Differential thermal overload relays, TeSys K, 2.6 to 3.7 A, class 10A

Manufactured by:
Schneider Electric
Schneider electric

F7024cacc987913f64001f037c11e43612bf31cb medium
Price (VAT excluded)
€ 49.55
Nuova Elva code
LR2K0310
Manufacturer code
LR2K0310
Availability
Standard lead time: 7 days

TeSys K overload relays are designed to be used with TeSys K contactors to make a motor starter. These differential thermal overload relays detect over currents in the lines to the motor. When an overcurrent is detected the overload relay working with the contactor will disconnect the power to the motor. This will minimize the damage to the motor windings. This overload relay has an adjustable trip current rating of 2.6 to 3.7 amperes. This trip current rating is calibrated per Class 10A. Mounting on DIN rail, separated from the contactor, with use of a terminal block LA7K0064 (to be ordered separately). Multi standards certified (IEC, UL, CSA, CCC, EAC), Green Premium compliant (RoHs/Reach).

Specifications

CertificationsCSA
Contact Configuration1 NO + 1 NC
Depth65 mm
Height58 mm
Net Weight0.145 kg
StandardBS 4941
Storage Temperature-40-70 °C
Warranty Length18 months
Width45 mm

Specifications

Network TypeDC || AC
Device Short NameLR2K
Thermal Protection Adjustment Range2.6-3.7 A
Relay Applicationmotor protection
Product Or Component Typedifferential thermal overload relay
Product NameTeSys LRK
Thermal Overload Classclass 10A IEC 60947-4-1
RangeTeSys
[Ui] Rated Insulation Voltagepower circuit 690 V BS 4941 || power circuit 690 V IEC 60947 || power circuit 750 V VDE 0110 group C || power circuit 600 V CSA C22.2 No 14
Product CompatibilityLC7K || LP1K || LP4K || LC1K

Contractual warranty

Warranty18 months

Complementary

Network Frequency<= 400 Hz
[Uimp] Rated Impulse Withstand Voltage6 kV
Power Dissipation Per Pole2 W
Local Signallingtrip indicator Yellow)
Tightening Torque1.3 N.m screw clamp terminals Philips No 2 || 1.3 N.m screw clamp terminals flat Ø 6 mm || 1.3 N.m screw clamp terminals pozidriv No 2
Control TypeRed push-button trip test function || Blue push-button stop and manual reset || selector switch manual or automatic reset
Mounting Supportunder contactor || plate, with specific accessories || rail, with specific accessories
Width45 mm
Depth65 mm
Height58 mm
[Ith] Conventional Free Air Thermal Current6 A signalling circuit
Auxiliary Contact Composition1 NO + 1 NC
Phase Failure Sensitivityyes IEC 60947-4-1
[Ue] Rated Operational Voltage<= 690 V power circuit || 690 V AC AC-15 signalling circuit || 250 V DC DC-13 signalling circuit
Associated Fuse Rating6 A gG signalling circuit VDE 0660 || 6 A gG signalling circuit IEC 60947
Net Weight0.145 kg
Connections - Terminalsscrew clamp terminals 1 1.5-4 mm²solid || screw clamp terminals 2 1.5-4 mm²solid || screw clamp terminals 1 0.75-4 mm²flexible without cable end || screw clamp terminals 2 0.75-4 mm²flexible without cable end || screw clamp terminals 1 0.34-2.5 mm²flexible with cable end || screw clamp terminals 2 0.34-1.5 mm²flexible with cable end

Offer Sustainability

Rohs Exemption InformationYes
Circularity ProfileENVEOLI2211018
Eu Rohs DirectiveCompliant
Mercury FreeYes
Environmental DisclosureENVPEP2211018
Sustainable Offer StatusGreen Premium product
Reach RegulationFree of Substances of Very High Concern above the threshold
California Proposition 65WARNING: This product can expose you to chemicals including: Antimony oxide & Antimony trioxide, which is known to the State of California to cause cancer. For more information go to www.P65Warnings.ca.gov
Reach Free Of SvhcYes
WeeeThe product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins.
China Rohs RegulationProduct out of China RoHS scope. Substance declaration for your information.

Environment

Product CertificationsUL || CSA || UKCA
Fire Resistance850 °C IEC 60695-2-1
Mechanical Robustnessshocks NO contact10 Gn for 11 ms IEC 60068-2-27 || shocks NC contact10 Gn for 11 ms IEC 60068-2-27 || vibrations NO contact2 Gn, 5...300 Hz IEC 60068-2-6 || vibrations NC contact2 Gn, 5...300 Hz IEC 60068-2-6
StandardsIEC 60947 || VDE 0660 || BS 4941 || NF C 63-650
Ambient Air Temperature For Operation-20-55 °C without derating IEC 60947 || -30-60 °C with derating IEC 60947
Ip Degree Of ProtectionIP2X conforming to IEC 60529
Flame RetardanceV1 conforming to UL 94 || requirement 2 conforming to NF F 16-101 || requirement 2 conforming to NF F 16-102
Ambient Air Temperature For Storage-40-70 °C
Protective TreatmentTC IEC 60068 || TC DIN 50016
Operating Altitude6561.68 ft (2000 m) without derating

Docs


Frequently bought together


Other Schneider Electric items

Request a quote