2 Digital output pairs expansion modules with screw term
- Manufactured by:
- Schneider Electric
- Price (VAT excluded)
- € 280.37
- Nuova Elva code
- XPSMCMDO0002
- Manufacturer code
- XPSMCMDO0002
- Availability
- 1 in stock
This Modicon MCM safe output expansion module has 2 start/restart interlock inputs, 2 output OSSD pairs and 2 status outputs and is fitted with captive screw clamp terminals. It is designed to monitor remotely your safe I/O. It is furnished with screw clamp terminals, removable terminal block for electrical connection. It is an IP20 rated product. This safe I/O module figures configurable filters and delays for each single input, configurable output activation and de-activation delays, independent control of pairs of outputs, and configurable diagnostic output signals. This module figures LEDs on its front face, displaying the status (power supply, run, internal or external errors, input and output status). This safe I/O module is connected to the safety controller via the backplane expansion connector. It weighs 0.23kg. Its dimension are 22.5mm (Depth), 99mm (Height) and 114.5mm (Width). Its housing is red. It is powered with 24 VDC. It is ideal for monitoring safety functions such as emergency stop, guard monitoring, perimeter guarding, position monitoring, speed monitoring and enabling movement. This safe I/O module is certified by RCM, CULus and TÜV. It can reach such safety levels as category 4 conforming to EN/ISO 13849-1, PLe conforming to EN/ISO 13849-1, Type 4 conforming to EN/IEC 61496-1, and SILCL3 conforming to IEC 62061. Compatible accessories for Modicon MCM module are a memory card and the backplane connector. The module instals on Omega 35mm DIN rail conforming to EN 50022. The Modicon MCM modular safety controller system provide flexibility and scalability from 8 inputs, 2 dual/4 single channel outputs up to 128 inputs, 16 dual/32 single channel outputs, up to 32 or 48 diagnostic status outputs. Modicon MCM modular safety controller system are designed to monitor multiple safety functions on and around a machine to minimise the risk of people accessing the dangerous moving parts of the machine.
Specifications
Certifications | CULus |
---|---|
Depth | 22.5 mm |
Height | 99 mm |
Net Weight | 0.23 kg |
Number of Outputs | 2 |
Standard | EN/IEC 61508 |
Storage Temperature | -20-85 °C |
Width | 114.5 mm |
Specifications | |
Discrete Output Type | PNP |
Function Of Module | monitoring safety actuators discrete output |
Discrete Input Type | isolated |
Range Of Product | Preventa Safety automation |
Number Of Outputs | 2 safety outputs OSSD contactor/drive connection || 2 configurable diagnostic connection |
Product Or Component Type | safe output expansion module |
Number Of Inputs | 2 digital external device monitoring |
[Us] Rated Supply Voltage | 24 V - 20...20 % DC |
Electrical Connection | screw terminal |
Device Short Name | XPSMCM |
Complementary | |
Connections - Terminals | 2 captive screw clamp terminals, removable terminal block || 1 captive screw clamp terminals, removable terminal block |
Net Weight | 0.23 kg |
Discrete Output Voltage | 24 V DC |
Power Dissipation In W | 3 W |
Quality Labels | CE |
Mounting Support | omega 35 mm DIN rail EN 50022 |
Width | 114.5 mm |
Discrete Output Current | 400 mA || 100 mA |
Depth | 22.5 mm |
Safety Level | can reach category 4 EN/ISO 13849-1 || can reach PL = e EN/ISO 13849-1 || can reach SIL 3 EN/IEC 61508 || SILCL 3 IEC 62061 |
Output Load | 60 Ohm |
Number Of Terminal Blocks | 4 |
Height | 99 mm |
Integrated Connection Type | backplane expansion bus |
Cable Cross Section | 0.2-1.5 mm² - AWG 24...AWG 16 flexible without cable end || 0.2-2.5 mm² - AWG 24...AWG 14 flexible without cable end || 0.25-1 mm² - AWG 23...AWG 18 flexible with cable end, without bezel || 0.25-2.5 mm² - AWG 23...AWG 14 flexible with cable end, with bezel || 0.25-2.5 mm² - AWG 23...AWG 14 flexible with cable end, without bezel || 0.5-1.5 mm² - AWG 20...AWG 16 flexible with cable end, with double bezel || 0.2-1 mm² - AWG 24...AWG 18 solid without cable end || 0.2-2.5 mm² - AWG 24...AWG 14 solid without cable end |
Load Type | resistive load |
Discrete Input Voltage | 24 V DC |
Power Consumption In W | 3 W |
Local Signalling | 1 LED green PWR power ON || 1 LED green RUN RUN (status) || 1 LED red E IN internal error || 1 LED red E EX external error || 2 LEDs orange ADDR node address || 2 LEDs green/red OUT output status || 2 LEDs yellow RST restart signal || 2 LEDs yellow STATUS output status |
Offer Sustainability | |
Rohs Exemption Information | Yes |
China Rohs Regulation | X |
Circularity Profile | ENVEOLI1409010EN |
Eu Rohs Directive | Pro-active compliance (Product out of EU RoHS legal scope) |
Mercury Free | Yes |
Environmental Disclosure | ENVPEP1409010EN |
Sustainable Offer Status | Green Premium product |
Pvc Free | Yes |
Reach Regulation | Free of Substances of Very High Concern above the threshold |
California Proposition 65 | WARNING: This product can expose you to chemicals including: Lead and lead compounds, which is known to the State of California to cause cancer and birth defects or other reproductive harm. For more information go to www.P65Warnings.ca.gov |
Reach Free Of Svhc | Yes |
Weee | The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins. |
Environment | |
Product Certifications | TÜV || cULus || RCM |
Ambient Air Temperature For Storage | -20-85 °C |
Service Life | 20 year(s) |
Relative Humidity | 10-95 % |
Safety Reliability Data | DC > 99 % || MTTFd < 100 years high || PFHd = 3.16E-9 1/h |
Overvoltage Category | II |
Insulation | 250 V AC between power supply and housing EN/IEC 61800-5-1 |
Standards | EN/ISO 13849-1 || EN/IEC 61800-5-1 || IEC 62061 || EN/IEC 61508 |
Pollution Degree | 2 |
Ambient Air Temperature For Operation | -10-55 °C |
Electromagnetic Compatibility | electrostatic discharge immunity test 6 kV on contact) EN/IEC 61000-4-2 || electrostatic discharge immunity test 20 kV on air) EN/IEC 61000-4-2 || susceptibility to electromagnetic fields 10 V/m 80...1000 MHz) EN/IEC 61000-4-3 || susceptibility to electromagnetic fields 30 V/m 1.4 GHz...2 GHz) EN/IEC 61000-4-3 |
Shock Resistance | 10 gn 16 ms) 1000 shocks on each axis EN/IEC 61496-1 |
Vibration Resistance | +/-0.35 mm 10-55 Hz)EN/IEC 61496-1 |
[Uimp] Rated Impulse Withstand Voltage | 4 kV EN/IEC 61800-5-1 |
Ip Degree Of Protection | IP20 enclosure) |