IEC contactor, TeSys Deca, nonreversing, 95A, 60HP at 480VAC, 3 phase, 3 pole, 3 NO, 240VAC 50/60Hz coil, open style

Manufactured by:
Schneider Electric
Schneider electric

B2ab55f5e827f92efd3671f3e7776d1bcde719e0 medium
Price (VAT excluded)
€ 438.75
Nuova Elva code
LC1D95U7
Manufacturer code
LC1D95U7
Availability
Standard lead time: 10 days

TeSys D contactors have been designed for perfect integration into control systems. They can be used to create motor starters for almost any type of application. TeSys D contactors are available in 13 contactor ratings for inductive motor applications up to 150 full-load amps and resistive loads up to 200 amps. This 95A inductive 3 pole IEC contactor can be mounted on DIN rail or mounted directly to a panel. Contactors have both Horsepower and Kw motor rating for international acceptance. Contactor is rated for 25HP at 200 to 208VAC, 30HP at 240VAC, 60HP at 480VAC and 60HP at 600VAC three phase. Contactor is also rated for 7.5HP at 115VAC and 15HP at 240VAC single phase. Contactor is supplied with a 240 VAC 50/60 Hz coil. Contactor has one normally open and one normally closed auxiliary contact built-in as standard. The NC contact is mirror certified. Screw clamp terminals are used for load and auxiliary connections. An extensive line of accessories makes it easy to meet the requirements of most applications. The contactor is 5.00 inches tall, 3.35 inches wide and 5.12 inches deep. It weighs 3.55 lbs. Contactor is certified to UL, CSA, IEC, CCC, EAC and Marine standards. Contactor also meets the requirements of RoHS/REACh making it a Green Premium product.

Specifications

CertificationsBV
Contact Configuration1 NO + 1 NC
Depth130 mm
Height127 mm
Impedance0.8 MOhm - Ith 125 A 50 Hz Power Circuit
Net Weight1.61 kg
StandardCSA C22.2 No 60947-4-1
Warranty Length18 months
Width85 mm

Specifications

[Uc] Control Circuit Voltage240 V AC 50/60 Hz
Device Short NameLC1D
[Ue] Rated Operational Voltagepower circuit <= 690 V AC 25...400 Hz
Range Of ProductTeSys Deca
Contactor Applicationmotor control || resistive load
Product Or Component Typecontactor
RangeTeSys
Utilisation CategoryAC-3 || AC-3e || AC-4 || AC-1
[Ie] Rated Operational Current95 A 60 °C) <= 440 V AC-3 power circuit || 125 A 60 °C) <= 690 V AC-1 power circuit || 95 A 60 °C) <= 440 V AC-3e power circuit
Poles Description3P

Contractual warranty

Warranty18 months

Complementary

Non-Overlap Time1.5 ms on de-energisation between NC and NO contact || 1.5 ms on energisation between NC and NO contact
Control Circuit TypeAC 50/60 Hz
Safety Reliability LevelB10d = 1.3 Mcycles contactor with nominal load EN/ISO 13849-1 || B10d = 20 Mcycles contactor with mechanical load EN/ISO 13849-1
Pollution Degree3
Insulation Resistance> 10 MOhm signalling circuit
Rated Breaking Capacity1100 A 440 V power circuit IEC 60947
Irms Rated Making Capacity1100 A 440 V AC power circuit IEC 60947 || 140 A AC signalling circuit IEC 60947-5-1 || 250 A DC signalling circuit IEC 60947-5-1
Associated Fuse Rating10 A gG signalling circuit IEC 60947-5-1 || 200 A gG <= 690 V type 1 power circuit || 160 A gG <= 690 V type 2 power circuit
[Uimp] Rated Impulse Withstand Voltage8 kV IEC 60947
Inrush Power In Va245-245 VA 60 Hz 0.75 20 °C) || 245-245 VA 50 Hz 0.75 20 °C)
Pole Contact Composition3 NO
Minimum Switching Current5 mA signalling circuit
Connections - Terminalscontrol circuit screw clamp terminals 2 1-2.5 mm² flexible with cable end || control circuit screw clamp terminals 1 1-2.5 mm² flexible with cable end || control circuit screw clamp terminals 1 1-4 mm² flexible without cable end || control circuit screw clamp terminals 2 1-4 mm² flexible without cable end || control circuit screw clamp terminals 1 1-4 mm² solid without cable end || control circuit screw clamp terminals 2 1-4 mm² solid without cable end || power circuit connector 1 4-50 mm² flexible without cable end || power circuit connector 2 4-25 mm² flexible without cable end || power circuit connector 1 4-50 mm² flexible with cable end || power circuit connector 2 4-16 mm² flexible with cable end || power circuit connector 1 4-50 mm² solid without cable end || power circuit connector 2 4-25 mm² solid without cable end
Coil Technologywithout built-in suppressor module
Operating Time20...35 ms closing || 6...20 ms opening
Minimum Switching Voltage17 V signalling circuit
Maximum Operating Rate3600 cyc/h 60 °C
Signalling Circuit Frequency25...400 Hz
Tightening Torquecontrol circuit 1.2 N.m screw clamp terminals flat Ø 6 mm || control circuit 1.2 N.m screw clamp terminals Philips No 2 || power circuit 12 N.m connector flat Ø 6 to Ø 8 mm || power circuit 12 N.m connector hexagonal 4 mm || control circuit 1.2 N.m screw clamp terminals pozidriv No 2
Electrical Durability1.2 Mcycles 95 A AC-3 || 1.3 Mcycles 125 A AC-1 || 1.2 Mcycles 95 A AC-3e
Mechanical Durability4 Mcycles
Auxiliary Contacts Typemechanically linked 1 NO + 1 NC IEC 60947-5-1 || mirror contact 1 NC IEC 60947-4-1
Power Dissipation Per Pole12.5 W AC-1 || 7.2 W AC-3 || 7.2 W AC-3e
Compatibility CodeLC1D
Hold-In Power Consumption In Va26-26 VA 60 Hz 0.3 20 °C) || 26-26 VA 50 Hz 0.3 20 °C)
Overvoltage CategoryIII
Maximum Horse Power Rating7.5 hp 120 V at AC 60 Hz for 1 phase || 15 hp 230/240 V at AC 60 Hz for 1 phase || 30 hp 200/208 V at AC 60 Hz for 3 phase || 30 hp 230/240 V at AC 60 Hz for 3 phase || 60 hp 460/480 V at AC 60 Hz for 3 phase || 60 hp 575/600 V at AC 60 Hz for 3 phase
Motor Power Kw25 kW 220...230 V AC 50 Hz AC-3) || 45 kW 380...400 V AC 50 Hz AC-3) || 45 kW 415...440 V AC 50 Hz AC-3) || 55 kW 500 V AC 50 Hz AC-3) || 45 kW 660...690 V AC 50 Hz AC-3) || 15 kW 400 V AC 50 Hz AC-4) || 25 kW 220...230 V AC 50 Hz AC-3e) || 45 kW 380...400 V AC 50 Hz AC-3e) || 45 kW 415...440 V AC 50 Hz AC-3e) || 55 kW 500 V AC 50 Hz AC-3e) || 45 kW 660...690 V AC 50 Hz AC-3e)
[Ui] Rated Insulation Voltagepower circuit 1000 V IEC 60947-4-1 || power circuit 600 V CSA || power circuit 600 V UL || signalling circuit 690 V IEC 60947-1 || signalling circuit 600 V CSA || signalling circuit 600 V UL
[Icw] Rated Short-Time Withstand Current1100 A 40 °C - 1 s power circuit || 800 A 40 °C - 10 s power circuit || 400 A 40 °C - 1 min power circuit || 135 A 40 °C - 10 min power circuit || 140 A - 100 ms signalling circuit || 120 A - 500 ms signalling circuit || 100 A - 1 s signalling circuit
Heat Dissipation6-10 W 50/60 Hz
Protective Coverwith
Average Impedance0.8 mOhm - Ith 125 A 50 Hz power circuit
Auxiliary Contact Composition1 NO + 1 NC
[Ith] Conventional Free Air Thermal Current10 A 60 °C signalling circuit || 125 A 60 °C power circuit
Control Circuit Voltage Limits0.8...1.1 Uc -40-55 °C operational AC 50 Hz || 0.85...1.1 Uc -40-55 °C operational AC 60 Hz || 0.3...0.6 Uc -40-70 °C drop-out AC 50/60 Hz || 1...1.1 Uc 55-70 °C operational AC 50/60 Hz
Mounting Supportrail || plate
Contact CompatibilityM11

Offer Sustainability

Rohs Exemption InformationYes
WeeeThe product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins.
China Rohs RegulationPro-active China RoHS declaration (out of China RoHS legal scope)
Eu Rohs DirectiveCompliant
Mercury FreeYes
Environmental DisclosureENVPEP110205EN
Sustainable Offer StatusGreen Premium product
Pvc FreeYes
Toxic Heavy Metal FreeYes
Reach RegulationFree of Substances of Very High Concern above the threshold
California Proposition 65WARNING: This product can expose you to chemicals including: Antimony oxide & Antimony trioxide, which is known to the State of California to cause cancer. For more information go to www.P65Warnings.ca.gov
Reach Free Of SvhcYes

Environment

Product CertificationsIECEE CB Scheme || UL || CSA || CCC || EAC || LROS (Lloyds register of shipping) || RINA || BV || DNV-GL
Operating Altitude0...9842.52 ft (0...3000 m)
Fire Resistance850 °C IEC 60695-2-1
Width85 mm
Depth130 mm
Permissible Ambient Air Temperature Around The Device-40-60 °C || 60-70 °C with derating
Height127 mm
StandardsEN/IEC 60947-1 || EN/IEC 60947-4-1 || EN/IEC 60947-5-1 || UL 60947-4-1 || UL 60947-5-1 || CSA C22.2 No 60947-4-1 || CSA C22.2 No 60947-5-1 || GB/T 14048.4
Climatic WithstandIACS E10 exposure to damp heat
Net Weight1.61 kg
Flame RetardanceV1 conforming to UL 94
Protective TreatmentTHIEC 60068-2-30
Ip Degree Of ProtectionIP20 front face IEC 60529
Mechanical Robustnessvibrations contactor open 2 Gn, 5...300 Hz) || shocks contactor open 8 Gn for 11 ms) || vibrations contactor closed 3 Gn, 5...300 Hz) || shocks contactor closed 10 Gn for 11 ms)

Docs


Frequently bought together


Other Schneider Electric items