Motor circuit breaker, TeSys GV4, 3P, 80A, Icu 100kA, thermal magnetic, lugs terminals

Manufactured by:
Schneider Electric
Schneider electric

0b0cb980c0c533d2e1cd6772621e51f14c521537 medium
Price (VAT excluded)
€ 364.05
Nuova Elva code
GV4PE80S6
Manufacturer code
GV4PE80S6
Availability
Send request for quotation

TeSys GV motor circuit breaker, 3 poles (3P), 80A/690V, for protection of 3-phase motors 22-37kW@400V. It provides thermal magnetic protection and additional motor protection functions, breaking capacity Icu 100kA@400V, start-stop control by toggle, connection for bars or cables with lugs. Thermal protection adjustable by dials with a setting current Ir in range 40-80A and a selectable tripping class 10 or 20, magnetic protection at 17 In. Additional protections have fixed pick-up and include short time delay protection Isd at 13 Ir, phase unbalance and loss protection, ground fault protection. It makes internal locations available for additional auxiliary contact blocks (OF, SD), and voltage trip units (MN, MX). Multi standards certified (IEC, UL, CSA, CCC, EAC, Marine, ATEX), Green Premium compliant (RoHS/REACh).

Specifications

CertificationsATEX
ColorGray
Depth116 mm
Height155 mm
Line Rated Current80 A
Net Weight1.45 kg
StandardCSA C22.2 No 60947-4-1
Storage Temperature-50-85 °C
Trip Point1360-1360 A
Warranty Length18 months
Width81 mm

Specifications

Range Of ProductTeSys GV4
Product Or Component Typemotor circuit breaker
Product NameTeSys GV4 || TeSys Deca
RangeTeSys Deca
Device Applicationmotor protection
Device Short NameGV4PE
Trip Unit Technologyelectronic || thermal-magnetic

Contractual warranty

Warranty18 months

Complementary

Mechanical Robustnessvibrations +/- 1 mm 2...13.2 Hz IEC 60068-2-6 || vibrations 0.7 gn 13.2...100 Hz IEC 60068-2-6 || shocks 15 gn 11 ms IEC 60068-2-27
Maximum Operating Rate25 cyc/h
Operating Positionany position
Connections - Terminalslugs-ring terminals
Utilisation Categorycategory A IEC 60947-2 || AC-3 IEC 60947-4-1
Net Weight1.45 kg
[Uimp] Rated Impulse Withstand Voltage8 kV IEC 60947-2
Control Typetoggle
Power Dissipation Per Pole4.6 W
Electrical Durability14000 cycles AC-3 440 V In/2 || 7000 cycles AC-3 440 V In
Breaking Capacity120 kA Icu 220...240 V AC 50/60 Hz IEC 60947-2 || 100 kA Icu 380...415 V AC 50/60 Hz IEC 60947-2 || 70 kA Icu 440 V AC 50/60 Hz IEC 60947-2 || 30 kA Icu 500 V AC 50/60 Hz IEC 60947-2 || 18 kA Icu 525 V AC 50/60 Hz IEC 60947-2 || 100 kA 208Y/120 V AC 50/60 Hz UL 60947 || 100 kA 240 V AC 50/60 Hz UL 60947 || 65 kA 480Y/277 V AC 50/60 Hz UL 60947 || 10 kA Icu 660...690 V AC 50/60 Hz IEC 60947-2 || 25 kA 600Y/347 V AC 50/60 Hz UL 60947
Line Rated Current80 A
Suitability For Isolationyes IEC 60947-1
[Ui] Rated Insulation Voltage800 V AC 50/60 Hz IEC 60947-2
Tightening Torque9 N.m 16-95 mm² || 5 N.m 1.5-10 mm²
Mechanical Durability40000 cycles
Poles Description3P
Connection Pitch27 mm without spreaders || 35 mm with spreaders
ColorGray RAL 7016)
Width81 mm
Depth116 mm
[Ue] Rated Operational Voltage690 V AC 50/60 Hz IEC 60947-2
Height155 mm
Phase Failure Sensitivityyes IEC 60947-4-1
Rated Dutycontinuous IEC 60947-4-1
Magnetic Tripping Current1360-1360 A
[Ith] Conventional Free Air Thermal Current115 A IEC 60947-4-1
Motor Power Kw37-37 kW 400...415 V AC 50/60 Hz || 45-45 kW 500 V AC 50/60 Hz || 22-22 kW 400...415 V AC 50/60 Hz || 30-30 kW 500 V AC 50/60 Hz || 37-37 kW 660...690 V AC 50/60 Hz || 45-45 kW 660...690 V AC 50/60 Hz || 55-55 kW 660...690 V AC 50/60 Hz || 30-30 kW 400...415 V AC 50/60 Hz || 37-37 kW 500 V AC 50/60 Hz

Offer Sustainability

Rohs Exemption InformationYes
Eu Rohs DirectiveCompliant
Halogen Content PerformanceHalogen free plastic parts product
Mercury FreeYes
Environmental DisclosureENVPEP1704004EN
Sustainable Offer StatusGreen Premium product
Pvc FreeYes
Reach RegulationReference contains Substances of Very High Concern above the threshold
WeeeThe product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins.
China Rohs RegulationProduct out of China RoHS scope. Substance declaration for your information.
Circularity ProfileENVEOLI1704004EN

Environment

Product CertificationsIEC || UL || CSA || CCC || EAC || ATEX || EU-RO MR
Fire Resistance960 °C IEC 60695-2-11
Ik Degree Of ProtectionIK07 IEC 62262
Ambient Air Temperature For Operation-25-70 °C
StandardsCSA C22.2 No 60947-4-1 || UL 60947-4-1 || EN/IEC 60947-4-1 || EN/IEC 60947-2
Climatic WithstandIACS E10
Pollution Degree3
Ambient Air Temperature For Storage-50-85 °C
Ip Degree Of ProtectionIP40 IEC 60529
Operating Altitude5000 m