TeSys GB2 thermal magnetic circuit protector, 1 P, 6 A, Id = 83 A

Manufactured by:
Schneider Electric
Schneider electric

719d3461b23dcd538846109e8509dd8dff6a5e28 medium
Price (VAT excluded)
€ 22.91
Nuova Elva code
GB2CB12
Manufacturer code
GB2CB12
Availability
5 in stock

TeSys GB circuit breaker, 1 pole (1P), 6A/250V IEC/277V UL, for the protection of industrial equipment control circuits. It provides thermal-magnetic protection with a magnetic tripping level at 83A (13 In) and breaking capacity Icu 1.5kA@240V. It can also be used for protection of DC loads up to 6A/48V DC-13 with a breaking capacity Icu 1.5kA@24V. Compact device (15mm wide), mounting on 35mm DIN-rail, control by toggle lever (start-stop guaranteed for 8000 cycles). Sold in lots of 6 units. Multi standards certified (IEC, UL, CSA), Green Premium product (RoHS/REACh).

Specifications

CertificationsCSA
Depth67 mm
Height74 mm
Line Rated Current6 A
Mounting TypeClips
StandardCSA C22.2 No 235
Storage Temperature-40-80 °C
Trip Point83-83 A
Warranty Length18 months
Width15 mm

Specifications

Network TypeAC/DC
Network Frequency50/60 Hz IEC 60947-2
Device Applicationcontrol
Device Short NameGB2
Trip Unit Technologythermal-magnetic
Magnetic Tripping Current83-83 A
Product Or Component Typecircuit breaker
Product NameTeSys GB2
Utilisation Categorycategory A IEC 60947-2 || DC-12 IEC 60947-5-1 || DC-13 IEC 60947-5-1
RangeTeSys
[Ics] Rated Service Short-Circuit Breaking Capacity75 % 110 V AC 50/60 Hz IEC 60947-2 || 75 % 230/240 V AC 50/60 Hz IEC 60947-2
Breaking Capacity3 kA Icu 110 V AC 50/60 Hz IEC 60947-2 || 1.5 kA Icu 230/240 V AC 50/60 Hz IEC 60947-2 || 1.5 kA Icu 24 V DC IEC 60947-2 || 1 kA Icu 48 V DC IEC 60947-2
Poles Description1P

Contractual warranty

Warranty18 months

Complementary

Mechanical Robustnessshocks 22 Gn for 20 ms IEC 60068-2-27 || vibrations 5 Gn, 5...110 Hz IEC 60068-2-6
Power Dissipation Per Pole2 W
Electrical Durability8000 cycles
Mounting Modeby clips
Tightening Torque1.2 N.m connector
Mechanical Durability8000 cycles
Quantity Per Setset of 6
Mounting Positionvertical || horizontal
Width15 mm
Depth67 mm
Line Rated Current6 A
[Ue] Rated Operational Voltage250 V AC 50/60 Hz IEC 60947-2 || 277 V AC 60 Hz CSA C22.2 No 235 || 277 V AC 60 Hz UL 1077 || 48 V DC
Height74 mm
Mounting Supportrail || plate
9 Mm Pitches2
Connections - Terminalsconnector 1 0.75-6 mm²solid without cable end || connector 2 0.75-4 mm²solid without cable end || connector 1 0.75-4 mm²flexible with cable end || connector 2 0.75-2.5 mm²flexible with cable end
[Uimp] Rated Impulse Withstand Voltage4 kV IEC 60947-2
Control Typetoggle

Offer Sustainability

Rohs Exemption InformationYes
Mercury FreeYes
Toxic Heavy Metal FreeYes
Reach RegulationFree of Substances of Very High Concern above the threshold
California Proposition 65WARNING: Cancer - www.P65Warnings.ca.gov
Reach Free Of SvhcYes
WeeeThe product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins.
China Rohs RegulationPro-active China RoHS declaration (out of China RoHS legal scope)
Eu Rohs DirectiveCompliant

Environment

Product CertificationsUL || CSA
Ambient Air Temperature For Operation-20-60 °C
StandardsEN/IEC 60947-1 || EN/IEC 60947-2 || CSA C22.2 No 235 || UL 1077
Ambient Air Temperature For Storage-40-80 °C
Protective TreatmentTC
Ip Degree Of ProtectionIP20 IEC 60529
Operating Altitude9842.52 ft (3000 m)
Fire Resistance960 °C IEC 60695-2-1