IEC contactor, TeSys Deca, nonreversing, 60A resistive, 4 pole, 4 NO, 48VAC 50/60Hz coil, open style

Manufactured by:
Schneider Electric
Schneider electric

Cc430dae75eb7ba6f32908bcf2a1e71f61c1a9b3 medium
Price (VAT excluded)
€ 284.85
Nuova Elva code
LC1DT60AE7
Manufacturer code
LC1DT60AE7
Availability
Standard lead time: 7 days

TeSys D contactors have been designed for perfect integration into control systems. They can be used to create motor starters for almost any type of application. TeSys D contactors are available in 13 contactor ratings for inductive motor applications up to 150 full-load amps and resistive loads up to 200 amps. This 4 pole IEC contactor can be mounted on DIN rail or mounted directly to a panel. Contactor has four normally open power contacts. Power contacts have a 60A resistive load rating. Contactor is supplied with a 48 VAC 50/60 Hz coil. Contactor has one normally open and one normally closed auxiliary contact built-in as standard. The NC contact is mirror certified. Screw clamp terminals are used for load and auxiliary connections. An extensive line of accessories makes it easy to meet the requirements of most applications. The contactor is 4.80 inches tall, 2.76 inches wide and 4.72 inches deep. It weighs 2.40 lbs. Contactor is certified to UL, CSA, IEC, CCC, EAC and Marine standards. Contactor also meets the requirements of RoHS/REACh making it a Green Premium product.

Specifications

CertificationsBV
Contact Configuration1 NO + 1 NC
Depth120 mm
Height122 mm
Impedance1.6 MOhm - Ith 60 A 50 Hz Power Circuit
Net Weight1.09 kg
StandardCSA C22.2 No 14
Warranty Length18 months
Width70 mm

Specifications

[Uc] Control Circuit Voltage48 V AC 50/60 Hz
Device Short NameLC1D
[Ue] Rated Operational Voltagepower circuit <= 690 V AC 25...400 Hz || power circuit <= 300 V DC
Range Of ProductTeSys Deca
Contactor Applicationresistive load
Product Or Component Typecontactor
RangeTeSys || TeSys Deca
Utilisation CategoryAC-1
[Ie] Rated Operational Current60 A 60 °C) <= 440 V AC AC-1 power circuit
Poles Description4P

Contractual warranty

Warranty18 months

Complementary

Non-Overlap Time1.5 ms on de-energisation between NC and NO contact || 1.5 ms on energisation between NC and NO contact
Control Circuit TypeAC 50/60 Hz
Safety Reliability LevelB10d = 1369863 cycles contactor with nominal load EN/ISO 13849-1 || B10d = 20000000 cycles contactor with mechanical load EN/ISO 13849-1
Pollution Degree3
Insulation Resistance> 10 MOhm signalling circuit
Rated Breaking Capacity800 A 440 V power circuit IEC 60947
Irms Rated Making Capacity140 A AC signalling circuit IEC 60947-5-1 || 250 A DC signalling circuit IEC 60947-5-1 || 800 A 440 V power circuit IEC 60947
Associated Fuse Rating10 A gG signalling circuit IEC 60947-5-1 || 80 A gG <= 690 V type 1 power circuit || 80 A gG <= 690 V type 2 power circuit
[Uimp] Rated Impulse Withstand Voltage6 kV IEC 60947
Inrush Power In Va140-140 VA 60 Hz 0.75 20 °C) || 160-160 VA 50 Hz 0.75 20 °C)
Pole Contact Composition4 NO
Minimum Switching Current5 mA signalling circuit
Connections - Terminalscontrol circuit screw clamp terminals 2 1-2.5 mm² flexible with cable end || control circuit screw clamp terminals 1 1-4 mm² flexible without cable end || control circuit screw clamp terminals 2 1-4 mm² flexible without cable end || control circuit screw clamp terminals 1 1-4 mm² flexible with cable end || control circuit screw clamp terminals 1 1-4 mm² solid without cable end || control circuit screw clamp terminals 2 1-4 mm² solid without cable end || power circuit screw clamp terminal 1 1-35 mm² flexible without cable end || power circuit screw clamp terminal 2 1-25 mm² flexible without cable end || power circuit screw clamp terminal 1 1-35 mm² flexible with cable end || power circuit screw clamp terminal 2 1-25 mm² flexible with cable end || power circuit screw clamp terminal 1 1-35 mm² solid without cable end || power circuit screw clamp terminal 2 1-25 mm² solid without cable end
Coil Technologywithout built-in suppressor module
Operating Time4...19 ms opening || 12...26 ms closing
Minimum Switching Voltage17 V signalling circuit
Maximum Operating Rate3600 cyc/h 60 °C
Signalling Circuit Frequency25...400 Hz
Tightening Torquecontrol circuit 1.7 N.m EverLink BTR screw connectors flat Ø 6 mm || control circuit 1.7 N.m EverLink BTR screw connectors Philips No 2 || power circuit 8 N.m EverLink BTR screw connectors 25-35 mm² hexagonal 4 mm || power circuit 5 N.m EverLink BTR screw connectors 1-25 mm² hexagonal 4 mm || control circuit 1.7 N.m EverLink BTR screw connectors pozidriv No 2 || power circuit 2.5 N.m EverLink BTR screw connectors pozidriv No 2
Electrical Durability1.4 Mcycles 60 A AC-1 <= 440 V
Mechanical Durability6 Mcycles
Auxiliary Contacts Typemechanically linked 1 NO + 1 NC IEC 60947-5-1 || mirror contact 1 NC IEC 60947-4-1
Power Dissipation Per Pole5.8 W AC-1
Compatibility CodeLC1D
Hold-In Power Consumption In Va13-13 VA 60 Hz 0.3 20 °C) || 15-15 VA 50 Hz 0.3 20 °C)
Overvoltage CategoryIII
[Ui] Rated Insulation Voltagepower circuit 600 V CSA || power circuit 600 V UL || signalling circuit 690 V IEC 60947-1 || signalling circuit 600 V CSA || signalling circuit 600 V UL || power circuit 690 V IEC 60947-4-1
[Icw] Rated Short-Time Withstand Current320 A 40 °C - 10 s power circuit || 720 A 40 °C - 1 s power circuit || 72 A 40 °C - 10 min power circuit || 165 A 40 °C - 1 min power circuit || 100 A - 1 s signalling circuit || 120 A - 500 ms signalling circuit || 140 A - 100 ms signalling circuit
Heat Dissipation4-5 W 50/60 Hz
Protective Coverwith
Average Impedance1.6 mOhm - Ith 60 A 50 Hz power circuit
Auxiliary Contact Composition1 NO + 1 NC
[Ith] Conventional Free Air Thermal Current10 A 60 °C signalling circuit || 60 A 60 °C power circuit
Control Circuit Voltage Limits0.3...0.6 Uc -40-70 °C drop-out AC 50/60 Hz || 0.8...1.1 Uc -40-60 °C operational AC 50 Hz || 0.85...1.1 Uc -40-60 °C operational AC 60 Hz || 1...1.1 Uc 60-70 °C operational AC 50/60 Hz
Mounting Supportrail || plate
Contact CompatibilityM6

Offer Sustainability

Rohs Exemption InformationYes
WeeeThe product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins.
China Rohs RegulationPro-active China RoHS declaration (out of China RoHS legal scope)
Circularity ProfileENVEOLI1503009EN
Eu Rohs DirectiveCompliant
Mercury FreeYes
Environmental DisclosureENVPEP1503009EN
Sustainable Offer StatusGreen Premium product
Pvc FreeYes
Toxic Heavy Metal FreeYes
Reach RegulationFree of Substances of Very High Concern above the threshold
California Proposition 65WARNING: This product can expose you to chemicals including: Antimony oxide & Antimony trioxide, which is known to the State of California to cause cancer. For more information go to www.P65Warnings.ca.gov
Reach Free Of SvhcYes

Environment

Product CertificationsRINA || GL || DNV || CSA || BV || LROS (Lloyds register of shipping) || GOST || UL || CCC
Operating Altitude0...9842.52 ft (0...3000 m)
Fire Resistance850 °C IEC 60695-2-1
Width70 mm
Depth120 mm
Permissible Ambient Air Temperature Around The Device-40-60 °C || 60-70 °C with derating
Height122 mm
StandardsCSA C22.2 No 14 || EN 60947-4-1 || EN 60947-5-1 || IEC 60947-4-1 || IEC 60947-5-1 || UL 508 || IEC 60335-1
Climatic WithstandIACS E10 exposure to damp heat || IEC 60947-1 Annex Q category D exposure to damp heat
Net Weight1.09 kg
Flame RetardanceV1 conforming to UL 94
Protective TreatmentTHIEC 60068-2-30
Ip Degree Of ProtectionIP20 front face IEC 60529
Mechanical Robustnessvibrations contactor open 2 Gn, 5...300 Hz) || vibrations contactor closed 4 Gn, 5...300 Hz) || shocks contactor closed 15 Gn for 11 ms) || shocks contactor open 10 Gn for 11 ms)

Docs


Frequently bought together


Other Schneider Electric items

Request a quote