TeSys Deca thermal overload relays , 17...25A , class 10A

Manufactured by:
Schneider Electric
Schneider electric

Aa53f0b4cf3430945c2baa102ec768812db74001 medium
Price (VAT excluded)
€ 114.66
Nuova Elva code
LRD3322
Manufacturer code
LRD3322
Availability
Send request for quotation

LRD3322 is a TeSys LRD thermal overload relay from Schneider Electric to be used with a TeSys D contactor. It protects motors 9-11kW@400V thanks to a thermal range 17-25A, a tripping class 10A and phase unbalance protection. LRD3322 is a TeSys LRD thermal overload relay from Schneider Electric for direct mounting on TeSys D contactors. With a thermal setting range 17-25A, a tripping class 10A and phase unbalance detection, it protects motors 11kW@400V. It provides manual test & reset buttons, automatic reset, trip auxiliary contact and flag indicator. Available worldwide, it is multi-standards certified (IEC, UL, CSA, CCC, EAC, Marine) and Green Premium compliant (RoHs/Reach). Thermal overload protection relay, bimetallic type, with phase unbalance protection (differential). Direct mounting on the bottom terminals of a Tesys contactor LC1D80 and D95 to form a compact starter. Light and compact, 70mm wide. Temperature compensated for a good accuracy of the protection. Manual control with test & reset buttons, manual / automatic reset selector. Trip signaling with 1NO+1NC auxiliary contacts and trip flag indicator. Can be completed with terminal blocks for separate mounting (LAD7B, LAD96) and remote control devices (LAD703, LA7D03).

Specifications

CertificationsATEX INERIS
Contact Configuration1 NO + 1 NC
Depth115 mm
Height81 mm
Net Weight0.51 kg
StandardCSA C22.2 No 60947-4-1
Storage Temperature-60-70 °C
Warranty Length18 months
Width70 mm

Specifications

Network TypeDC || AC
Device Short NameLRD
Thermal Protection Adjustment Range17-25 A
Relay Applicationmotor protection
Product Or Component Typedifferential thermal overload relay
Product NameTeSys LRD || TeSys Deca
Thermal Overload Classclass 10A IEC 60947-4-1
RangeTeSys
[Ui] Rated Insulation Voltagepower circuit 1000 V IEC 60947-4-1 || power circuit 600 V CSA || power circuit 600 V UL
Product CompatibilityLC1D80 || LC1D95

Contractual warranty

Warranty18 months

Complementary

Network Frequency0...400 Hz
[Uimp] Rated Impulse Withstand Voltage6 kV IEC 60947-1
Permissible Current0.72 A 500 V AC-15 signalling circuit || 0.06 A 440 V DC-13 signalling circuit
Tripping Threshold1.14 +/- 0.06 Ir IEC 60947-4-1
Tightening Torquecontrol circuit 1.7 N.m screw clamp terminals || power circuit 9 N.m screw clamp terminals
Control TypeRed push-button stop || Blue push-button reset
Mounting Supportplate, with specific accessories || rail, with specific accessories || under contactor
Width70 mm
Depth115 mm
Temperature Compensation-20-60 °C
Height81 mm
[Ith] Conventional Free Air Thermal Current5 A signalling circuit
Auxiliary Contact Composition1 NO + 1 NC
Connections - Terminalspower circuit screw clamp terminals 1 4-35 mm² flexible without cable end || power circuit screw clamp terminals 1 4-35 mm² flexible with cable end || power circuit screw clamp terminals 1 4-35 mm² solid without cable end || control circuit screw clamp terminals 2 1-2.5 mm² flexible without cable end || control circuit screw clamp terminals 2 1-2.5 mm² flexible with cable end || control circuit screw clamp terminals 2 1-2.5 mm² solid without cable end
Phase Failure Sensitivitytripping current 130 % of Ir on two phase, the last one at 0
[Ue] Rated Operational Voltage1000 V AC 0...400 Hz power circuit IEC 60947-4-1
Associated Fuse Rating4 A gG signalling circuit || 4 A BS signalling circuit
Net Weight0.51 kg

Offer Sustainability

Rohs Exemption InformationYes
Circularity ProfileENVEOLI1101001
Eu Rohs DirectiveCompliant
Mercury FreeYes
Environmental DisclosureENVPEP110101EN
Sustainable Offer StatusGreen Premium product
Toxic Heavy Metal FreeYes
Reach RegulationFree of Substances of Very High Concern above the threshold
California Proposition 65WARNING: This product can expose you to chemicals including: Antimony oxide & Antimony trioxide, which is known to the State of California to cause cancer. For more information go to www.P65Warnings.ca.gov
Reach Free Of SvhcYes
China Rohs RegulationPro-active China RoHS declaration (out of China RoHS legal scope)

Environment

Product CertificationsIEC || UL || CSA || CCC || EAC || ATEX INERIS || UKCA
Mechanical Robustnessvibrations6 Gn IEC 60068-2-6 || shocks15 Gn for 11 ms IEC 60068-2-7
StandardsEN/IEC 60947-4-1 || EN/IEC 60947-5-1 || UL 60947-4-1 || UL 60947-5-1 || CSA C22.2 No 60947-4-1 || CSA C22.2 No 60947-5-1 || GB/T 14048.4 || GB/T 14048.5 || EN 50495
Climatic WithstandIACS E10
Ambient Air Temperature For Operation-20-60 °C without derating IEC 60947-4-1
Dielectric Strength2.2 kV 50 Hz IEC 60947-1
Ip Degree Of ProtectionIP20 conforming to IEC 60529
Flame RetardanceV1 conforming to UL 94
Ambient Air Temperature For Storage-60-70 °C

Docs