Contactor, TeSys K, 3P, AC-3, lt or eq to 440V 9A, 1 NO aux., 380 to 400VAC coil

Manufactured by:
Schneider Electric
Schneider electric

7fdbd0dac366454800e9556992d03c5b1c51a2ae medium
Price (VAT excluded)
€ 38.84
Nuova Elva code
LC1K0910Q7
Manufacturer code
LC1K0910Q7
Availability
Send request for quotation

TeSys K contactor, 3 poles (3NO), for motor control applications up to 9A/690V AC-3 (4kW@400V), and for non-inductive load control applications up to 20A/690V AC-1. It provides a 380-400V 50/60Hz AC coil, 1NO built-in auxiliary contact, connection by screw clamp terminals. For operating rates until 600 cycles/hour and environments until 50°C, it procures reliability and durability to standard applications. Very compact (45mm width), DIN-rail mounting or screw fixing. Multi standards certified (IEC, UL, CSA, CCC, EAC), Green Premium compliant (RoHS/REACh).

Specifications

CertificationsCB Scheme
Contact Configuration1 NO
Impedance3 MOhm - Ith 20 A 50 Hz Power Circuit
Net Weight0.18 kg
StandardCSA C22.2 No 60947-4-1
Storage Temperature-50-80 °C
Warranty Length18 months

Specifications

Contactor Applicationmotor control || resistive load
Product Or Component Typecontactor
Product NameTeSys K
RangeTeSys
Device Applicationcontrol

Contractual warranty

Warranty18 months

Complementary

Minimum Switching Current5 mA signalling circuit
Safety Reliability LevelB10d = 1369863 cycles contactor with nominal load EN/ISO 13849-1 || B10d = 20000000 cycles contactor with mechanical load EN/ISO 13849-1
Insulation Resistance> 10 MOhm signalling circuit
Rated Breaking Capacity110 A 415 V IEC 60947 || 110 A 440 V IEC 60947 || 80 A 500 V IEC 60947 || 110 A 220...230 V IEC 60947 || 110 A 380...400 V IEC 60947 || 70 A 660...690 V IEC 60947
Irms Rated Making Capacity110 A AC power circuit NF C 63-110 || 110 A AC power circuit IEC 60947 || 110 A AC signalling circuit IEC 60947
Motor Power Kw2.2 kW 220...230 V AC 50/60 Hz AC-3 || 4 kW 380...415 V AC 50/60 Hz AC-3 || 4 kW 440 V AC 50/60 Hz AC-3 || 4 kW 480 V AC 50/60 Hz AC-3 || 4 kW 500...600 V AC 50/60 Hz AC-3 || 4 kW 660...690 V AC 50/60 Hz AC-3 || 2.2 kW 400 V AC 50/60 Hz AC-4 || 2.2 kW 220...230 V AC 50/60 Hz AC-3e || 4 kW 380...415 V AC 50/60 Hz AC-3e || 4 kW 440 V AC 50/60 Hz AC-3e || 4 kW 480 V AC 50/60 Hz AC-3e || 4 kW 500...600 V AC 50/60 Hz AC-3e || 4 kW 660...690 V AC 50/60 Hz AC-3e
Associated Fuse Rating25 A gG <= 440 V power circuit || 25 A aM power circuit || 10 A gG signalling circuit IEC 60947 || 10 A gG signalling circuit VDE 0660
Net Weight0.18 kg
Inrush Power In Va30-30 VA 20 °C)
Pole Contact Composition3 NO
Utilisation CategoryAC-1 || AC-4 || AC-3 || AC-3e
[Uc] Control Circuit Voltage380...400 V AC 50/60 Hz
[Ie] Rated Operational Current20 A 50 °C) <= 440 V AC AC-1 power circuit || 9 A<= 440 V AC AC-3 power circuit || 16 A 70 °C) 690 V AC AC-1 power circuit || 9 A<= 440 V AC AC-3e power circuit
Minimum Switching Voltage17 V signalling circuit
Maximum Operating Rate3600 cyc/h
Signalling Circuit Frequency<= 400 Hz
Auxiliary Contacts Typeinstantaneous 1 NO
Poles Description3P
Hold-In Power Consumption In Va4.5-4.5 VA 20 °C)
Operating Time10...20 ms coil de-energisation and NO opening || 10...20 ms coil energisation and NO closing
Overvoltage CategoryIII
Heat Dissipation1.3-1.3 W
Mechanical Robustnessshocks contactor closed, on X axis10 Gn for 11 ms IEC 60068-2-27 || shocks contactor closed, on Y axis15 Gn for 11 ms IEC 60068-2-27 || shocks contactor closed, on Z axis15 Gn for 11 ms IEC 60068-2-27 || shocks contactor opened, on X axis6 Gn for 11 ms IEC 60068-2-27 || shocks contactor opened, on Y axis10 Gn for 11 ms IEC 60068-2-27 || shocks contactor opened, on Z axis10 Gn for 11 ms IEC 60068-2-27 || vibrations contactor closed4 Gn, 5...300 Hz IEC 60068-2-6 || vibrations contactor opened2 Gn, 5...300 Hz IEC 60068-2-6
Average Impedance3 mOhm - Ith 20 A 50 Hz power circuit
Auxiliary Contact Composition1 NO
Control Circuit Voltage Limitsoperational 0.85...1.1 Uc 50 °C) || drop-out 0.2...0.75 Uc 50 °C)
Non Overlap Distance0.5 mm
[Ith] Conventional Free Air Thermal Current20 A 50 °C power circuit || 10 A 50 °C signalling circuit
Control Circuit TypeAC 50/60 Hz

Offer Sustainability

Rohs Exemption InformationYes
China Rohs RegulationPro-active China RoHS declaration (out of China RoHS legal scope)
Circularity ProfileENVEOLI1503003EN
Eu Rohs DirectiveCompliant
Mercury FreeYes
Environmental DisclosureENVPEP1503003EN
Sustainable Offer StatusGreen Premium product
Toxic Heavy Metal FreeYes
Reach RegulationFree of Substances of Very High Concern above the threshold
California Proposition 65WARNING: This product can expose you to chemicals including: Antimony oxide & Antimony trioxide, which is known to the State of California to cause cancer. For more information go to www.P65Warnings.ca.gov
Reach Free Of SvhcYes
WeeeThe product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins.

Environment

Product CertificationsCB Scheme || CCC || UL || CSA || EAC || CE || UKCA
StandardsEN/IEC 60947-4-1 || GB/T 14048.4 || UL 60947-4-1 || CSA C22.2 No 60947-4-1 || JIS C8201-4-1
Flame RetardanceV1 conforming to UL 94 || requirement 2 conforming to NF F 16-101 || requirement 2 conforming to NF F 16-102
Ambient Air Temperature For Storage-50-80 °C
Protective TreatmentTC IEC 60068 || TC DIN 50016
Operating Altitude6561.68 ft (2000 m) without derating

Docs