TeSys Deca reversing contactor - 3P(3 NO) - AC-3 - <= 440 V 9 A - 24 V DC coil

Manufactured by:
Schneider Electric
Schneider electric

D9c9206628693cc52a36eebf7d3c3d21bf590e5f medium
Nuova Elva code
LC2D093BL
Manufacturer code
LC2D093BL
Availability
Send request for quotation

TeSys D reversing contactor, 3 poles (3NO), for motor control applications up to 12A/690V AC-3 (5.5kW@400V). It provides 440V 50/60Hz AC coils, 2NO+2NC built-in auxiliary contacts (NC mirror certified), connection by screw clamp terminals. For operating rates until 3600 cycles/hour and environments until 60°C, it procures high reliability and durability. Compact (90mm width), DIN-rail mounting or screw fixing. With pre-wired reversing power connections, mechanical interlock (without electrical interlocking). Multi standards certified (IEC, UL, CSA, CCC, EAC, Marine), Green Premium compliant (RoHS/REACh).

Specifications

CertificationsBV
Contact Configuration1 NO + 1 NC
Depth95 mm
Height99 mm
Impedance2.5 MOhm - Ith 16 A 50 Hz Power Circuit
Net Weight1.017 kg
StandardCSA C22.2 No 14
Storage Temperature-60-80 °C
Warranty Length18 months
Width90 mm

Specifications

Product CertificationsDNV || CSA || CCC || UL || GL || LROS (Lloyds register of shipping) || BV || RINA || GOST || UKCA
Control Circuit TypeDC low consumption
StandardsCSA C22.2 No 14 || EN 60947-4-1 || EN 60947-5-1 || IEC 60947-4-1 || IEC 60947-5-1 || UL 508 || IEC 60335-1
Safety Reliability LevelB10d = 1369863 cycles contactor with nominal load EN/ISO 13849-1 || B10d = 20000000 cycles contactor with mechanical load EN/ISO 13849-1
Contactor Applicationresistive load || motor control
Rated Breaking Capacity250 A 440 V power circuit IEC 60947
Product Or Component Typereversing contactor
Irms Rated Making Capacity250 A 440 V power circuit IEC 60947 || 140 A AC signalling circuit IEC 60947-5-1 || 250 A DC signalling circuit IEC 60947-5-1
Product NameTeSys D || TeSys Deca
Associated Fuse Rating25 A gG <= 690 V type 1 power circuit || 20 A gG <= 690 V type 2 power circuit || 10 A gG signalling circuit IEC 60947-5-1
[Uimp] Rated Impulse Withstand Voltage6 kV IEC 60947
Interlocking Typemechanical
Connections - Terminalspower circuit spring terminals 1 2.5-2.5 mm²flexible without cable end || power circuit spring terminals 2 2.5-2.5 mm²flexible without cable end || control circuit spring terminals 1 2.5-2.5 mm²flexible without cable end || control circuit spring terminals 2 2.5-2.5 mm²flexible without cable end
RangeTeSys || TeSys Deca
Pole Contact Composition3 NO
Device Presentationpreassembled with reversing power busbar
Utilisation CategoryAC-1 || AC-3
[Ie] Rated Operational Current9 A 60 °C) <= 440 V AC AC-3 power circuit || 16 A 60 °C) <= 440 V AC AC-1 power circuit
Maximum Operating Rate3600 cyc/h 60 °C
Tightening Torquecontrol circuit 1.7 N.m screw clamp terminals pozidriv No 2 || power circuit 2.5 N.m screw clamp terminals pozidriv No 2
Electrical Durability0.6 Mcycles 25 A AC-1 <= 440 V || 2 Mcycles 9 A AC-3 <= 440 V
Mechanical Durability30 Mcycles
[Uc] Control Circuit Voltage24 V DC
Poles Description3P
Operating Time65.45...88.55 ms closing || 20...30 ms opening
Overvoltage CategoryIII
Motor Power Kw2.2 kW 220...230 V AC 50 Hz || 4 kW 380...400 V AC 50 Hz || 4 kW 415...440 V AC 50 Hz || 5.5 kW 500 V AC 50 Hz || 5.5 kW 660...690 V AC 50 Hz
Maximum Horse Power Rating0.5 hp 115 V at AC 60 Hz for 1 phase || 1 hp 230/240 V at AC 60 Hz for 1 phase || 2 hp 200/208 V at AC 60 Hz for 3 phase || 2 hp 230/240 V at AC 60 Hz for 3 phase || 5 hp 460/480 V at AC 60 Hz for 3 phase || 7.5 hp 575/600 V at AC 60 Hz for 3 phase
[Ui] Rated Insulation Voltagepower circuit 690 V IEC 60947-4-1 || power circuit 600 V CSA || power circuit 600 V UL || signalling circuit 690 V IEC 60947-1 || signalling circuit 600 V CSA || signalling circuit 600 V UL
Device Short NameLC2D
[Icw] Rated Short-Time Withstand Current30 A 40 °C - 10 min power circuit || 61 A 40 °C - 1 min power circuit || 105 A 40 °C - 10 s power circuit || 210 A 40 °C - 1 s power circuit || 100 A - 1 s signalling circuit || 120 A - 500 ms signalling circuit || 140 A - 100 ms signalling circuit
Protective Coverwith
[Ue] Rated Operational Voltagepower circuit <= 690 V AC 25...400 Hz || power circuit <= 300 V DC
Power Dissipation Per Pole0.2 W AC-3 || 1.56 W AC-1
Average Impedance2.5 mOhm - Ith 16 A 50 Hz power circuit
Auxiliary Contact Composition1 NO + 1 NC
[Ith] Conventional Free Air Thermal Current16 A 60 °C power circuit || 10 A 60 °C signalling circuit
Mounting Supportplate || rail

Contractual warranty

Warranty18 months

Complementary

Non-Overlap Time1.5 ms on de-energisation between NC and NO contact || 1.5 ms on energisation between NC and NO contact
Inrush Power In W2.4-2.4 W 20 °C)
Auxiliary Contacts Typemechanically linked 1 NO + 1 NC IEC 60947-5-1 || mirror contact 1 NC IEC 60947-4-1
Minimum Switching Current5 mA signalling circuit
Control Circuit Voltage Limits0.1...0.3 Uc -40-70 °C drop-out DC || 0.8...1.25 Uc -40-60 °C operational DC || 1...1.25 Uc 60-70 °C operational DC
Hold-In Power Consumption In W2.4-2.4 W 20 °C
Insulation Resistance> 10 MOhm signalling circuit
Coil Technologybuilt-in bidirectional peak limiting diode suppressor
Time Constant40 ms
Minimum Switching Voltage17 V signalling circuit
Signalling Circuit Frequency25...400 Hz

Offer Sustainability

Rohs Exemption InformationYes
China Rohs RegulationProduct out of China RoHS scope. Substance declaration for your information.
Circularity ProfileENVEOLI1102030EN
Eu Rohs DirectiveCompliant
Mercury FreeYes
Environmental DisclosureENVPEP110230EN
Sustainable Offer StatusGreen Premium product
Pvc FreeYes
Toxic Heavy Metal FreeYes
Reach RegulationFree of Substances of Very High Concern above the threshold
California Proposition 65WARNING: This product can expose you to chemicals including: Antimony oxide & Antimony trioxide, which is known to the State of California to cause cancer. For more information go to www.P65Warnings.ca.gov
Reach Free Of SvhcYes

Environment

Mechanical Robustnessvibrations contactor open2 Gn, 5...300 Hz || vibrations contactor closed4 Gn, 5...300 Hz || shocks contactor open10 Gn for 11 ms || shocks contactor closed15 Gn for 11 ms
Ip Degree Of ProtectionIP20 front face IEC 60529
Operating Altitude0...9842.52 ft (0...3000 m)
Fire Resistance850 °C IEC 60695-2-1
Width90 mm
Depth95 mm
Ambient Air Temperature For Operation-40-60 °C || 60-70 °C with derating
Height99 mm
Climatic WithstandIACS E10 || IEC 60947-1 Annex Q category D
Pollution Degree3
Net Weight1.017 kg
Flame RetardanceV1 conforming to UL 94
Ambient Air Temperature For Storage-60-80 °C
Protective TreatmentTH IEC 60068-2-30