TeSys Deca reversing contactor - 3P(3 NO) - AC-3 - <= 440 V 9 A - 115 V AC coil

Manufactured by:
Schneider Electric
Schneider electric

668d40c6d6d6f95638b2eeaca3f783e5d4c52c52 medium
Price (VAT excluded)
€ 116.60
Nuova Elva code
LC2D09FE7
Manufacturer code
LC2D09FE7
Availability
Send request for quotation

TeSys D reversing contactor, 3 poles (3NO), for motor control applications up to 9A/690V AC-3 (4kW@400V). It provides 115V 50/60Hz AC coils, 2NO+2NC built-in auxiliary contacts (NC mirror certified), connection by screw clamp terminals. For operating rates until 3600 cycles/hour and environments until 60°C, it procures high reliability and durability. Compact (90mm width), DIN-rail mounting or screw fixing. With pre-wired reversing power connections, mechanical interlock (without electrical interlocking). Multi standards certified (IEC, UL, CSA, CCC, EAC, Marine), Green Premium compliant (RoHS/REACh).

Specifications

CertificationsBV
Contact Configuration1 NO + 1 NC
Depth86 mm
Height77 mm
Impedance2.5 MOhm - Ith 25 A 50 Hz Power Circuit
Net Weight0.687 kg
StandardCSA C22.2 No 14
Storage Temperature-60-80 °C
Warranty Length18 months
Width90 mm

Specifications

Product CertificationsDNV || CSA || CCC || UL || GL || LROS (Lloyds register of shipping) || BV || RINA || GOST || UKCA
Control Circuit TypeAC 50/60 Hz
StandardsCSA C22.2 No 14 || EN 60947-4-1 || EN 60947-5-1 || IEC 60947-4-1 || IEC 60947-5-1 || UL 508 || IEC 60335-1
Safety Reliability LevelB10d = 1369863 cycles contactor with nominal load EN/ISO 13849-1 || B10d = 20000000 cycles contactor with mechanical load EN/ISO 13849-1
Contactor Applicationresistive load || motor control
Rated Breaking Capacity250 A 440 V power circuit IEC 60947
Product Or Component Typereversing contactor
Irms Rated Making Capacity250 A 440 V power circuit IEC 60947 || 140 A AC signalling circuit IEC 60947-5-1 || 250 A DC signalling circuit IEC 60947-5-1
Product NameTeSys Deca
Associated Fuse Rating25 A gG <= 690 V type 1 power circuit || 20 A gG <= 690 V type 2 power circuit || 10 A gG signalling circuit IEC 60947-5-1
[Uimp] Rated Impulse Withstand Voltage6 kV IEC 60947
Interlocking Typemechanical
Connections - Terminalspower circuit screw clamp terminals 1 1-4 mm²flexible without cable end || power circuit screw clamp terminals 2 1-4 mm²flexible without cable end || power circuit screw clamp terminals 1 1-4 mm²flexible with cable end || power circuit screw clamp terminals 2 1-2.5 mm²flexible with cable end || power circuit screw clamp terminals 1 1-4 mm²solid || power circuit screw clamp terminals 2 1-4 mm²solid || control circuit screw clamp terminals 1 1-4 mm²flexible without cable end || control circuit screw clamp terminals 2 1-4 mm²flexible without cable end || control circuit screw clamp terminals 1 1-4 mm²flexible with cable end || control circuit screw clamp terminals 2 1-2.5 mm²flexible with cable end || control circuit screw clamp terminals 1 1-4 mm²solid || control circuit screw clamp terminals 2 1-4 mm²solid
RangeTeSys || TeSys Deca
Pole Contact Composition3 NO
Device Presentationpreassembled with reversing power busbar
Utilisation CategoryAC-3 || AC-1
[Ie] Rated Operational Current9 A 60 °C) <= 440 V AC AC-3 power circuit || 25 A 60 °C) <= 440 V AC AC-1 power circuit
Maximum Operating Rate3600 cyc/h 60 °C
Tightening Torquepower circuit 1.7 N.m screw clamp terminals flat Ø 6 mm || power circuit 1.7 N.m screw clamp terminals Philips No 2 || control circuit 1.7 N.m screw clamp terminals flat Ø 6 mm || control circuit 1.7 N.m screw clamp terminals Philips No 2 || control circuit 1.7 N.m screw clamp terminals pozidriv No 2 || power circuit 2.5 N.m screw clamp terminals pozidriv No 2
Electrical Durability0.6 Mcycles 25 A AC-1 <= 440 V || 2 Mcycles 9 A AC-3 <= 440 V
Mechanical Durability15 Mcycles
[Uc] Control Circuit Voltage115 V AC 50/60 Hz
Poles Description3P
Operating Time12...22 ms closing || 4...19 ms opening
Overvoltage CategoryIII
Motor Power Kw2.2 kW 220...230 V AC 50 Hz || 4 kW 380...400 V AC 50 Hz || 4 kW 415...440 V AC 50 Hz || 5.5 kW 500 V AC 50 Hz || 5.5 kW 660...690 V AC 50 Hz
Maximum Horse Power Rating0.5 hp 115 V at AC 60 Hz for 1 phase || 1 hp 230/240 V at AC 60 Hz for 1 phase || 2 hp 200/208 V at AC 60 Hz for 3 phase || 2 hp 230/240 V at AC 60 Hz for 3 phase || 5 hp 460/480 V at AC 60 Hz for 3 phase || 7.5 hp 575/600 V at AC 60 Hz for 3 phase
[Ui] Rated Insulation Voltagepower circuit 690 V IEC 60947-4-1 || power circuit 600 V CSA || power circuit 600 V UL || signalling circuit 690 V IEC 60947-1 || signalling circuit 600 V CSA || signalling circuit 600 V UL
Device Short NameLC2D
[Icw] Rated Short-Time Withstand Current30 A 40 °C - 10 min power circuit || 61 A 40 °C - 1 min power circuit || 105 A 40 °C - 10 s power circuit || 210 A 40 °C - 1 s power circuit || 100 A - 1 s signalling circuit || 120 A - 500 ms signalling circuit || 140 A - 100 ms signalling circuit
Protective Coverwith
[Ue] Rated Operational Voltagepower circuit <= 690 V AC 25...400 Hz || power circuit <= 300 V DC
Power Dissipation Per Pole0.2 W AC-3 || 1.56 W AC-1
Average Impedance2.5 mOhm - Ith 25 A 50 Hz power circuit
Auxiliary Contact Composition1 NO + 1 NC
[Ith] Conventional Free Air Thermal Current10 A 60 °C signalling circuit || 25 A 60 °C power circuit
Mounting Supportplate || rail

Contractual warranty

Warranty18 months

Complementary

Non-Overlap Time1.5 ms on de-energisation between NC and NO contact || 1.5 ms on energisation between NC and NO contact
Hold-In Power Consumption In Va7.5-7.5 VA 60 Hz 0.3 20 °C) || 7-7 VA 50 Hz 0.3 20 °C)
Heat Dissipation2-3 W 50/60 Hz
Minimum Switching Current5 mA signalling circuit
Control Circuit Voltage Limits0.3...0.6 Uc -40-70 °C drop-out AC 50/60 Hz || 0.8...1.1 Uc -40-60 °C operational AC 50 Hz || 0.85...1.1 Uc -40-60 °C operational AC 60 Hz || 1...1.1 Uc 60-70 °C operational AC 50/60 Hz
Insulation Resistance> 10 MOhm signalling circuit
Inrush Power In Va70-70 VA 60 Hz 0.75 20 °C) || 70-70 VA 50 Hz 0.75 20 °C)
Coil Technologywithout built-in suppressor module
Minimum Switching Voltage17 V signalling circuit
Signalling Circuit Frequency25...400 Hz
Auxiliary Contacts Typemechanically linked 1 NO + 1 NC IEC 60947-5-1 || mirror contact 1 NC IEC 60947-4-1

Offer Sustainability

Rohs Exemption InformationYes
WeeeThe product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins.
China Rohs RegulationPro-active China RoHS declaration (out of China RoHS legal scope)
Circularity ProfileENVEOLI1501004
Eu Rohs DirectiveCompliant
Mercury FreeYes
Environmental DisclosureENVPEP1501004
Sustainable Offer StatusGreen Premium product
Pvc FreeYes
Toxic Heavy Metal FreeYes
Reach RegulationFree of Substances of Very High Concern above the threshold
California Proposition 65WARNING: This product can expose you to chemicals including: Antimony oxide & Antimony trioxide, which is known to the State of California to cause cancer. For more information go to www.P65Warnings.ca.gov
Reach Free Of SvhcYes

Environment

Mechanical Robustnessvibrations contactor open2 Gn, 5...300 Hz || vibrations contactor closed4 Gn, 5...300 Hz || shocks contactor open10 Gn for 11 ms || shocks contactor closed15 Gn for 11 ms
Ip Degree Of ProtectionIP20 front face IEC 60529
Operating Altitude0...9842.52 ft (0...3000 m)
Fire Resistance850 °C IEC 60695-2-1
Width90 mm
Depth86 mm
Ambient Air Temperature For Operation-40-60 °C || 60-70 °C with derating
Height77 mm
Climatic WithstandIACS E10 || IEC 60947-1 Annex Q category D
Pollution Degree3
Net Weight0.687 kg
Flame RetardanceV1 conforming to UL 94
Ambient Air Temperature For Storage-60-80 °C
Protective TreatmentTH IEC 60068-2-30

Docs


Frequently bought together


Other Schneider Electric items

Request a quote