TeSys D, replaement coil, for LC1D09 to 38 contactors and CAD relays, 24 VAC 50/60 Hz coil
- Manufactured by:
- Schneider Electric
TeSys D replacement coils are for replacing the operating coil in a TeSys D contactors with 9 amperes to 38 ampere ratings and Tesys D Relays. This coil has an operating voltage of 24 Vac 50/60 Hz. This coil has an inrush consumption rating of 70 VA and a sealed consumpation rating ofd 7 VA. The 60Hz operating range is 85 to 110% of nomial voltage at 60 degrees C. Green Premium compliant (RoHS/REACh).
Specifications
Net Weight | 0.07 kg |
---|---|
Warranty Length | 18 months |
Specifications | |
Average Resistance | 5.37 Ohm 20 °C |
Device Short Name | LXD1 |
[Uc] Control Circuit Voltage | 24 V AC 50/60 Hz |
Control Circuit Type | AC 50/60 Hz |
Product Or Component Type | contactor coil |
Range | TeSys |
Inductance Of Closed Circuit | 0.22 H |
Maximum Operating Rate | 3600 cyc/h 60 °C |
Mechanical Durability | 15 Mcycles |
Product Compatibility | LC1D09...D38 || CAD || LC1DT20...DT40 |
Contractual warranty | |
Warranty | 18 months |
Complementary | |
Control Circuit Voltage Limits | drop-out 0.3...0.6 Uc 50/60 Hz 60 °C) || operational 0.8...1.1 Uc 50 Hz 60 °C) || operational 0.85...1.1 Uc 60 Hz 60 °C) |
Inrush Power In Va | 70-70 VA 60 Hz 0.75 20 °C) || 70-70 VA 50 Hz 0.75 20 °C) |
Coil Technology | without built-in suppressor module |
Hold-In Power Consumption In Va | 7.5-7.5 VA 60 Hz 0.3 20 °C) || 7-7 VA 50 Hz 0.3 20 °C) |
Heat Dissipation | 2-3 W 50/60 Hz |
Offer Sustainability | |
Rohs Exemption Information | Yes |
Circularity Profile | ENVEOLI100405 |
Eu Rohs Directive | Pro-active compliance (Product out of EU RoHS legal scope) |
Mercury Free | Yes |
Environmental Disclosure | ENVPEP060301EN |
Sustainable Offer Status | Green Premium product |
Pvc Free | Yes |
Toxic Heavy Metal Free | Yes |
Reach Regulation | Reference contains Substances of Very High Concern above the threshold |
California Proposition 65 | WARNING: This product can expose you to chemicals including: Antimony oxide & Antimony trioxide, which is known to the State of California to cause cancer. For more information go to www.P65Warnings.ca.gov |
China Rohs Regulation | Product out of China RoHS scope. Substance declaration for your information. |
Environment | |
Ambient Air Temperature For Operation | -5-60 °C |
Net Weight | 0.07 kg |