Load center, QO, 3 phase, 12 spaces, 12 circuits, 125A fixed main lugs, NEMA1, gnd bar, UL

Manufactured by:
Schneider Electric
Schneider electric

1f2c02831fa7b52a11206a62757ab4e734fe7f10 medium
Nuova Elva code
QO312L125G
Availability
Send request for quotation

QO Load Centers offer premium features by allowing QO breakers, ground fault interrupters, arc fault interrupters, and surge arresters to be installed inside. QO Load Centers are designed for residential and industrial use to protect electrical systems, equipment, and people. They are available in both traditional and plug on neutral configurations. There is 3 types of mains available. There is main circuit breaker, main lugs, and generator panel. Single and three phase options are available. The bus bars are tin plated copper and are shielded. Indoor and outdoors enclosures are an option. QO Load Centers enable the use of a full complement of accessories. This 3 phase load center has 12 spaces and 12 circuits. This system provides 125A fixed main lugs in a NEMA 1 enclosure. It also includes a ground bar, and is UL rated.

Specifications

CertificationsUL
Enclosure MaterialWelded Sheet Steel
Height455 mm
Line Rated Current125 A
MaterialTin-Plated Copper
Number of Circuits12
Number of Phases3
Short Circuit Current65 kA
Warranty Length18 months
Width362 mm

Specifications

Range Of ProductQO
Product Or Component TypeLoad Center
Cover Typeorder separately

Contractual warranty

Warranty18 months

Complementary

Height455 mm
Materialtin plated copper busbar
Surface Finishbaked enamel Gray
Line Rated Current125 A
Enclosure Materialwelded sheet steel
Awg GaugeAWG 6...AWG 2/0 aluminium/copper
Width362 mm
Wiring Configuration3-wire || 4-wire
Load Center TypeFixed Mains (lugs)
Device Compositiongrounding bar included (not installed)
Box Number6
Tightening Torquemain lugs 50 lb.in, AWG 6...AWG 2/0, aluminium/copper || Cover 20 lb.in
[Ue] Rated Operational Voltage208Y/120 V AC || 240/120 V delta AC || 240 V delta AC
Electrical Connectionlugs
Number Of Circuits12
Number Of Spaces12
Phase3 phase
Short-Circuit Current65 kA
Number Of Tandem Circuit Breakers0

Offer Sustainability

Rohs Exemption InformationYes
Eu Rohs DirectiveCompliant
Mercury FreeYes
Environmental DisclosureENVPEP2101006
Sustainable Offer StatusGreen Premium product
Toxic Heavy Metal FreeYes
Reach RegulationFree of Substances of Very High Concern above the threshold
California Proposition 65WARNING: This product can expose you to chemicals including: Lead and lead compounds, which is known to the State of California to cause cancer and birth defects or other reproductive harm. For more information go to www.P65Warnings.ca.gov
Reach Free Of SvhcYes
China Rohs RegulationPro-active China RoHS declaration (out of China RoHS legal scope)

Environment

Product CertificationsUL Listed
Nema Degree Of ProtectionNEMA 1 indoor
Ambient Air Temperature For Operation-5 °C || 40 °C