IEC contactor, TeSys Deca, nonreversing, 32A, 20HP at 480VAC, up to 100kA SCCR, 3 phase, 3 NO, 110VAC 50/60Hz coil, open
- Manufactured by:
- Schneider Electric
TeSys D contactors have been designed for perfect integration into control systems. They can be used to create motor starters for almost any type of application. TeSys D contactors are available in 13 contactor ratings for inductive motor applications up to 150 full-load amps and resistive loads up to 200 amps. This 32A inductive 3 pole IEC contactor can be mounted on DIN rail or mounted directly to a panel. Contactors have both Horsepower and Kw motor rating for international acceptance. Contactor is rated for 7.5HP at 200 to 208VAC, 10HP at 240VAC, 20HP at 480VAC and 30HP at 600VAC three phase. Contactor is also rated for 2HP at 115VAC and 5HP at 240VAC single phase. When used with a 480VAC up to 60A circuit breaker, this contactor can have a SCCR up to 85kA. When used with up to a 600VAC 80A Class J or CC fuse, this contactor can have a SCCR up to 100kA. Contactor is supplied with a 110 VAC 50/60 Hz coil. Contactor has one normally open and one normally closed auxiliary contact built-in as standard. The NC contact is mirror certified. Screw clamp terminals are used for load and auxiliary connections. An extensive line of accessories makes it easy to meet the requirements of most applications. The contactor is 3.35 inches tall, 1.77 inches wide and 3.62 inches deep. It weighs 0.83 lbs. Contactor is certified to UL, CSA, IEC, CCC, EAC and Marine standards. Contactor also meets the requirements of RoHS/REACh making it a Green Premium product.
Specifications
Certifications | BV |
---|---|
Contact Configuration | 1 NO + 1 NC |
Depth | 92 mm |
Height | 85 mm |
Impedance | 2 MOhm - Ith 50 A 50 Hz Power Circuit |
Net Weight | 0.375 kg |
Standard | CSA C22.2 No 14 |
Warranty Length | 18 months |
Width | 45 mm |
Specifications | |
[Uc] Control Circuit Voltage | 110 V AC 50/60 Hz |
[Ue] Rated Operational Voltage | power circuit <= 690 V AC 25...400 Hz || power circuit <= 300 V DC |
Range Of Product | TeSys Deca |
Contactor Application | resistive load || motor control |
Product Or Component Type | contactor |
Utilisation Category | AC-1 || AC-3 || AC-4 || AC-3e |
[Ie] Rated Operational Current | 32 A 60 °C) <= 440 V AC AC-3 power circuit || 50 A 60 °C) <= 440 V AC AC-1 power circuit || 32 A 60 °C) <= 440 V AC AC-3e power circuit |
Poles Description | 3P |
Device Short Name | LC1D |
Contractual warranty | |
Warranty | 18 months |
Complementary | |
Non-Overlap Time | 1.5 ms on de-energisation between NC and NO contact || 1.5 ms on energisation between NC and NO contact |
Control Circuit Type | AC 50/60 Hz standard |
Safety Reliability Level | B10d = 1369863 cycles contactor with nominal load EN/ISO 13849-1 || B10d = 20000000 cycles contactor with mechanical load EN/ISO 13849-1 |
Pollution Degree | 3 |
Insulation Resistance | > 10 MOhm signalling circuit |
Rated Breaking Capacity | 550 A 440 V power circuit IEC 60947 |
Irms Rated Making Capacity | 140 A AC signalling circuit IEC 60947-5-1 || 250 A DC signalling circuit IEC 60947-5-1 || 550 A 440 V power circuit IEC 60947 |
Associated Fuse Rating | 10 A gG signalling circuit IEC 60947-5-1 || 63 A gG <= 690 V type 1 power circuit || 63 A gG <= 690 V type 2 power circuit |
[Uimp] Rated Impulse Withstand Voltage | 6 kV IEC 60947 |
Inrush Power In Va | 70-70 VA 60 Hz 0.75 20 °C) || 70-70 VA 50 Hz 0.75 20 °C) |
Pole Contact Composition | 3 NO |
Minimum Switching Current | 5 mA signalling circuit |
Connections - Terminals | control circuit screw clamp terminals 1 1-4 mm² flexible without cable end || control circuit screw clamp terminals 2 1-4 mm² flexible without cable end || control circuit screw clamp terminals 1 1-4 mm² flexible with cable end || control circuit screw clamp terminals 2 1-2.5 mm² flexible with cable end || control circuit screw clamp terminals 1 1-4 mm² solid without cable end || control circuit screw clamp terminals 2 1-4 mm² solid without cable end || power circuit screw clamp terminals 1 2.5-10 mm² flexible without cable end || power circuit screw clamp terminals 2 2.5-10 mm² flexible without cable end || power circuit screw clamp terminals 1 1-10 mm² flexible with cable end || power circuit screw clamp terminals 2 1.5-6 mm² flexible with cable end || power circuit screw clamp terminals 1 1.5-10 mm² solid without cable end || power circuit screw clamp terminals 2 2.5-10 mm² solid without cable end |
Coil Technology | without built-in suppressor module |
Operating Time | 12...22 ms closing || 4...19 ms opening |
Minimum Switching Voltage | 17 V signalling circuit |
Maximum Operating Rate | 3600 cyc/h 60 °C |
Signalling Circuit Frequency | 25...400 Hz |
Tightening Torque | control circuit 1.7 N.m screw clamp terminals flat Ø 6 mm || control circuit 1.7 N.m screw clamp terminals Philips No 2 || power circuit 2.5 N.m screw clamp terminals flat Ø 6 mm || power circuit 2.5 N.m screw clamp terminals Philips No 2 || control circuit 1.7 N.m screw clamp terminals pozidriv No 2 || power circuit 2.5 N.m screw clamp terminals pozidriv No 2 |
Electrical Durability | 1.65 Mcycles 32 A AC-3 <= 440 V || 1.4 Mcycles 50 A AC-1 <= 440 V || 1.65 Mcycles 32 A AC-3e <= 440 V |
Mechanical Durability | 15 Mcycles |
Auxiliary Contacts Type | mechanically linked 1 NO + 1 NC IEC 60947-5-1 || mirror contact 1 NC IEC 60947-4-1 |
Power Dissipation Per Pole | 2 W AC-3 || 5 W AC-1 || 2 W AC-3e |
Compatibility Code | LC1D |
Hold-In Power Consumption In Va | 7.5-7.5 VA 60 Hz 0.3 20 °C) || 7-7 VA 50 Hz 0.3 20 °C) |
Overvoltage Category | III |
Maximum Horse Power Rating | 2 hp 115 V at AC 50/60 Hz for 1 phase || 5 hp 230/240 V at AC 50/60 Hz for 1 phase || 7.5 hp 200/208 V at AC 50/60 Hz for 3 phase || 10 hp 230/240 V at AC 50/60 Hz for 3 phase || 20 hp 460/480 V at AC 50/60 Hz for 3 phase || 30 hp 575/600 V at AC 50/60 Hz for 3 phase |
Motor Power Kw | 7.5 kW 220...230 V AC 50/60 Hz AC-3) || 15 kW 380...400 V AC 50/60 Hz AC-3) || 15 kW 415...440 V AC 50/60 Hz AC-3) || 18.5 kW 500 V AC 50/60 Hz AC-3) || 18.5 kW 660...690 V AC 50/60 Hz AC-3) || 7.5 kW 400 V AC 50/60 Hz AC-4) || 7.5 kW 220...230 V AC 50/60 Hz AC-3e) || 15 kW 380...400 V AC 50/60 Hz AC-3e) || 15 kW 415...440 V AC 50/60 Hz AC-3e) || 18.5 kW 500 V AC 50/60 Hz AC-3e) || 18.5 kW 660...690 V AC 50/60 Hz AC-3e) |
[Ui] Rated Insulation Voltage | power circuit 690 V IEC 60947-4-1 || power circuit 600 V CSA || power circuit 600 V UL || signalling circuit 690 V IEC 60947-1 || signalling circuit 600 V CSA || signalling circuit 600 V UL |
[Icw] Rated Short-Time Withstand Current | 260 A 40 °C - 10 s power circuit || 430 A 40 °C - 1 s power circuit || 60 A 40 °C - 10 min power circuit || 138 A 40 °C - 1 min power circuit || 100 A - 1 s signalling circuit || 120 A - 500 ms signalling circuit || 140 A - 100 ms signalling circuit |
Heat Dissipation | 2-3 W 50/60 Hz |
Protective Cover | with |
Average Impedance | 2 mOhm - Ith 50 A 50 Hz power circuit |
Auxiliary Contact Composition | 1 NO + 1 NC |
[Ith] Conventional Free Air Thermal Current | 10 A 60 °C signalling circuit || 50 A 60 °C power circuit |
Control Circuit Voltage Limits | 0.3...0.6 Uc -40-70 °C drop-out AC 50/60 Hz || 0.8...1.1 Uc -40-60 °C operational AC 50 Hz || 0.85...1.1 Uc -40-60 °C operational AC 60 Hz || 1...1.1 Uc 60-70 °C operational AC 50/60 Hz |
Mounting Support | plate || rail |
Contact Compatibility | M2 |
Offer Sustainability | |
Rohs Exemption Information | Yes |
Weee | The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins. |
China Rohs Regulation | Pro-active China RoHS declaration (out of China RoHS legal scope) |
Circularity Profile | ENVEOLI1102029EN |
Eu Rohs Directive | Compliant |
Mercury Free | Yes |
Environmental Disclosure | ENVPEP110229EN |
Sustainable Offer Status | Green Premium product |
Pvc Free | Yes |
Toxic Heavy Metal Free | Yes |
Reach Regulation | Free of Substances of Very High Concern above the threshold |
California Proposition 65 | WARNING: This product can expose you to chemicals including: Antimony oxide & Antimony trioxide, which is known to the State of California to cause cancer. For more information go to www.P65Warnings.ca.gov |
Reach Free Of Svhc | Yes |
Environment | |
Product Certifications | GOST || BV || LROS (Lloyds register of shipping) || RINA || CCC || DNV || UL || CSA || GL || UKCA |
Operating Altitude | 0...9842.52 ft (0...3000 m) |
Fire Resistance | 850 °C IEC 60695-2-1 |
Width | 45 mm |
Depth | 92 mm |
Permissible Ambient Air Temperature Around The Device | -40-60 °C || 60-70 °C with derating |
Height | 85 mm |
Standards | CSA C22.2 No 14 || EN 60947-4-1 || EN 60947-5-1 || IEC 60947-4-1 || IEC 60947-5-1 || UL 508 || IEC 60335-1 |
Climatic Withstand | IACS E10 exposure to damp heat || IEC 60947-1 Annex Q category D exposure to damp heat |
Net Weight | 0.375 kg |
Flame Retardance | V1 conforming to UL 94 |
Protective Treatment | THIEC 60068-2-30 |
Ip Degree Of Protection | IP20 front face IEC 60529 |
Mechanical Robustness | vibrations contactor open 2 Gn, 5...300 Hz) || vibrations contactor closed 4 Gn, 5...300 Hz) || shocks contactor closed 15 Gn for 11 ms) || shocks contactor open 8 Gn for 11 ms) |