Emergency stop switching off, Harmony XB4, metal, red mushroom 40mm, 22mm, trigger latching turn to release, 2NC+1NO

Manufactured by:
Schneider Electric
Schneider electric

B52301d1380b87a52b730329fad9ac0220902801 medium
Price (VAT excluded)
€ 42.20
Nuova Elva code
XB4BS84441
Manufacturer code
XB4BS84441
Availability
Send request for quotation

This Harmony XB4 emergency stop / shutdown 40mm mushroom head modular red push button operates with a latched turn to release mechanism. It has a metal bezel. This emergency stop / shutdown button, also called EMS (Emergency Machine Stop) and EMO (Emergency Off), is easily installed into a standard 22mm diameter cut-outs and connected with simple screw-clamp connections. It is clearly distinguishable visually at a distance thanks to a clear color and a prominent 40mm mushroom shape. It is impact resistant, dust resistant, water resistant and vibration resistant thanks to its IP66, making it ideal for operation in harsh environments.

Specifications

Bezel MaterialChromium Plated Metal
CertificationsBV
Contact MaterialSilver Alloy
Depth82 mm
Height47 mm
StandardCSA C22.2 No 14
Storage Temperature-40-70 °C
Warranty Length18 months
Width40 mm

Specifications

Resetturn to release
Sale Per Indivisible Quantity1
Bezel Materialchromium plated metal
Contact Operationslow-break
Operator Profilered mushroom Ø 40 mm, unmarked
Device Short NameXB4
Range Of ProductHarmony XB4
Mounting Diameter22 mm
Type Of Operatortrigger action and mechanical latching
Product Or Component Typeemergency stop push-button || emergency switching off push-button
Shape Of Signaling Unit Headround
Fixing Collar Materialzamak
Head Typestandard
Connections - Terminalsscrew clamp terminals, <= 2 x 1.5 mm² with cable end EN 60947-1 || screw clamp terminals, >= 1 x 0.22 mm² without cable end EN 60947-1

Contractual warranty

Warranty18 months

Complementary

Contacts Usagestandard contacts
Device Presentationcomplete product
Resistance To High Pressure Washer7000000 Pa 55 °C 0.1 m
Electrical Durability1000000 cycles, AC-15, 2 A 230 V 3600 cyc/h 0.5 EN/IEC 60947-5-1 appendix C || 1000000 cycles, AC-15, 3 A 120 V 3600 cyc/h 0.5 EN/IEC 60947-5-1 appendix C || 1000000 cycles, AC-15, 4 A 24 V 3600 cyc/h 0.5 EN/IEC 60947-5-1 appendix C || 1000000 cycles, DC-13, 0.2 A 110 V 3600 cyc/h 0.5 EN/IEC 60947-5-1 appendix C || 1000000 cycles, DC-13, 0.5 A 24 V 3600 cyc/h 0.5 EN/IEC 60947-5-1 appendix C
[Ui] Rated Insulation Voltage600 V 3)EN 60947-1
[Ie] Rated Operational Current3 A 240 V, AC-15, A600 EN/IEC 60947-5-1 || 6 A 120 V, AC-15, A600 EN/IEC 60947-5-1 || 0.1 A 600 V, DC-13, Q600 EN/IEC 60947-5-1 || 0.27 A 250 V, DC-13, Q600 EN/IEC 60947-5-1 || 0.55 A 125 V, DC-13, Q600 EN/IEC 60947-5-1 || 1.2 A 600 V, AC-15, A600 EN/IEC 60947-5-1
Mechanical Durability300000 cycles
Electrical Reliabilityλ < 10exp(-6) 5 V 1 mA in clean environment EN/IEC 60947-5-4 || λ < 10exp(-8) 17 V 5 mA in clean environment EN/IEC 60947-5-4
Width40 mm
Depth82 mm
Tightening Torque0.8-1.2 N.m EN 60947-1
Height47 mm
Shape Of Screw Headcross Philips no 1 || cross pozidriv No 1 || slotted flat Ø 4 mm || slotted flat Ø 5.5 mm
Terminals Description Iso N°1(13-14)NO
Short-Circuit Protection10 A cartridge fuse gG EN/IEC 60947-5-1
Operating Travel1.5 mm NC changing electrical state) || 2.6 mm NO changing electrical state) || 4.3 mm total travel)
Contacts Materialsilver alloy (Ag/Ni)
Positive Openingwith EN/IEC 60947-5-1 appendix K
[Ith] Conventional Free Air Thermal Current10 A EN/IEC 60947-5-1
[Uimp] Rated Impulse Withstand Voltage6 kV EN 60947-1

Offer Sustainability

Rohs Exemption InformationYes
China Rohs RegulationX
Circularity ProfileENVEOLI2201004EN
Eu Rohs DirectivePro-active compliance (Product out of EU RoHS legal scope)
Mercury FreeYes
Environmental DisclosureENVPEP2201004EN
Sustainable Offer StatusGreen Premium product
Toxic Heavy Metal FreeYes
Reach RegulationFree of Substances of Very High Concern above the threshold
California Proposition 65WARNING: This product can expose you to chemicals including: Di-isodecyl phthalate (DIDP), which is known to the State of California to cause birth defects or other reproductive harm. For more information go to www.P65Warnings.ca.gov
Reach Free Of SvhcYes
WeeeThe product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins.

Environment

Product CertificationsUL Listed || BV || CSA || LROS (Lloyds register of shipping) || DNV || GL
Electrical Shock Protection Classclass I IEC 60536
Protective TreatmentTH
Ik Degree Of ProtectionIK06 IEC 50102
Ambient Air Temperature For Operation-40-70 °C
StandardsEN/ISO 13850 || EN/IEC 60947-1 || EN/IEC 60947-5-5 || IEC 60364-5-53 || EN/IEC 60947-5-4 || EN/IEC 60204-1 || UL 508 || EN/IEC 60947-5-1 || CSA C22.2 No 14 || JIS C8201-5-1 || JIS C8201-1
Shock Resistance30 gn 18 ms) half sine wave acceleration IEC 60068-2-27 || 50 gn 11 ms) half sine wave acceleration IEC 60068-2-27
Vibration Resistance5 gn 2-500 Hz)IEC 60068-2-6
Ip Degree Of ProtectionIP66 IEC 60529 || IP69 || IP69K
Ambient Air Temperature For Storage-40-70 °C
Nema Degree Of ProtectionNEMA 13 || NEMA 4X

Docs


Frequently bought together


Similar items


Request a quote