C, copper 70 °C / PVC || with UL Type 1 kit 3 UL 508 cable 40 °C, copper 75 °C / PVC
Width245 mm
Transmission Rate9600 bps or 19200 bps
Braking To Standstillby DC injection
Air Flow214 m3/h
Depth190 mm
Protection Typeoverheating protection drive || line supply undervoltage drive || against input phase loss drive || thermal protection motor || motor phase break motor || with PTC probes motor || thermal power stage drive || short-circuit between motor phases drive || input phase breaks drive || overcurrent between output phases and earth drive || overvoltages on the DC bus drive || break on the control circuit drive || against exceeding limit speed drive || line supply overvoltage and undervoltage drive
Supplyinternal supply for reference potentiometer (1 to 10 kOhm) 10.5 V DC +/- 5 %, <10 A overload and short-circuit protection || internal supply 24 V DC 21-27 V), <200 A overload and short-circuit protection
Analogue Input TypeVIA switch-configurable voltage 0...10 V DC 24 V max 30000 Ohm 10 bits || VIB configurable voltage 0...10 V DC 24 V max 30000 Ohm 10 bits || VIB configurable PTC probe 0...6 probes 1500 Ohm || VIA switch-configurable current 0...20 mA 250 Ohm 10 bits
Discrete And Process Manufacturingbuilding - HVAC compressor for scroll || building - HVAC fan || building - HVAC pump
Sampling Duration2 ms +/- 0.5 ms F discrete || 2 ms +/- 0.5 ms R discrete || 2 ms +/- 0.5 ms RES discrete || 3.5 ms +/- 0.5 ms VIA analog || 22 ms +/- 0.5 ms VIB analog
Height330 mm
Speed Accuracy+/- 10 % of nominal slip 0.2 Tn to Tn
Option Cardcommunication card LonWorks
Acceleration And Deceleration Rampslinear adjustable separately from 0.01 to 3200 s || automatic based on the load
Analogue Output TypeFM switch-configurable voltage 0...10 V DC 7620 Ohm 10 bits || FM switch-configurable current 0...20 mA 970 Ohm 10 bits
Speed Drive Output Frequency0.5-200 Hz

Offer Sustainability

Rohs Exemption InformationYes
Eu Rohs DirectivePro-active compliance (Product out of EU RoHS legal scope)
Mercury FreeYes
Environmental DisclosureENVPEP110204EN
Sustainable Offer StatusGreen Premium product
Reach RegulationReference contains Substances of Very High Concern above the threshold
California Proposition 65WARNING: This product can expose you to chemicals including: Lead and lead compounds, which is known to the State of California to cause cancer and birth defects or other reproductive harm. For more information go to www.P65Warnings.ca.gov
WeeeThe product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins.
China Rohs RegulationX
Circularity ProfileENVEOLI1102030EN

Environment

Product CertificationsCSA || UL || C-tick || NOM 117
Pollution Degree2 IEC 61800-5-1
Regulation Loopadjustable PI regulator
Ambient Air Temperature For Storage-25-70 °C
Relative Humidity5-95 % without condensation IEC 60068-2-3 || 5-95 % without dripping water IEC 60068-2-3
Assembly Stylewith heat sink
Ip Degree Of ProtectionIP20 on upper part without blanking plate on cover EN/IEC 61800-5-1 || IP20 on upper part without blanking plate on cover EN/IEC 60529 || IP21 EN/IEC 61800-5-1 || IP21 EN/IEC 60529 || IP41 on upper part EN/IEC 61800-5-1 || IP41 on upper part EN/IEC 60529
Operating Altitude3280.84...9842.52 ft (1000...3000 m) limited to 2000 m for the Corner Grounded distribution network with current derating 1 % per 100 m || <= 3280.84 ft (1000 m) without derating
Operating Positionvertical +/- 10 degree
StandardsEN 61800-3 environments 1 category C2 || EN 61800-3 category C2 || IEC 61800-3 || IEC 61800-3 environments 1 category C1 || IEC 61800-5-1 || IEC 61800-3 environments 2 category C1 || IEC 61800-3 environments 2 category C2 || IEC 61800-3 environments 1 category C2 || EN 55011 class A group 1 || EN 61800-3 environments 1 category C3 || IEC 61800-3 environments 1 category C3 || EN 61800-3 || IEC 61800-3 category C3 || EN 61800-3 category C3 || IEC 61800-3 category C2 || EN 61800-5-1 || UL Type 1 || IEC 61800-3 environments 2 category C3 || EN 61800-3 environments 1 category C1 || EN 61800-3 environments 2 category C2 || EN 61800-3 environments 2 category C3 || EN 61800-3 environments 2 category C1
Electromagnetic Compatibilityelectrostatic discharge immunity test level 3 IEC 61000-4-2 || radiated radio-frequency electromagnetic field immunity test level 3 IEC 61000-4-3 || electrical fast transient/burst immunity test level 4 IEC 61000-4-4 || 1.2/50 µs - 8/20 µs surge immunity test level 3 IEC 61000-4-5 || conducted radio-frequency immunity test level 3 IEC 61000-4-6 || voltage dips and interruptions immunity test IEC 61000-4-11
Ambient Air Temperature For Operation-10-40 °C without derating) || 40-50 °C with derating factor)
Shock Resistance15 gn 11 ms IEC 60068-2-27
Environmental Characteristicclasses 3C1 IEC 60721-3-3 || classes 3S2 IEC 60721-3-3
MarkingCE
Vibration Resistance1.5 mm 3-13 Hz)EN/IEC 60068-2-6 || 1 gn 13-200 Hz)EN/IEC 60068-2-8
Noise Level54 dB 86/188/EEC

Docs


Frequently bought together


Other Schneider Electric items

Request a quote