TeSys F contactor - 3P (3 NO) - AC-3 - <= 440 V 115 A - coil 110 V AC

Manufactured by:
Schneider Electric
Schneider%20electric

075b95e914533f7240bfaca9456181c4201dd82d medium
Price (VAT excluded)
€ 618.30
Nuova Elva code
LC1F115F7
Manufacturer code
LC1F115F7
Availability
Send request for quotation

TeSys F contactor, 3 poles (3NO), 115A/690V AC-3, for motor applications up to 55kW@400V. It provides a low sealed consumption 110V 40-400Hz AC coil, bolt terminals for bars or cables with lugs. For high operating rates until 2400 cycles/hour and environments until 55°C, it procures high reliability and durability. It makes installation and maintenance easy thanks to its drawer-mounted coil and a large choice of add-on blocks and accessories (to be ordered separately). Multi standards certified (IEC, UL, CSA, CCC, EAC, Marine), Green Premium compliant (RoHS/REACh).

Specifications

CertificationsABS
Contact Configuration3 NO
Depth171 mm
Height162 mm
Impedance0.37 MOhm - Ith 200 A 50 Hz
Net Weight3.43 kg
StandardEN 60947-1
Storage Temperature-60-80 °C
Warranty Length18 months
Width163.3 mm

Specifications

[Uc] Control Circuit Voltage110 V AC 40...400 Hz
Device Short NameLC1F
Range Of ProductTeSys F
[Ue] Rated Operational Voltage<= 690 V AC 50/60 Hz || <= 460 V DC
Contactor Applicationmotor control || resistive load
Product Or Component Typecontactor
RangeTeSys
Utilisation CategoryAC-4 || AC-1 || AC-3
[Ie] Rated Operational Current200 A 40 °C) <= 440 V AC-1 || 115 A 55 °C) <= 440 V AC-3
Poles Description3P

Contractual warranty

Warranty18 months

Complementary

Product CertificationsCCC || CB || RMRoS || LROS (Lloyds register of shipping) || DNV || ABS || RINA || UL || BV || UKCA
Associated Fuse Rating125 A aM <= 440 V || 200 A gG <= 440 V
[Uimp] Rated Impulse Withstand Voltage8 kV
Inrush Power In Va770-770 VA, 40...400 Hz 0.9 20 °C)
Connections - Terminalspower circuit bar 2 20 x 3 mm || power circuit lugs-ring terminals 1 95-95 mm² || power circuit connector 1 95-95 mm² || control circuit screw clamp terminals 1 1-4 mm²flexible without cable end || control circuit screw clamp terminals 2 1-4 mm²flexible without cable end || control circuit screw clamp terminals 1 1-4 mm²flexible with cable end || control circuit screw clamp terminals 2 1-2.5 mm²flexible with cable end || control circuit screw clamp terminals 1 1-4 mm²solid without cable end || control circuit screw clamp terminals 2 1-4 mm²solid without cable end || power circuit bolted connection
Pole Contact Composition3 NO
Operating Time35 ms closing at Uc) || 130 ms opening at Uc)
Maximum Operating Rate2400 cyc/h 55 °C
Mechanical Durability10 Mcycles
Tightening Torquepower circuit 10 N.m || control circuit 1.2 N.m
Compatibility CodeLC1F
Power Dissipation Per Pole15 W AC-1 || 5 W AC-3
Hold-In Power Consumption In Va8.1-8.1 VA, 40...400 Hz 0.9 20 °C)
Overvoltage CategoryIII
Motor Power Kw55 kW 380...400 V AC 50/60 Hz AC-3) || 59 kW 415 V AC 50/60 Hz AC-3) || 59 kW 440 V AC 50/60 Hz AC-3) || 75 kW 500 V AC 50/60 Hz AC-3) || 80 kW 660...690 V AC 50/60 Hz AC-3) || 30 kW 220...230 V AC 50/60 Hz AC-3) || 18.5 kW 400 V AC 50/60 Hz AC-4)
[Ui] Rated Insulation Voltage1000 V IEC 60947-4-1 || 1500 V VDE 0110 group C
[Icw] Rated Short-Time Withstand Current1100 A 40 °C - 10 s || 640 A 40 °C - 30 s || 520 A 40 °C - 1 min || 400 A 40 °C - 3 min || 320 A 40 °C - 10 min
Heat Dissipation5.9-7.2 W
Average Impedance0.37 mOhm - Ith 200 A 50 Hz
[Ith] Conventional Free Air Thermal Current200 A 40 °C
Control Circuit Voltage Limitsoperational 0.85...1.1 Uc 40...400 Hz 55 °C) || drop-out 0.2...0.55 Uc 40...400 Hz 55 °C)
StandardsEN 60947-4-1 || IEC 60947-1 || IEC 60947-4-1 || EN 60947-1 || JIS C8201-4-1
Mounting Supportplate
Control Circuit TypeAC 40...400 Hz
Rated Breaking Capacity920 A IEC 60947-4-1

Offer Sustainability

Rohs Exemption InformationYes
Eu Rohs DirectiveCompliant
Mercury FreeYes
Environmental DisclosureENVPEP111201EN
Sustainable Offer StatusGreen Premium product
Reach RegulationReference contains Substances of Very High Concern above the threshold
California Proposition 65WARNING: This product can expose you to chemicals including: Lead and lead compounds, which is known to the State of California to cause cancer and birth defects or other reproductive harm. For more information go to www.P65Warnings.ca.gov
WeeeThe product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins.
China Rohs RegulationProduct out of China RoHS scope. Substance declaration for your information.
Circularity ProfileENVEOLI111214EN_V1

Environment

Ambient Air Temperature For Operation-40-60 °C
Permissible Ambient Air Temperature Around The Device60-70 °C at Uc
Height162 mm
Net Weight3.43 kg
Ambient Air Temperature For Storage-60-80 °C
Protective TreatmentTH
Ip Degree Of ProtectionIP2X front face with shrouds IEC 60529 || IP2X front face with shrouds VDE 0106
Operating Altitude9842.52 ft (3000 m) without derating
Width163.3 mm
Depth171 mm

Docs