Control station, Harmony XALD, XALK, plastic, yellow lid, 1 red mushroom push button 40mm, turn to release, 2NC

Manufactured by:
Schneider Electric
Schneider electric

A02816aaf009ec77ef5301429364f236a057c25f medium
Price (VAT excluded)
€ 39.81
Nuova Elva code
XALK178F
Manufacturer code
XALK178F
Availability
Send request for quotation

This Harmony XALK yellow (RAL1021) control station is ideal for a clearly visible emergency shutdown of any machine. This yellow control station enables machine builders to easily add control and signalling functionality on their machines, with permanent modifications or damage to their machine body. It is designed for simple and mass production machines, textiles, packaging, handling small lifting systems, control of garage doors, rolling shutters, smoke extraction vents. It offers emergency stop and emergency switching off functions. It is impact resistant, dust resistant, water resistant, corrosion resistant, and vibration resistant thanks to its IP69 / IP67 / IP66 / IP69K, making it ideal for operation in harsh environments.

Specifications

Contact MaterialSilver Alloy
MaterialPolycarbonate
Net Weight0.194 kg
StandardCSA C22.2 No 14
Storage Temperature-40-70 °C
Warranty Length18 months

Specifications

Control Station Applicationemergency switching off function || emergency stop function
Operator Profile1 mushroom head push-button
Colour Of Coveryellow RAL 1021)
Contact Operationslow-break
Device Short NameXALK
Product Destinationfor XB5 Ø 22 mm control and signalling units
Resetturn to release
Range Of ProductHarmony XALK
Colour Of Base Of Enclosurelight grey RAL 7035)
Control Station Composition1 mushroom head Ø 40 mm push-button, red 2 NC unmarked
Operators Descriptionred unmarked 2 NC
Product Or Component Typecomplete control station
Materialpolycarbonate

Contractual warranty

Warranty18 months

Complementary

Short-Circuit Protection10 A cartridge fuse gG EN/IEC 60947-5-1
Resistance To High Pressure Washer7000000 Pa 55 °C 0.1 m
Electrical Durability1000000 cycles, AC-15, 2 A 230 V 3600 cyc/h 0.5 EN/IEC 60947-5-1 appendix C || 1000000 cycles, AC-15, 3 A 120 V 3600 cyc/h 0.5 EN/IEC 60947-5-1 appendix C || 1000000 cycles, AC-15, 4 A 24 V 3600 cyc/h 0.5 EN/IEC 60947-5-1 appendix C || 1000000 cycles, DC-13, 0.2 A 110 V 3600 cyc/h 0.5 EN/IEC 60947-5-1 appendix C || 1000000 cycles, DC-13, 0.5 A 24 V 3600 cyc/h 0.5 EN/IEC 60947-5-1 appendix C
Connections - Terminalsscrew clamp terminals, <= 2 x 1.5 mm² with cable end EN/IEC 60947-1 || screw clamp terminals, >= 1 x 0.22 mm² without cable end EN/IEC 60947-1
[Ui] Rated Insulation Voltage600 V 3)EN/IEC 60947-1
[Ie] Rated Operational Current3 A 240 V, AC-15, A600 EN/IEC 60947-5-1 || 6 A 120 V, AC-15, A600 EN/IEC 60947-5-1 || 0.1 A 600 V, DC-13, Q600 EN/IEC 60947-5-1 || 0.27 A 250 V, DC-13, Q600 EN/IEC 60947-5-1 || 0.55 A 125 V, DC-13, Q600 EN/IEC 60947-5-1 || 1.2 A 600 V, AC-15, A600 EN/IEC 60947-5-1
Mechanical Durability300000 cycles
Electrical Reliabilityλ < 10exp(-6) 5 V, 1 mA EN/IEC 60947-5-4 || λ < 10exp(-8) 17 V, 5 mA EN/IEC 60947-5-4
Tightening Torque0.8-1.2 N.m EN/IEC 60947-1
Shape Of Screw Headcross Philips no 1 || cross pozidriv No 1 || slotted flat Ø 4 mm || slotted flat Ø 5.5 mm
Operating Force44 N
Operating Travel1.5 mm NC changing electrical state) || 4.3 mm total travel)
Contacts Materialsilver alloy (Ag/Ni)
Positive Openingwith EN/IEC 60947-5-1 appendix K
[Ith] Conventional Free Air Thermal Current10 A EN/IEC 60947-5-1
Cable Entry1 knock-out for cable entry 0-14 mm || 2 knock-outs for Pg 13 cable gland and ISO M20 0-12 mm
Net Weight0.194 kg
[Uimp] Rated Impulse Withstand Voltage6 kV EN/IEC 60947-1

Offer Sustainability

Rohs Exemption InformationYes
Circularity ProfileENVEOLI1806010EN
Eu Rohs DirectivePro-active compliance (Product out of EU RoHS legal scope)
Mercury FreeYes
Environmental DisclosureENVPEP1806010EN
Sustainable Offer StatusGreen Premium product
Toxic Heavy Metal FreeYes
Reach RegulationFree of Substances of Very High Concern above the threshold
Reach Free Of SvhcYes
WeeeThe product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins.
China Rohs RegulationX

Environment

Ik Degree Of ProtectionIK03 EN 50102
Protective TreatmentTH
Ambient Air Temperature For Operation-40-70 °C
StandardsEN/IEC 60204-1 || JIS C 4520 || EN/IEC 60947-5-1 || IEC 60364-5-53 || EN/ISO 13850 || CSA C22.2 No 14 || UL 508 || EN/IEC 60947-5-5 || EN/IEC 60947-5-4 || EN/IEC 60947-1
Shock Resistance30 gn 18 ms) half sine wave acceleration IEC 60068-2-27 || 50 gn 11 ms) half sine wave acceleration IEC 60068-2-27
Vibration Resistance5 gn 12-500 Hz)IEC 60068-2-6
Ip Degree Of ProtectionIP66 IEC 60529 || IP67 || IP69 || IP69K
Ambient Air Temperature For Storage-40-70 °C
Overvoltage Categoryclass II IEC 60536
Nema Degree Of ProtectionNEMA 13 || NEMA 4X