TeSys F contactor - 3P (3 NO) - AC-3 - <= 440 V 185 A - coil 110 V AC

Manufactured by:
Schneider Electric
Schneider electric

B8e2731a9727376070c0fa6591e167c26b44bd9a medium
Nuova Elva code
LC1F185F7
Manufacturer code
LC1F185F7
Availability
Send request for quotation

TeSys F contactor, 3 poles (3NO), 185A/690V AC-3, for motor applications up to 90kW@400V. It provides a low sealed consumption 110V 40-400Hz AC coil, bolt terminals for bars or cables with lugs. For high operating rates until 2400 cycles/hour and environments until 55°C, it procures high reliability and durability. It makes installation and maintenance easy thanks to its drawer-mounted coil and a large choice of add-on blocks and accessories (to be ordered separately). Multi standards certified (IEC, UL, CSA, CCC, EAC, Marine), Green Premium compliant (RoHS/REACh).

Specifications

CertificationsABS
Contact Configuration3 NO
Depth181 mm
Height174 mm
Impedance0.33 MOhm - Ith 275 A 50 Hz
Net Weight4.65 kg
StandardEN 60947-1
Storage Temperature-60-80 °C
Warranty Length18 months
Width168.5 mm

Specifications

[Uc] Control Circuit Voltage110 V AC 40...400 Hz
Device Short NameLC1F
Range Of ProductTeSys F
[Ue] Rated Operational Voltage<= 460 V DC || <= 690 V AC 50/60 Hz
Contactor Applicationmotor control || resistive load
Product Or Component Typecontactor
RangeTeSys
Utilisation CategoryAC-1 || AC-3
[Ie] Rated Operational Current275 A 40 °C) <= 440 V AC-1 || 185 A 55 °C) <= 440 V AC-3
Poles Description3P

Contractual warranty

Warranty18 months

Complementary

Product CertificationsUL || CSA || ABS || LROS (Lloyds register of shipping) || CB || DNV || RINA || RMRoS || BV || UKCA
Rated Breaking Capacity1480 A IEC 60947-4-1
Power Range30-50 kW 200-240 V 3 phase || 55-100 kW 200-240 V 3 phase || 55-100 kW 380-440 V 3 phase || 55-100 kW 480-500 V 3 phase || 110-220 kW 480-500 V 3 phase
Associated Fuse Rating200 A aM <= 440 V || 315 A gG <= 440 V
[Uimp] Rated Impulse Withstand Voltage8 kV
Inrush Power In Va1070-1070 VA, 40...400 Hz 0.9 20 °C)
Connections - Terminalscontrol circuit screw clamp terminals 1 1-4 mm²flexible without cable end || control circuit screw clamp terminals 2 1-4 mm²flexible without cable end || control circuit screw clamp terminals 1 1-4 mm²flexible with cable end || control circuit screw clamp terminals 2 1-2.5 mm²flexible with cable end || control circuit screw clamp terminals 1 1-4 mm²solid without cable end || control circuit screw clamp terminals 2 1-4 mm²solid without cable end || power circuit bar 2 25 x 3 mm || power circuit lugs-ring terminals 1 150-150 mm² || power circuit connector 1 150-150 mm² || power circuit bolted connection
Pole Contact Composition3 NO
Motor Starter Typedirect on-line contactor
Operating Time35 ms closing at Uc) || 130 ms opening at Uc)
Maximum Operating Rate2400 cyc/h 55 °C
Power Dissipation Per Pole12 W AC-3 || 25 W AC-1
Mechanical Durability10 Mcycles
Tightening Torquecontrol circuit 1.2 N.m || power circuit 18 N.m
Compatibility CodeLC1F
Hold-In Power Consumption In Va9.9-9.9 VA, 40...400 Hz 0.9 20 °C)
Overvoltage CategoryIII
Motor Power Kw90 kW 380...400 V AC 50/60 Hz AC-3) || 100 kW 415 V AC 50/60 Hz AC-3) || 100 kW 440 V AC 50/60 Hz AC-3) || 110 kW 500 V AC 50/60 Hz AC-3) || 110 kW 660...690 V AC 50/60 Hz AC-3) || 55 kW 220...230 V AC 50/60 Hz AC-3) || 33 kW 400 V AC 50/60 Hz AC-4)
[Ui] Rated Insulation Voltage1000 V IEC 60947-4-1 || 1500 V VDE 0110 group C
[Icw] Rated Short-Time Withstand Current1500 A 40 °C - 10 s || 920 A 40 °C - 30 s || 740 A 40 °C - 1 min || 500 A 40 °C - 3 min || 400 A 40 °C - 10 min
Heat Dissipation8-9.8 W
Average Impedance0.33 mOhm - Ith 275 A 50 Hz
[Ith] Conventional Free Air Thermal Current275 A 40 °C
Control Circuit Voltage Limitsoperational 0.85...1.1 Uc 40...400 Hz 55 °C) || drop-out 0.2...0.55 Uc 40...400 Hz 55 °C)
StandardsEN 60947-4-1 || IEC 60947-4-1 || EN 60947-1 || IEC 60947-1 || JIS C8201-4-1
Mounting Supportplate
Control Circuit TypeAC 40...400 Hz
Contactor Coil Voltage110 V AC standard

Offer Sustainability

Rohs Exemption InformationYes
Circularity ProfileENVEOLI100418
Eu Rohs DirectiveCompliant
Mercury FreeYes
Environmental DisclosureENVPEP080208EN
Sustainable Offer StatusGreen Premium product
Pvc FreeYes
Reach RegulationReference contains Substances of Very High Concern above the threshold
California Proposition 65WARNING: This product can expose you to chemicals including: Lead and lead compounds, which is known to the State of California to cause cancer and birth defects or other reproductive harm. For more information go to www.P65Warnings.ca.gov
WeeeThe product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins.
China Rohs RegulationProduct out of China RoHS scope. Substance declaration for your information.

Environment

Ambient Air Temperature For Operation-5-55 °C
Permissible Ambient Air Temperature Around The Device-40-70 °C
Height174 mm
Net Weight4.65 kg
Ambient Air Temperature For Storage-60-80 °C
Protective TreatmentTH
Ip Degree Of ProtectionIP2X front face with shrouds IEC 60529 || IP2X front face with shrouds VDE 0106
Operating Altitude9842.52 ft (3000 m) without derating
Width168.5 mm
Depth181 mm

Docs


Frequently bought together


Similar items


Request a quote