Safety Reliability Data | MTTFd = 1875.9 years || B10d = 1731395 |
---|
Maximum Voltage Drop | <1.15 V on-state |
---|
Connections - Terminals | screw terminals 0.2...3.3 mm², AWG 24...AWG 12) with cable end input || screw terminals 0.5...5.26 mm², AWG 20...AWG 10) with cable end output || screw terminals 0.2...3.3 mm², AWG 24...AWG 12) without cable end input || screw terminals 0.5...8.26 mm², AWG 20...AWG 8) without cable end output || forked type tag connectors 9.2 x 4 mm input || ring lugs 9.2 x 4 mm input || forked type tag connectors 11.7 x 4.5 mm output || ring lugs 11.7 x 4.5 mm output |
---|
Dielectric Strength | 4 kV AC for input/output || 4 kV AC for input or output to case |
---|
Response Time | 0.5 cycle (turn-on) || 0.5 cycle (turn-off) |
---|
Surge Current | 1750 A 16.6 ms |
---|
Load Current | 0.15-125 A |
---|
Local Signalling | LED, steady, green ON status control input/test button actuated || LED, steady, amber ON status load || LED, flashing, amber control input to energise load || LED, steady, red open-circuit control input || LED, flashing, red load cut-off/short-circuit |
---|
Net Weight | 97.1 g |
---|
[Uimp] Rated Impulse Withstand Voltage | 6 kV output to case || 6 kV input to output |
---|
Minimum Switching Voltage | 4 V DC turn-on |
---|
Cos Phi | 0.5-0.5 (with maximum load) |
---|
Maximum Leakage Current | 1 mA off-state |
---|
Ip Degree Of Protection | IP20 |
---|
Device Presentation | complete product |
---|
Electromagnetic Compatibility | electrostatic discharge 6 kV criteria A contact discharge conforming to IEC 61000-4-2 || electrostatic discharge 8 kV criteria A air discharge conforming to IEC 61000-4-2 || radiated radio-frequency electromagnetic field immunity test criteria A output ports conforming to IEC 61000-4-3 || radiated radio-frequency electromagnetic field immunity test criteria B alarm port conforming to IEC 61000-4-3 || electrical fast transient/burst immunity test 1 kV, 5/100 kHz criteria B output ports conforming to IEC 61000-4-4 || surge immunity test 1 kV criteria A output ports line to line conforming to IEC 61000-4-5 || surge immunity test 2 kV criteria A output ports line to earth conforming to IEC 61000-4-5 |
---|
Absolute Maximum Voltage | 1200 V |
---|
Dv/Dt | 500 V/µs off-state at maximum voltage |
---|
Maximum Output Current | 30 mA 32 V DC |
---|
Maximum Switching Voltage | 1 V DC turn-off |
---|
Capacitance Unbalance | 8 pF for input/output |
---|
Minimum Load | 150 mA |
---|
[Uc] Control Circuit Voltage | 4...32 V DC |
---|
Input Current Limits | 7-12 mA |
---|
Protection Device Type | type 1 - 80 A miniature circuit breaker (MCB) B || type 2 - 63 A miniature circuit breaker (MCB) B |
---|
Auxiliary Connection Terminal | screw-type connector, 0.5...1.5 mm² AWG 20...AWG 16)slotted Philips |
---|
Output Voltage | 48...660 V AC |
---|
Maximum Horse Power Rating | 2 hp 120 V AC || 5 hp 240 V AC || 10 hp 480 V AC |
---|
Tightening Torque | 1.5...1.7 N.m for input || 2...2.2 N.m for output || 17.7...19.47 lb.in for output || 13.27...15.04 lb.in for input || 0.5...0.6 N.m for auxillary terminal || 4.4...5.3 lb.in for auxillary terminal |
---|
Insulation Resistance | 1000 MOhm at 500 V DC |
---|
Thermal Resitance | 0.22 °C/W junction to case |
---|
Maximum I²T For Fusing | 12709 A².s for 8.33 ms at 60 Hz || 13950 A².s for 10 ms at 50 Hz |
---|