IEC contactor, TeSys Deca, nonreversing, 115A, 75HP at 480VAC, up to 100kA SCCR, 3 phase, 3 NO, 110VAC 50/60Hz coil, open

Manufactured by:
Schneider Electric
Schneider electric

21668195be1d251d4d317e7486d01a34a720301d medium
Price (VAT excluded)
€ 450.00
Nuova Elva code
LC1D115F7
Manufacturer code
LC1D115F7
Availability
Send request for quotation

TeSys D contactors have been designed for perfect integration into control systems. They can be used to create motor starters for almost any type of application. TeSys D contactors are available in 13 contactor ratings for inductive motor applications up to 150 full-load amps and resistive loads up to 200 amps. This 115A inductive 3 pole IEC contactor can be mounted on DIN rail or mounted directly to a panel. Contactors have both Horsepower and Kw motor rating for international acceptance. Contactor is rated for 30HP at 200 to 208VAC, 40HP at 240VAC, 75HP at 480VAC and 100HP at 600VAC three phase. When used with a 480VAC up to 250A circuit breaker, this contactor can have a SCCR up to 100kA. When used with a 600VAC up to 250A circuit breaker, this contactor can have a SCCR up to 50kA. When used with 600VAC Class J or CC fuses up to 250A, this contactor can have a SCCR up to 100kA. Contactor is supplied with a 110 VAC 50/60 Hz coil. Contactor has one normally open and one normally closed auxiliary contact built-in as standard. The NC contact is mirror certified. Screw clamp terminals are used for load and auxiliary connections. An extensive line of accessories makes it easy to meet the requirements of most applications. The contactor is 6.22 inches tall, 4.72 inches wide and 5.35 inches deep. It weighs 5.51 lbs. Contactor is certified to UL, CSA, IEC, CCC, EAC and Marine standards. Contactor also meets the requirements of RoHS/REACh making it a Green Premium product.

Specifications

CertificationsBV
Contact Configuration1 NO + 1 NC
Depth136 mm
Height158 mm
Impedance0.6 MOhm - Ith 200 A 50 Hz Power Circuit
Net Weight2.5 kg
StandardCSA C22.2 No 14
Warranty Length18 months
Width120 mm

Specifications

[Uc] Control Circuit Voltage110 V AC 50/60 Hz
Device Short NameLC1D
[Ue] Rated Operational Voltagepower circuit <= 1000 V AC 25...400 Hz || power circuit <= 300 V DC
Range Of ProductTeSys Deca
Contactor Applicationresistive load || motor control
Product Or Component Typecontactor
RangeTeSys
Utilisation CategoryAC-3 || AC-4 || AC-1 || AC-3e
[Ie] Rated Operational Current200 A 60 °C) <= 440 V AC AC-1 power circuit || 115 A 60 °C) <= 440 V AC AC-3 power circuit || 115 A 60 °C) <= 440 V AC AC-3e power circuit
Poles Description3P

Contractual warranty

Warranty18 months

Complementary

Non-Overlap Time1.5 ms on de-energisation between NC and NO contact || 1.5 ms on energisation between NC and NO contact
Control Circuit TypeAC 50/60 Hz standard
Safety Reliability LevelB10d = 1369863 cycles contactor with nominal load EN/ISO 13849-1 || B10d = 20000000 cycles contactor with mechanical load EN/ISO 13849-1
Pollution Degree3
Insulation Resistance> 10 MOhm signalling circuit
Rated Breaking Capacity1100 A 440 V power circuit IEC 60947
Irms Rated Making Capacity1260 A 440 V power circuit IEC 60947 || 140 A AC signalling circuit IEC 60947-5-1 || 250 A DC signalling circuit IEC 60947-5-1
Associated Fuse Rating250 A gG <= 690 V type 1 power circuit || 200 A gG <= 690 V type 2 power circuit || 10 A gG signalling circuit
[Uimp] Rated Impulse Withstand Voltage8 kV IEC 60947
Inrush Power In Va280-350 VA 60 Hz 0.8 20 °C) || 280-350 VA 50 Hz 0.8 20 °C)
Pole Contact Composition3 NO
Minimum Switching Current5 mA signalling circuit
Connections - Terminalscontrol circuit screw clamp terminals 2 1-2.5 mm² flexible with cable end || control circuit screw clamp terminals 1 1-2.5 mm² flexible with cable end || control circuit screw clamp terminals 1 1-2.5 mm² flexible without cable end || control circuit screw clamp terminals 2 1-2.5 mm² flexible without cable end || control circuit screw clamp terminals 1 1-2.5 mm² solid without cable end || control circuit screw clamp terminals 2 1-2.5 mm² solid without cable end || power circuit connector 1 10-120 mm² flexible without cable end || power circuit connector 2 10-50 mm² flexible without cable end || power circuit connector 1 10-120 mm² flexible with cable end || power circuit connector 2 10-50 mm² flexible with cable end || power circuit connector 1 10-120 mm² solid without cable end || power circuit connector 2 10-50 mm² solid without cable end
Coil Technologybuilt-in bidirectional peak limiting diode suppressor
Operating Time6...20 ms opening || 20...50 ms closing
Minimum Switching Voltage17 V signalling circuit
Maximum Operating Rate2400 cyc/h 60 °C
Signalling Circuit Frequency25...400 Hz
Tightening Torquecontrol circuit 1.2 N.m screw clamp terminals flat Ø 6 mm || control circuit 1.2 N.m screw clamp terminals Philips No 2 || power circuit 12 N.m connector hexagonal 4 mm || control circuit 1.2 N.m screw clamp terminals pozidriv No 2
Electrical Durability0.8 Mcycles 200 A AC-1 <= 440 V || 0.95 Mcycles 115 A AC-3 <= 440 V || 0.95 Mcycles 115 A AC-3e <= 440 V
Mechanical Durability8 Mcycles
Auxiliary Contacts Typemechanically linked 1 NO + 1 NC IEC 60947-5-1 || mirror contact 1 NC IEC 60947-4-1
Power Dissipation Per Pole24 W AC-1 || 7.9 W AC-3 || 7.9 W AC-3e
Compatibility CodeLC1D
Hold-In Power Consumption In Va2-18 VA 60 Hz 0.3 20 °C) || 2-18 VA 50 Hz 0.3 20 °C)
Overvoltage CategoryIII
Maximum Horse Power Rating30 hp 200/208 V at AC 50/60 Hz for 3 phase || 40 hp 230/240 V at AC 50/60 Hz for 3 phase || 75 hp 460/480 V at AC 50/60 Hz for 3 phase || 100 hp 575/600 V at AC 50/60 Hz for 3 phase
Motor Power Kw30 kW 220...230 V AC 50/60 Hz AC-3) || 55 kW 380...400 V AC 50/60 Hz AC-3) || 59 kW 415...440 V AC 50/60 Hz AC-3) || 75 kW 500 V AC 50/60 Hz AC-3) || 80 kW 660...690 V AC 50/60 Hz AC-3) || 65 kW 1000 V AC 50/60 Hz AC-3) || 18.5 kW 400 V AC 50/60 Hz AC-4) || 30 kW 220...230 V AC 50/60 Hz AC-3e) || 55 kW 380...400 V AC 50/60 Hz AC-3e) || 59 kW 415...440 V AC 50/60 Hz AC-3e) || 75 kW 500 V AC 50/60 Hz AC-3e) || 80 kW 660...690 V AC 50/60 Hz AC-3e) || 65 kW 1000 V AC 50/60 Hz AC-3e)
[Ui] Rated Insulation Voltagepower circuit 600 V CSA || power circuit 600 V UL || power circuit 1000 V IEC 60947-4-1 || signalling circuit 690 V IEC 60947-1 || signalling circuit 600 V CSA || signalling circuit 600 V UL
[Icw] Rated Short-Time Withstand Current250 A 40 °C - 10 min power circuit || 550 A 40 °C - 1 min power circuit || 950 A 40 °C - 10 s power circuit || 1100 A 40 °C - 1 s power circuit || 100 A - 1 s signalling circuit || 120 A - 500 ms signalling circuit || 140 A - 100 ms signalling circuit
Heat Dissipation3-8 W 50/60 Hz
Protective Coverwith
Average Impedance0.6 mOhm - Ith 200 A 50 Hz power circuit
Auxiliary Contact Composition1 NO + 1 NC
[Ith] Conventional Free Air Thermal Current200 A 60 °C power circuit
Control Circuit Voltage Limits0.3...0.5 Uc -40-70 °C drop-out AC 50/60 Hz || 0.8...1.15 Uc -40-55 °C operational AC 50/60 Hz || 1...1.15 Uc 55-70 °C operational AC 50/60 Hz
Mounting Supportrail || plate
Contact CompatibilityM13

Offer Sustainability

Rohs Exemption InformationYes
Circularity ProfileENVEOLI100405
Eu Rohs DirectiveCompliant
Mercury FreeYes
Environmental DisclosureENVPEP060301EN
Sustainable Offer StatusGreen Premium product
Pvc FreeYes
Reach RegulationReference contains Substances of Very High Concern above the threshold
California Proposition 65WARNING: This product can expose you to chemicals including: Antimony oxide & Antimony trioxide, which is known to the State of California to cause cancer. For more information go to www.P65Warnings.ca.gov
WeeeThe product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins.
China Rohs RegulationProduct out of China RoHS scope. Substance declaration for your information.

Environment

Product CertificationsBV || UL || GL || DNV || LROS (Lloyds register of shipping) || RINA || CSA || CCC || GOST || UKCA || CE
Operating Altitude0...9842.52 ft (0...3000 m)
Fire Resistance850 °C IEC 60695-2-1
Width120 mm
Depth136 mm
Permissible Ambient Air Temperature Around The Device-40-60 °C || 60-70 °C with derating
Height158 mm
StandardsCSA C22.2 No 14 || EN 60947-4-1 || EN 60947-5-1 || IEC 60947-4-1 || IEC 60947-5-1 || UL 508
Climatic WithstandIACS E10 exposure to damp heat || IEC 60947-1 Annex Q category D exposure to damp heat
Net Weight2.5 kg
Flame RetardanceV1 conforming to UL 94
Protective TreatmentTHIEC 60068-2-30
Ip Degree Of ProtectionIP20 front face IEC 60529
Mechanical Robustnessvibrations contactor open 2 Gn, 5...300 Hz) || vibrations contactor closed 4 Gn, 5...300 Hz) || shocks contactor closed 15 Gn for 11 ms) || shocks contactor open 6 Gn for 11 ms)

Docs


Frequently bought together


Other Schneider Electric items

Request a quote