IEC contactor, TeSys Deca, nonreversing, 38A, 20HP at 480VAC, up to 100kA SCCR, 3 phase, 3 NO, low consumption 24VDC coil

Manufactured by:
Schneider Electric
Schneider electric

C7744c2a6e5451c08d03b57a9135126a8864955e medium
Price (VAT excluded)
€ 171.59
Nuova Elva code
LC1D38BL
Manufacturer code
LC1D38BL
Availability
Send request for quotation

TeSys D contactors have been designed for perfect integration into control systems. They can be used to create motor starters for almost any type of application. TeSys D contactors are available in 13 contactor ratings for inductive motor applications up to 150 full-load amps and resistive loads up to 200 amps. This 38A inductive 3 pole IEC contactor can be mounted on DIN rail or mounted directly to a panel. Contactors have both Horsepower and Kw motor rating for international acceptance. Contactor is rated for 10HP at 200 to 208VAC, 10HP at 240VAC, 20HP at 480VAC and 25HP at 600VAC three phase. Contactor is also rated for 2HP at 115VAC and 5HP at 240VAC single phase. When used with a 480VAC up to 60A circuit breaker, this contactor can have a SCCR up to 85kA. When used with up to a 600VAC 80A Class J or CC fuse, this contactor can have a SCCR up to 100kA. Contactor is supplied with a low consumption 24 VDC coil with transient suppressor module. Contactor has one normally open and one normally closed auxiliary contact built-in as standard. The NC contact is mirror certified. Screw clamp terminals are used for load and auxiliary connections. An extensive line of accessories makes it easy to meet the requirements of most applications. The contactor is 3.35 inches tall, 1.77 inches wide and 3.98 inches deep. It weighs 1.19 lbs. Contactor is certified to UL, CSA, IEC, CCC, EAC and Marine standards. Contactor also meets the requirements of RoHS/REACh making it a Green Premium product.

Specifications

CertificationsBV
Contact Configuration1 NO + 1 NC
Depth101 mm
Height85 mm
Impedance2 MOhm - Ith 50 A 50 Hz Power Circuit
Net Weight0.54 kg
StandardCSA C22.2 No 14
Warranty Length18 months
Width45 mm

Specifications

[Uc] Control Circuit Voltage24 V DC
Device Short NameLC1D
[Ue] Rated Operational Voltagepower circuit <= 690 V AC 25...400 Hz || power circuit <= 300 V DC
Range Of ProductTeSys Deca
Contactor Applicationmotor control || resistive load
Product Or Component Typecontactor
RangeTeSys || TeSys Deca
Utilisation CategoryAC-4 || AC-1 || AC-3 || AC-3e
[Ie] Rated Operational Current50 A 60 °C) <= 440 V AC AC-1 power circuit || 38 A 60 °C) <= 440 V AC AC-3 power circuit || 38 A 60 °C) <= 440 V AC AC-3e power circuit
Poles Description3P

Contractual warranty

Warranty18 months

Complementary

Non-Overlap Time1.5 ms on de-energisation between NC and NO contact || 1.5 ms on energisation between NC and NO contact
Control Circuit TypeDC low consumption
Safety Reliability LevelB10d = 1369863 cycles contactor with nominal load EN/ISO 13849-1 || B10d = 20000000 cycles contactor with mechanical load EN/ISO 13849-1
Pollution Degree3
Hold-In Power Consumption In W2.4-2.4 W 20 °C
Insulation Resistance> 10 MOhm signalling circuit
Rated Breaking Capacity550 A 440 V power circuit IEC 60947
Irms Rated Making Capacity140 A AC signalling circuit IEC 60947-5-1 || 250 A DC signalling circuit IEC 60947-5-1 || 550 A 440 V power circuit IEC 60947
Associated Fuse Rating10 A gG signalling circuit IEC 60947-5-1 || 63 A gG <= 690 V type 1 power circuit || 63 A gG <= 690 V type 2 power circuit
[Uimp] Rated Impulse Withstand Voltage6 kV IEC 60947
Pole Contact Composition3 NO
Minimum Switching Current5 mA signalling circuit
Connections - Terminalscontrol circuit screw clamp terminals 2 1-2.5 mm² flexible with cable end || control circuit screw clamp terminals 1 1-4 mm² flexible without cable end || control circuit screw clamp terminals 2 1-4 mm² flexible without cable end || control circuit screw clamp terminals 1 1-4 mm² flexible with cable end || control circuit screw clamp terminals 1 1-4 mm² solid without cable end || control circuit screw clamp terminals 2 1-4 mm² solid without cable end || power circuit screw clamp terminals 1 2.5-10 mm² flexible without cable end || power circuit screw clamp terminals 2 2.5-10 mm² flexible without cable end || power circuit screw clamp terminals 1 1-10 mm² flexible with cable end || power circuit screw clamp terminals 2 1.5-6 mm² flexible with cable end || power circuit screw clamp terminals 1 1.5-10 mm² solid without cable end || power circuit screw clamp terminals 2 2.5-10 mm² solid without cable end
Coil Technologybuilt-in bidirectional peak limiting diode suppressor
Time Constant40 ms
Operating Time65.45...88.55 ms closing || 20...30 ms opening
Minimum Switching Voltage17 V signalling circuit
Maximum Operating Rate3600 cyc/h 60 °C
Signalling Circuit Frequency25...400 Hz
Tightening Torquecontrol circuit 1.7 N.m screw clamp terminals flat Ø 6 mm || control circuit 1.7 N.m screw clamp terminals Philips No 2 || power circuit 2.5 N.m screw clamp terminals flat Ø 6 mm || power circuit 2.5 N.m screw clamp terminals Philips No 2 || control circuit 1.7 N.m screw clamp terminals pozidriv No 2 || power circuit 2.5 N.m screw clamp terminals pozidriv No 2
Electrical Durability1.4 Mcycles 50 A AC-1 <= 440 V || 1.4 Mcycles 38 A AC-3 <= 440 V || 1.4 Mcycles 38 A AC-3e <= 440 V
Mechanical Durability30 Mcycles
Power Dissipation Per Pole5 W AC-1 || 3 W AC-3 || 3 W AC-3e
Inrush Power In W2.4-2.4 W 20 °C)
Auxiliary Contacts Typemechanically linked 1 NO + 1 NC IEC 60947-5-1 || mirror contact 1 NC IEC 60947-4-1
Compatibility CodeLC1D
Overvoltage CategoryIII
Maximum Horse Power Rating10 hp 230/240 V at AC 50/60 Hz for 3 phase || 10 hp 200/208 V at AC 50/60 Hz for 3 phase || 5 hp 240 V at AC 50/60 Hz for 1 phase || 20 hp 480 V at AC 50/60 Hz for 3 phase || 25 hp 600 V at AC 50/60 Hz for 3 phase
Motor Power Kw18.5 kW 500 V AC 50/60 Hz AC-3) || 18.5 kW 660...690 V AC 50/60 Hz AC-3) || 7.5 kW 400 V AC 50/60 Hz AC-4) || 18.5 kW 380...400 V AC 50/60 Hz AC-3) || 9 kW 220...230 V AC 50/60 Hz AC-3) || 18.5 kW 415...440 V AC 50/60 Hz AC-3) || 18.5 kW 500 V AC 50/60 Hz AC-3e) || 18.5 kW 660...690 V AC 50/60 Hz AC-3e) || 18.5 kW 380...400 V AC 50/60 Hz AC-3e) || 9 kW 220...230 V AC 50/60 Hz AC-3e) || 18.5 kW 415...440 V AC 50/60 Hz AC-3e)
[Ui] Rated Insulation Voltagepower circuit 600 V CSA || power circuit 600 V UL || signalling circuit 690 V IEC 60947-1 || signalling circuit 600 V CSA || signalling circuit 600 V UL || power circuit 690 V IEC 60947-4-1
[Icw] Rated Short-Time Withstand Current60 A 40 °C - 10 min power circuit || 430 A 40 °C - 1 s power circuit || 150 A 40 °C - 1 min power circuit || 310 A 40 °C - 10 s power circuit || 100 A - 1 s signalling circuit || 120 A - 500 ms signalling circuit || 140 A - 100 ms signalling circuit
Protective Coverwith
Average Impedance2 mOhm - Ith 50 A 50 Hz power circuit
Auxiliary Contact Composition1 NO + 1 NC
[Ith] Conventional Free Air Thermal Current10 A 60 °C signalling circuit || 50 A 60 °C power circuit
Control Circuit Voltage Limits0.1...0.3 Uc -40-70 °C drop-out DC || 0.8...1.25 Uc -40-60 °C operational DC || 1...1.25 Uc 60-70 °C operational DC
Mounting Supportrail || plate
Contact CompatibilityM5

Offer Sustainability

Rohs Exemption InformationYes
WeeeThe product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins.
China Rohs RegulationPro-active China RoHS declaration (out of China RoHS legal scope)
Circularity ProfileENVEOLI1102029EN
Eu Rohs DirectiveCompliant
Mercury FreeYes
Environmental DisclosureENVPEP110229EN
Sustainable Offer StatusGreen Premium product
Pvc FreeYes
Toxic Heavy Metal FreeYes
Reach RegulationFree of Substances of Very High Concern above the threshold
California Proposition 65WARNING: This product can expose you to chemicals including: Antimony oxide & Antimony trioxide, which is known to the State of California to cause cancer. For more information go to www.P65Warnings.ca.gov
Reach Free Of SvhcYes

Environment

Product CertificationsGOST || UL || LROS (Lloyds register of shipping) || CCC || DNV || GL || CSA || RINA || BV
Operating Altitude0...9842.52 ft (0...3000 m)
Fire Resistance850 °C IEC 60695-2-1
Width45 mm
Depth101 mm
Permissible Ambient Air Temperature Around The Device-40-60 °C || 60-70 °C with derating
Height85 mm
StandardsCSA C22.2 No 14 || EN 60947-4-1 || EN 60947-5-1 || IEC 60947-4-1 || IEC 60947-5-1 || UL 508 || IEC 60335-1
Climatic WithstandIACS E10 exposure to damp heat || IEC 60947-1 Annex Q category D exposure to damp heat
Net Weight0.54 kg
Flame RetardanceV1 conforming to UL 94
Protective TreatmentTHIEC 60068-2-30
Ip Degree Of ProtectionIP20 front face IEC 60529
Mechanical Robustnessvibrations contactor open 2 Gn, 5...300 Hz) || vibrations contactor closed 4 Gn, 5...300 Hz) || shocks contactor closed 15 Gn for 11 ms) || shocks contactor open 8 Gn for 11 ms)

Docs


Frequently bought together


Other Schneider Electric items

Request a quote