ClimaSys outdoor cooling unit side of enclosure - 2900W at 400 V

Manufactured by:
Schneider Electric
Schneider%20electric

9140e28931b7a1e828d2731e3d5a2df095d2e65d medium
Price (VAT excluded)
€ 6394.21
Nuova Elva code
NSYCUHD3K3P4
Manufacturer code
NSYCUHD3K3P4
Availability
Send request for quotation

Specifications

CertificationsCE
ColorGray RAL 7035)
Depth336 mm
Height1270 mm
Input Voltage400 V
Line Rated Current2.6 A
MaterialSteel
Mounting TypeScrews
Net Weight84 kg
Number of Phases3
Operating TemperatureInside The Enclosure 20-46 °C || Maximum 55-55 °C || Outside The Enclosure -20-50 °C
StandardEN 378
Width500 mm

Specifications

Product Destinationfor enclosure
Mounting Locationside
Mounting Modeby screws
Cooling Power2900 W 50/60 Hz L35-L35 || 2250 W 50/60 Hz L35-L50
Product Or Component Typecooling unit
Product NameCU
Phase3 phase
Type Of Installationoutdoor
RangeClimaSys
Input Voltage400 V 50/60 Hz

Complementary

Power Consumption In W1220 W 50/60 Hz, L35-L35 || 1440 W 50/60 Hz, L35-L50
Protection Typethermal protection T 6 A || short-circuit protection (magnetic)
Line Rated Current2.6 A
Type Of Ventilation Filteroptional external circuit filter
Ambient Air Temperature For Operationinside the enclosure 20-46 °C || maximum 55-55 °C || outside the enclosure -20-50 °C
ColorGray RAL 7035)
Energy Efficiency Ratio2.4
Materialsteel
Net Weight84 kg
Depth336 mm
Control Typemechanical
Noise Level70 dB EN/ISO 3746
Pressure25 bar
Air Flowinternal circuit 1450 m3/h 50/60 Hz || external circuit 1450 m3/h 50/60 Hz
Cooling Gas TypeR134a 0.84 kg)
Inrush Current14 A
Width500 mm
Height1270 mm
Temperature Setting Range20-50 °C

Offer Sustainability

China Rohs RegulationPro-active China RoHS declaration (out of China RoHS legal scope)
Reach Free Of SvhcYes
WeeeThe product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins.
Circularity ProfileENVEOLI2106024EN
Rohs Exemption InformationYes
Mercury FreeYes
Environmental DisclosureENVPEP2106024EN
Sustainable Offer StatusGreen Premium product
Toxic Heavy Metal FreeYes
Eu Rohs DirectiveCompliant
Reach RegulationFree of Substances of Very High Concern above the threshold

Environment

Product CertificationsCE
Directives2006/42/EC - machinery || 2006/95/EC - low voltage directive || 2004/108/EC - electromagnetic compatibility
StandardsEN/ISO 12100 || EN 60335-1 || EN 60204-1 || EN 60335-2-40 || EN 378
Ip Degree Of ProtectionIP55 IEC 60529 on the internal circuit) || IP34 IEC 60529 on the external circuit)

Docs


Other Schneider Electric items

Request a quote