IEC contactor, TeSys D, nonreversing, 40A, 30HP at 480VAC, up to 100kA SCCR, 3 phase, 3 NO, 110VAC 50/60Hz coil, open
- Manufactured by:
- Schneider Electric
TeSys D contactors have been designed for perfect integration into control systems. They can be used to create motor starters for almost any type of application. TeSys D contactors are available in 13 contactor ratings for inductive motor applications up to 150 full-load amps and resistive loads up to 200 amps. This 40A inductive 3 pole IEC contactor can be mounted on DIN rail or mounted directly to a panel. Contactors have both Horsepower and Kw motor rating for international acceptance. Contactor is rated for 10HP at 200 to 208VAC, 10HP at 240VAC, 30HP at 480VAC and 30HP at 600VAC three phase. Contactor is also rated for 3HP at 115VAC and 5HP at 240VAC single phase. When used with a 480VAC up to 110A circuit breaker, this contactor can have a SCCR up to 100kA. When used with up to a 600VAC 90A Class J or CC fuse, this contactor can have a SCCR up to 100kA. Contactor is supplied with a 110 VAC 50/60 Hz coil. Contactor has one normally open and one normally closed auxiliary contact built-in as standard. The NC contact is mirror certified. Screw clamp terminals are used for load and auxiliary connections. An extensive line of accessories makes it easy to meet the requirements of most applications. The contactor is 4.80 inches tall, 2.17 inches wide and 4.72 inches deep. It weighs 1.87 lbs. Contactor is certified to UL, CSA, IEC, CCC, EAC and Marine standards. Contactor also meets the requirements of RoHS/REACh making it a Green Premium product.
Specifications
Certifications | BV |
---|---|
Contact Configuration | 1 NO + 1 NC |
Depth | 119 mm |
Height | 127 mm |
Net Weight | 1.4 kg |
Standard | CSA C22.2 No 14 |
Warranty Length | 18 months |
Width | 75 mm |
Specifications | |
[Uc] Control Circuit Voltage | 110 V AC 50/60 Hz |
Device Short Name | LC1D |
[Ue] Rated Operational Voltage | power circuit <= 690 V AC 25...400 Hz |
Range Of Product | TeSys Deca |
Contactor Application | motor control || resistive load |
Product Or Component Type | contactor |
Range | TeSys |
Utilisation Category | AC-3 || AC-1 || AC-4 || AC-2 || AC-3e |
[Ie] Rated Operational Current | 40 A 60 °C) <= 440 V AC AC-3 power circuit || 60 A 60 °C) <= 440 V AC AC-1 power circuit || 40 A 60 °C) <= 440 V AC AC-3e power circuit |
Poles Description | 3P |
Contractual warranty | |
Warranty | 18 months |
Complementary | |
Non-Overlap Time | 1.5 ms on de-energisation between NC and NO contacts || 1.5 ms on energisation between NC and NO contacts |
Insulation Resistance | > 10 MOhm control circuit |
Rated Breaking Capacity | 800 A 440 V power circuit IEC 60947 |
Irms Rated Making Capacity | 800 A 440 V power circuit IEC 60947 || 140 A AC control circuit IEC 60947-5-1 |
Associated Fuse Rating | 10 A gG control circuit IEC 60947-5-1 || 80 A gG <= 690 V type 1 power circuit || 80 A gG <= 690 V type 2 power circuit |
[Uimp] Rated Impulse Withstand Voltage | 8 kV IEC 60947 |
Inrush Power In Va | 140-140 VA 0.75 20 °C) || 160-160 VA 0.75 20 °C) |
Pole Contact Composition | 3 NO |
Connections - Terminals | control circuit screw clamp terminals 1 1-4 mm² rigid || control circuit screw clamp terminals 2 1-4 mm² rigid || control circuit screw clamp terminals 1 1-4 mm² flexible without cable end || control circuit screw clamp terminals 2 1-4 mm² flexible without cable end || control circuit screw clamp terminals 1 1-2.5 mm² flexible with cable end || control circuit screw clamp terminals 2 1-2.5 mm² flexible with cable end || power circuit screw terminals 1 2.5-25 mm² rigid || power circuit screw terminals 2 2.5-16 mm² rigid || power circuit screw terminals 1 2.5-25 mm² flexible without cable end || power circuit screw terminals 2 2.5-16 mm² flexible without cable end || power circuit screw terminals 1 2.5-25 mm² flexible with cable end || power circuit screw terminals 2 2.5-10 mm² flexible with cable end |
Coil Technology | without built-in bidirectional peak limiting diode suppressor |
Operating Time | 4...19 ms opening || 12...26 ms closing |
Minimum Switching Current | 5 mA control circuit |
Minimum Switching Voltage | 17 V control circuit |
Maximum Operating Rate | 3600 cyc/h 60 °C |
Tightening Torque | control circuit 1.7 N.m screw clamp terminal flat Ø 6 mm || control circuit 1.7 N.m screw clamp terminal Philips No 2 || power circuit 5 N.m screw terminal flat Ø 6 to Ø 8 mm || control circuit 1.7 N.m screw clamp terminal pozidriv No 2 |
Mechanical Durability | 6000000 cycles |
Auxiliary Contacts Type | mechanically linked 1 NO + 1 NC IEC 60947-5-1 || mirror contact 1 NC IEC 60947-4-1 |
Compatibility Code | LC1D |
Hold-In Power Consumption In Va | 13-13 VA 60 Hz 0.3 20 °C) || 15-15 VA 50 Hz 0.3 20 °C) |
Overvoltage Category | III |
Maximum Horse Power Rating | 3 hp 115 V at AC 60 Hz for 1 phase || 5 hp 230/240 V at AC 60 Hz for 1 phase || 10 hp 200/208 V at AC 60 Hz for 3 phase || 10 hp 230/240 V at AC 60 Hz for 3 phase || 30 hp 460/480 V at AC 60 Hz for 3 phase || 30 hp 575/600 V at AC 60 Hz for 3 phase |
Motor Power Kw | 18.5 kW 380...400 V AC 50 Hz AC-3) || 22 kW 500 V AC 50 Hz AC-3) || 30 kW 660...690 V AC 50 Hz AC-3) || 22 kW 1000 V AC 50 Hz AC-3) || 22 kW 415 V AC 50 Hz AC-3) || 22 kW 440 V AC 50 Hz AC-3) || 11 kW 220...230 V AC 50 Hz AC-3) || 9 kW 400 V AC 50 Hz AC-4) || 18.5 kW 380...400 V AC 50 Hz AC-3e) || 22 kW 500 V AC 50 Hz AC-3e) || 30 kW 660...690 V AC 50 Hz AC-3e) || 22 kW 1000 V AC 50 Hz AC-3e) || 22 kW 415 V AC 50 Hz AC-3e) || 22 kW 440 V AC 50 Hz AC-3e) || 11 kW 220...230 V AC 50 Hz AC-3e) |
Power Dissipation Per Pole | 5.4 W AC-1 || 2.4 W AC-3 || 2.4 W AC-3e |
[Ui] Rated Insulation Voltage | control circuit 600 V CSA || control circuit 600 V UL || power circuit 600 V CSA || power circuit 600 V UL || control circuit 690 V IEC 60947-1 || power circuit 690 V IEC 60947-1 |
Heat Dissipation | 4-5 W 50/60 Hz control circuit |
Protective Cover | with |
Auxiliary Contact Composition | 1 NO + 1 NC |
[Ith] Conventional Free Air Thermal Current | 10 A 60 °C control circuit || 60 A 60 °C power circuit |
Control Circuit Voltage Limits | 0.3...0.6 Uc -40-70 °C drop-out AC 50/60 Hz || 0.8...1.1 Uc -40-60 °C operational AC 50 Hz || 0.85...1.1 Uc -40-60 °C operational AC 60 Hz || 1...1.1 Uc 60-70 °C operational AC 50/60 Hz |
Mounting Support | rail || plate |
Control Circuit Type | AC 50/60 Hz |
Safety Reliability Level | B10d = 1369863 cycles contactor with nominal load EN/ISO 13849-1 || B10d = 20000000 cycles contactor with mechanical load EN/ISO 13849-1 |
Offer Sustainability | |
Rohs Exemption Information | Yes |
Weee | The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins. |
China Rohs Regulation | Pro-active China RoHS declaration (out of China RoHS legal scope) |
Circularity Profile | ENVEOLI1503009EN |
Eu Rohs Directive | Compliant |
Mercury Free | Yes |
Environmental Disclosure | ENVPEP1503009EN |
Sustainable Offer Status | Green Premium product |
Pvc Free | Yes |
Toxic Heavy Metal Free | Yes |
Reach Regulation | Free of Substances of Very High Concern above the threshold |
California Proposition 65 | WARNING: This product can expose you to chemicals including: Antimony oxide & Antimony trioxide, which is known to the State of California to cause cancer. For more information go to www.P65Warnings.ca.gov |
Reach Free Of Svhc | Yes |
Environment | |
Product Certifications | CCC || CSA || GL || RINA || UL || DNV || LROS (Lloyds register of shipping) || GOST || BV |
Fire Resistance | 850 °C IEC 60695-2-1 |
Width | 75 mm |
Depth | 119 mm |
Height | 127 mm |
Standards | EN 60947-5-1 || IEC 60947-5-1 || EN 60947-4-1 || UL 508 || IEC 60947-4-1 || CSA C22.2 No 14 |
Climatic Withstand | IACS E10 exposure to damp heat |
Net Weight | 1.4 kg |
Flame Retardance | V1 conforming to UL 94 |
Ip Degree Of Protection | IP2X IEC 60529 || IP2X VDE 0106 |
Mechanical Robustness | shocks contactor opened 10 Gn for 11 ms) || shocks contactor closed 15 Gn for 11 ms) || vibrations contactor opened 2 Gn, 5...300 Hz) || vibrations contactor closed 4 Gn, 5...300 Hz) |
Operating Altitude | 0...9842.52 ft (0...3000 m) |