ClimaSys standard cooling unit side of enclosure - 380W at 230 V

Manufactured by:
Schneider Electric
Schneider%20electric

791fb28eb94ef7053ef6f9a2bf241c2fbe7f7bd2 medium
Price (VAT excluded)
€ 1726.16
Nuova Elva code
NSYCU400UL
Manufacturer code
NSYCU400UL
Availability
Send request for quotation

Specifications

CertificationsUL
ColorGray RAL 7035)
Depth180 mm
Height460 mm
Input Voltage230 V
Line Rated Current1.6 A
MaterialSteel
Mounting TypeScrews
Net Weight17 kg
Number of Phases1
StandardDIN 3168
Width285 mm

Specifications

Product Destinationfor enclosure
Mounting Locationside
Mounting Modeby screws
Cooling Power820 Btu/h 50/60 Hz L35-L50 || 1300 Btu/h 50/60 Hz L35-L35
Product Or Component Typecooling unit
Product NameCU
Phase1 phase
Type Of Installationindoor
RangeClimaSys
Input Voltage230 V 50/60 Hz

Complementary

Power Consumption In W280 W 50/60 Hz, L35-L35 || 330 W 50/60 Hz, L35-L50
Protection Typethermal protection T 4 A || short-circuit protection (magnetic)
Line Rated Current1.6 A
Type Of Ventilation Filteroptional external circuit filter
Ambient Air Temperature For Operationmaximum 50-50 °C || inside the enclosure 20-46 °C || outside the enclosure 20-50 °C
ColorGray RAL 7035)
Energy Efficiency Ratio1.4
Materialsteel
Net Weight17 kg
Depth180 mm
Control Typeelectronic controller
Noise Level60 dB
Pressure26 bar
Air Flowinternal circuit 280 m3/h 50/60 Hz || external circuit 280 m3/h 50/60 Hz
Cooling Gas TypeR134a 0.16 kg)
Inrush Current6 A
Width285 mm
Height460 mm
Temperature Setting Range20-50 °C

Offer Sustainability

China Rohs RegulationPro-active China RoHS declaration (out of China RoHS legal scope)
Reach Free Of SvhcYes
WeeeThe product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins.
Circularity ProfileENVEOLI2106024EN
Rohs Exemption InformationYes
Mercury FreeYes
Environmental DisclosureENVPEP2106024EN
Sustainable Offer StatusGreen Premium product
Toxic Heavy Metal FreeYes
Eu Rohs DirectiveCompliant
Reach RegulationFree of Substances of Very High Concern above the threshold

Environment

Product CertificationsUL
StandardsDIN 3168
Ip Degree Of ProtectionIP55 IEC 60529 on the internal circuit) || IP34 IEC 60529 on the external circuit)

Docs


Other Schneider Electric items

Request a quote