Compact discovery packs, Zelio Logic, smart relay discovery pack, 12 I/O, 24 V DC

Manufactured by:
Schneider Electric
Schneider electric

Be56604800873580bdc05f869888de6c800098f8 medium
Price (VAT excluded)
€ 201.30
Nuova Elva code
SR2PACKBD
Manufacturer code
SR2PACKBD
Availability
Standard lead time: 8 days

This Schneider Electric Zelio Logic SR2 discovery pack compact smart relay / programmable controller uses a supply voltage of 24 volts direct current, has 12 inputs / outputs with screw-clamp terminals and has an integrated LCD display. This compact programmable relay discovery pack is ideal for discovering the Zelio Logic range of programmable smart relays. It has compact form-factor, allowing installation on DIN rail. It also offers simple programming, display and diagnosing of malfunctions display and navigation buttons. Discovery package includes one copy of Zelio Soft and one USB cable to connect the relay to your PC. Simple ladder programming, adapted for non-specialists. Discovery package, coming with Zelio Soft programming software, the simplest way to learn and use this relay. Built-in EEPROM flash memory for data backup up to 10 years, easy-to-recover after a power shortage or incident. The main application of this module is industry and building/service sector. This product is certified by C-Tick, GL, UL, CSA and GOST. It meets EN/IEC 60068-2-6 Fc and EN/IEC 61000-4-11 standards. Easy to use, Zelio Logic provides a real alternative solutions based on cabled logic or specific cards.

Specifications

CertificationsC-tick
Net Weight0.7 kg
Number of Outputs4
StandardEN/IEC 60068-2-27 Ea
Storage Temperature-40-70 °C
Warranty Length18 months

Specifications

Range Of ProductZelio Logic
Number Of Outputs4 relay
Product Or Component Typecompact discovery packs
Discrete Input Number8 EN/IEC 61131-2 type 1

Contractual warranty

Warranty18 months

Complementary

Contacts Type And CompositionNO relay output
Backup Time10 years 25 °C
Clock Drift12 min/year 0-55 °C || 6 s/month 25-25 °C
Analogue Input Typecommon mode
Discrete Input Current4 mA
Current State 1 Guaranteed>= 1.2 mA IB...IG used as discrete input circuit) || >= 2.2 mA I1...IA and IH...IR discrete input circuit)
Response Time10 ms from state 0 to state 1)relay output || 5 ms from state 1 to state 0)relay output
Clockwith
Power Dissipation In W3 W without extension
Local Displaywith
Net Weight0.7 kg
Input Impedance12 kOhm IB...IG used as analogue input circuit || 12 kOhm IB...IG used as discrete input circuit || 7.4 kOhm I1...IA and IH...IR discrete input circuit
Input/Output Number12
Voltage State 0 Guaranteed<= 5 V I1...IA and IH...IR discrete input circuit || <= 5 V IB...IG used as discrete input circuit
Output Voltage Limits24...250 V AC relay output) || 5...30 V DC relay output)
Conversion Timesmart relay cycle time analogue input circuit
Electrical DurabilityAC-12 500000 cycles 230 V, 1.5 A relay output EN/IEC 60947-5-1 || AC-15 500000 cycles 230 V, 0.9 A relay output EN/IEC 60947-5-1 || DC-12 500000 cycles 24 V, 1.5 A relay output EN/IEC 60947-5-1 || DC-13 500000 cycles 24 V, 0.6 A relay output EN/IEC 60947-5-1
Analogue Input Number4
Connections - Terminalsscrew terminals, 1 x 0.2...1 x 2.5 mm² AWG 25...AWG 14) semi-solid || screw terminals, 1 x 0.2...1 x 2.5 mm² AWG 25...AWG 14) solid || screw terminals, 1 x 0.25...1 x 2.5 mm² AWG 24...AWG 14) flexible with cable end || screw terminals, 2 x 0.2...2 x 1.5 mm² AWG 24...AWG 16) solid || screw terminals, 2 x 0.25...2 x 0.75 mm² AWG 24...AWG 18) flexible with cable end
Voltage State 1 Guaranteed>= 15 V I1...IA and IH...IR discrete input circuit || >= 15 V IB...IG used as discrete input circuit
Input Compatibility3-wire proximity sensors PNP discrete input
Current State 0 Guaranteed<= 0.5 mA IB...IG used as discrete input circuit) || <= 0.75 mA I1...IA and IH...IR discrete input circuit)
Discrete Input Typeresistive
Supply Voltage Limits19.2-30 V
Operating Distance10 m between stations, with screened cable (sensor not isolated) analogue input circuit
Overvoltage CategoryIII EN/IEC 60664-1
Mechanical Durability10000000 cycles relay output
Maximum Supply Current100 mA without extension)
Tightening Torque0.5 N.m
Temperature Probe TypeNTC 10k 25 °C || NTC 1000k 25 °C || KTY81 210/220/221/222/250 || Pt 500
Switching Capacity In Ma>= 10 mA 12 V relay output)
Analogue Input Resolution8 bits
[Uimp] Rated Impulse Withstand Voltage4 kVEN/IEC 60947-1 and EN/IEC 60664-1
Analogue Input Range0...10 V || 0...24 V
Operating Rate In Hz0.1 Hz at Ie)relay output || 10 Hz no load)relay output
Counting Frequency1 kHz discrete input
Cycle Time6-90 ms
Kit CompositionSR2B121BD || cable PC SR2USB01 for connection to PC
Reverse Polarity Protectionwith
Maximum Permissible Voltage30 V analogue input circuit
Repeat Accuracy+/- 2 % 55 °C analogue input circuit
[Us] Rated Supply Voltage24 V
Checksprogram memory on each power up
Conversion Error+/- 5 % 25 °C analogue input circuit || +/- 6.2 % 55 °C analogue input circuit
Output Thermal Current8 A for all 4 outputs relay output
Number Or Control Scheme Lines120-120 ladder || 0-200 FBD
Lsb Value39 mV analogue input circuit
Discrete Input Voltage24 V DC

Offer Sustainability

Rohs Exemption InformationYes
Circularity ProfileENVEOLI0604006EN
Eu Rohs DirectivePro-active compliance (Product out of EU RoHS legal scope)
Mercury FreeYes
Environmental DisclosureENVPEP060406EN
Sustainable Offer StatusGreen Premium product
Pvc FreeYes
Reach RegulationReference contains Substances of Very High Concern above the threshold
California Proposition 65WARNING: This product can expose you to chemicals including: Lead and lead compounds, which is known to the State of California to cause cancer and birth defects or other reproductive harm. For more information go to www.P65Warnings.ca.gov
WeeeThe product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins.
China Rohs RegulationX

Environment

Product CertificationsCSA || C-tick || UL || GOST || GL
Relative Humidity95-95 % without condensation or dripping water
Maximum Altitude Transport3048 m
Operating Altitude6561.68 ft (2000 m)
StandardsEN/IEC 61000-4-4 level 3 || EN/IEC 61000-4-12 || EN/IEC 61000-4-5 || EN/IEC 60068-2-6 Fc || EN/IEC 61000-4-2 level 3 || EN/IEC 61000-4-6 level 3 || EN/IEC 61000-4-3 || EN/IEC 61000-4-11 || EN/IEC 60068-2-27 Ea
Disturbance Radiated/Conductedclass B EN 55022-11 group 1
Ambient Air Temperature For Operation-20-40 °C in non-ventilated enclosure IEC 60068-2-1 and IEC 60068-2-2 || -20-55 °C IEC 60068-2-1 and IEC 60068-2-2
Immunity To Microbreaks1 ms
Environmental CharacteristicEMC directive EN/IEC 61000-6-2 || EMC directive EN/IEC 61000-6-3 || EMC directive EN/IEC 61000-6-4 || EMC directive EN/IEC 61131-2 zone B || low voltage directive EN/IEC 61131-2
Ip Degree Of ProtectionIP20 IEC 60529 terminal block) || IP40 IEC 60529 front panel)
Pollution Degree2 EN/IEC 61131-2
Ambient Air Temperature For Storage-40-70 °C

Docs


Frequently bought together