TeSys F contactor - 3P (3 NO) - AC-3 - <= 440 V 330 A - coil 110 V AC
- Manufactured by:
- Schneider Electric
TeSys F contactor, 3 poles (3NO), 330A/1000V AC-3, for motor applications up to 160kW@400V. It provides a low sealed consumption 110V 40-400Hz AC coil, bolt terminals for bars or cables with lugs. For high operating rates until 2400 cycles/hour and environments until 55°C, it procures high reliability and durability. It makes installation and maintenance easy thanks to its drawer-mounted coil and a large choice of add-on blocks and accessories (to be ordered separately). Multi standards certified (IEC, UL, CSA, CCC, EAC, Marine), Green Premium compliant (RoHS/REACh).
Specifications
Certifications | ABS |
---|---|
Contact Configuration | 3 NO |
Depth | 219 mm |
Height | 206 mm |
Impedance | 0.28 MOhm - Ith 400 A 50 Hz |
Net Weight | 8.6 kg |
Standard | EN 60947-1 |
Storage Temperature | -60-80 °C |
Warranty Length | 18 months |
Width | 213 mm |
Specifications | |
[Uc] Control Circuit Voltage | 110 V AC 40...400 Hz |
Device Short Name | LC1F |
Range Of Product | TeSys F |
[Ue] Rated Operational Voltage | <= 1000 V AC 50/60 Hz || <= 460 V DC |
Contactor Application | motor control || resistive load |
Product Or Component Type | contactor |
Range | TeSys |
Utilisation Category | AC-4 || AC-1 || AC-3 |
[Ie] Rated Operational Current | 400 A 40 °C) <= 440 V AC AC-1 || 330 A 55 °C) <= 440 V AC AC-3 |
Poles Description | 3P |
Contractual warranty | |
Warranty | 18 months |
Complementary | |
Product Certifications | BV || DNV || CSA || ABS || UL || CB || RMRoS || LROS (Lloyds register of shipping) || RINA || UKCA |
Rated Breaking Capacity | 2640 A IEC 60947-4-1 |
Power Range | 55-100 kW 200-240 V 3 phase || 110-220 kW 480-500 V 3 phase || 110-220 kW 380-440 V 3 phase |
Associated Fuse Rating | 400 A aM <= 440 V || 500 A gG <= 440 V |
[Uimp] Rated Impulse Withstand Voltage | 8 kV |
Inrush Power In Va | 650-650 VA, 40...400 Hz 0.9 20 °C) |
Connections - Terminals | control circuit screw clamp terminals 1 1-4 mm²flexible without cable end || control circuit screw clamp terminals 2 1-4 mm²flexible without cable end || control circuit screw clamp terminals 1 1-4 mm²flexible with cable end || control circuit screw clamp terminals 2 1-2.5 mm²flexible with cable end || control circuit screw clamp terminals 1 1-4 mm²solid without cable end || control circuit screw clamp terminals 2 1-4 mm²solid without cable end || power circuit lugs-ring terminals 1 240-240 mm² || power circuit bar 2 30 x 5 mm || power circuit bolted connection |
Pole Contact Composition | 3 NO |
Motor Starter Type | direct on-line contactor |
Operating Time | 40...65 ms closing || 100...170 ms opening |
Maximum Operating Rate | 2400 cyc/h 55 °C |
Power Dissipation Per Pole | 44 W AC-1 || 31 W AC-3 |
Mechanical Durability | 10 Mcycles |
Tightening Torque | control circuit 1.2 N.m || power circuit 35 N.m |
Compatibility Code | LC1F |
Hold-In Power Consumption In Va | 10-10 VA, 40...400 Hz 0.9 20 °C) |
Overvoltage Category | III |
Motor Power Kw | 160 kW 380...400 V AC 50/60 Hz AC-3) || 180 kW 415 V AC 50/60 Hz AC-3) || 200 kW 440 V AC 50/60 Hz AC-3) || 200 kW 500 V AC 50/60 Hz AC-3) || 220 kW 660...690 V AC 50/60 Hz AC-3) || 160 kW 1000 V AC 50/60 Hz AC-3) || 100 kW 220...230 V AC 50/60 Hz AC-3) || 59 kW 400 V AC 50/60 Hz AC-4) |
[Ui] Rated Insulation Voltage | 1000 V IEC 60947-4-1 || 1500 V VDE 0110 group C |
[Icw] Rated Short-Time Withstand Current | 2650 A 40 °C - 10 s || 1800 A 40 °C - 30 s || 1300 A 40 °C - 1 min || 900 A 40 °C - 3 min || 750 A 40 °C - 10 min |
Heat Dissipation | 8-8 W |
Average Impedance | 0.28 mOhm - Ith 400 A 50 Hz |
[Ith] Conventional Free Air Thermal Current | 400 A 40 °C |
Control Circuit Voltage Limits | operational 0.85...1.1 Uc 40...400 Hz 55 °C) || drop-out 0.35...0.55 Uc 40...400 Hz 55 °C) |
Standards | EN 60947-1 || JIS C8201-4-1 || EN 60947-4-1 || IEC 60947-4-1 || IEC 60947-1 |
Mounting Support | plate |
Control Circuit Type | AC 40...400 Hz |
Contactor Coil Voltage | 110 V AC standard |
Offer Sustainability | |
Rohs Exemption Information | Yes |
Eu Rohs Directive | Compliant |
Mercury Free | Yes |
Environmental Disclosure | ENVPEP1505009EN |
Sustainable Offer Status | Green Premium product |
Reach Regulation | Reference contains Substances of Very High Concern above the threshold |
California Proposition 65 | WARNING: This product can expose you to chemicals including: Lead and lead compounds, which is known to the State of California to cause cancer and birth defects or other reproductive harm. For more information go to www.P65Warnings.ca.gov |
Weee | The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins. |
China Rohs Regulation | Product out of China RoHS scope. Substance declaration for your information. |
Circularity Profile | ENVEOLI1505009EN |
Environment | |
Ambient Air Temperature For Operation | -5-55 °C |
Permissible Ambient Air Temperature Around The Device | -40-70 °C |
Height | 206 mm |
Net Weight | 8.6 kg |
Ambient Air Temperature For Storage | -60-80 °C |
Protective Treatment | TH |
Ip Degree Of Protection | IP20 front face with shrouds IEC 60529 || IP20 front face with shrouds VDE 0106 |
Operating Altitude | 9842.52 ft (3000 m) without derating |
Width | 213 mm |
Depth | 219 mm |