TeSys GV2 Manual Starter and Protector, magnetic circuit protector, toggle switch, 2.5 A, screw clamp terminals
- Manufactured by:
- Schneider Electric
- Price (VAT excluded)
- € 49.95
- Nuova Elva code
- GV2LE07
- Manufacturer code
- GV2LE07
- Availability
- Standard lead time: 8 days
TeSys GV motor circuit breaker, 3 poles (3P), 2.5A/690V, for 3-phase motor applications 0.75kW@400V. It provides a magnetic protection with a tripping level at 13xIn, high breaking capacity Icu 100kA@400V. Connection by screw clamp terminals. Start-stop control by toggle guaranteed for 100 000 cycles AC-3. To complete motor protection, use in association with a thermal overload relay LRD07 (to be ordered separately). Multi standards certified (IEC, UL, CSA, CCC, EAC, Marine), Green Premium compliant (RoHS/REACh).
Specifications
Certifications | BV |
---|---|
Color | Gray |
Depth | 78.5 mm |
Height | 89 mm |
Line Rated Current | 2.5 A |
Net Weight | 0.33 kg |
Standard | EN/IEC 60947-2 |
Storage Temperature | -40-80 °C |
Trip Point | 33.5-33.5 A |
Warranty Length | 18 months |
Width | 45 mm |
Specifications | |
Product Or Component Type | motor circuit breaker |
Product Name | TeSys GV2 |
Range | TeSys Deca |
Device Application | motor protection |
Device Short Name | GV2LE |
Trip Unit Technology | magnetic |
Contractual warranty | |
Warranty | 18 months |
Complementary | |
Line Rated Current | 2.5 A |
Net Weight | 0.33 kg |
Fixing Mode | 35 mm symmetrical DIN rail clipped || panel screwed with adaptor plate) |
[Uimp] Rated Impulse Withstand Voltage | 6 kV IEC 60947-2 |
[Ics] Rated Service Short-Circuit Breaking Capacity | 100 % 230/240 V AC 50/60 Hz IEC 60947-2 || 100 % 400/415 V AC 50/60 Hz IEC 60947-2 || 100 % 440 V AC 50/60 Hz IEC 60947-2 || 100 % 500 V AC 50/60 Hz IEC 60947-2 || 75 % 690 V AC 50/60 Hz IEC 60947-2 |
Control Type | toggle |
Power Dissipation Per Pole | 1.8 W |
Electrical Durability | 100000 cycles AC-3 415 V In |
[Ui] Rated Insulation Voltage | 690 V AC 50/60 Hz IEC 60947-2 |
Breaking Capacity | 100 kA Icu 230/240 V AC 50/60 Hz IEC 60947-2 || 100 kA Icu 400/415 V AC 50/60 Hz IEC 60947-2 || 100 kA Icu 440 V AC 50/60 Hz IEC 60947-2 || 100 kA Icu 500 V AC 50/60 Hz IEC 60947-2 || 3 kA Icu 690 V AC 50/60 Hz IEC 60947-2 |
Suitability For Isolation | yes IEC 60947-1 § 7-1-6 |
[Ue] Rated Operational Voltage | 690 V AC 50/60 Hz IEC 60947-2 |
Tightening Torque | 1.7 N.m screw clamp terminal |
Mechanical Durability | 100000 cycles |
Poles Description | 3P |
Color | dark grey |
Width | 45 mm |
Depth | 78.5 mm |
Network Frequency | 50/60 Hz IEC 60947-2 |
Height | 89 mm |
Rated Duty | continuous IEC 60947-4-1 |
Network Type | AC |
Magnetic Tripping Current | 33.5-33.5 A |
[Ith] Conventional Free Air Thermal Current | 2.5 A IEC 60947-4-1 |
Motor Power Kw | 0.75-0.75 kW 400/415 V AC 50/60 Hz || 1.1-1.1 kW 400/415 V AC 50/60 Hz || 1.1-1.1 kW 500 V AC 50/60 Hz || 1.5-1.5 kW 690 V AC 50/60 Hz |
Utilisation Category | category A IEC 60947-2 || AC-3 IEC 60947-4-1 |
Offer Sustainability | |
Rohs Exemption Information | Yes |
Eu Rohs Directive | Compliant |
Mercury Free | Yes |
Environmental Disclosure | ENVPEP121004 |
Sustainable Offer Status | Green Premium product |
Reach Regulation | Reference contains Substances of Very High Concern above the threshold |
California Proposition 65 | WARNING: This product can expose you to chemicals including: Antimony oxide & Antimony trioxide, which is known to the State of California to cause cancer. For more information go to www.P65Warnings.ca.gov |
Weee | The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins. |
China Rohs Regulation | Product out of China RoHS scope. Substance declaration for your information. |
Circularity Profile | ENVEOLI121004 |
Environment | |
Product Certifications | CCC || UL || CSA || EAC || LROS (Lloyds register of shipping) || BV || RINA || DNV-GL || UKCA || IECEE CB Scheme |
Fire Resistance | 960 °C IEC 60695-2-11 |
Ik Degree Of Protection | IK04 |
Mechanical Robustness | shocks 30 Gn for 11 ms || vibrations 5 Gn, 5...150 Hz |
Ambient Air Temperature For Operation | -20-60 °C |
Standards | EN/IEC 60947-2 || UL 60947-4-1 |
Climatic Withstand | IACS E10 |
Ambient Air Temperature For Storage | -40-80 °C |
Ip Degree Of Protection | IP20 IEC 60529 |
Operating Altitude | 6561.68 ft (2000 m) |